FORM 160.87-OM1
ISSUE DATE: 8/24/2018
JOHNSON CONTROLS
28
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Economizer Motor Run (LED)
Illuminates when the Economizer Compressor is cur-
rently running.
Economizer Discharge Temperature
Displays the temperature of the refrigerant vapor at the
discharge of the Economizer Compressor before the re-
frigerant enters the condenser.
Economizer % Full Load Amps
Displays the percentage of full load amps (FLA) uti-
lized by the Economizer Motor.
Economizer Current Limit
Displays the Economizer active motor current limit in
percentage at Full Load Amps.
Economizer PRV Position
Displays how open the PRV vanes are in percentage
from 100% (open) to 0% (closed).
Economizer Pressure
Displays the pressure within the Economizer.
Economizer Saturation
Displays the saturation temperature within the Econo-
mizer calculated from the Economizer Pressure.
Economizer Setpoint
Displays the Level setpoint as set in the Economizer
screen.
Economizer Level
Displays the refrigerant level in the Economizer.
Oil Sump Temperature
Displays the temperature of the oil in the sump.
Leaving Condenser Liquid Temperature
Displays the temperature of the liquid as it leaves the
condenser tube bundle.
Entering Condenser Liquid Temperature
Displays the temperature of the liquid as it enters the
condenser.
Condenser Pressure
Displays the pressure of the refrigerant within the con-
denser.
Condenser Saturation Temperature
Displays the saturation temperature of the refrigerant
within the Condenser calculated from the Condenser
Pressure.
Condenser Drop Leg
Displays the subcooled temperature at the condenser.
Condenser Level
Displays the refrigerant level within the condenser.
Leaving Chilled Liquid Temperature
Displays the leaving chilled liquid temperature at the
evaporator.
Entering Chilled Liquid Temperature
Displays the entering chilled liquid temperature at the
evaporator.
Chilled Liquid Setpoint
Displays the Leaving Chilled Liquid Setpoint which is
set either locally on the Setpoint Screen or remotely
from a BAS.
Evaporator Pressure
Displays the evaporator pressure.
Evaporator Saturation Temperature
Shows the saturation temperature of the Evaporator
calculated form the Evaporator Pressure.
NAVIGATION
Home
Access Level Required: VIEW
Returns user to HOME Screen.
System
Access Level Required: SERVICE
Returns user to SYSTEM Screen.