SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
43
FORM 160.87-OM1
ISSUE DATE: 8/24/2018
2
Capacity Control
Access Level Required: SERVICE
Navigates to CAPACITY CONTROL Screen.
Motor
Access Level Required: SERVICE
Moves to a subscreen that allows programming of the
Hot Gas Bypass control setpoints and manual control
of the Hot Gas Bypass valve. Only displayed if Hot
Gas Bypass feature has been enabled on the OPERA-
TIONS Screen.
PRV Calibrate
Access Level Required: SERVICE
Moves to the subscreen that allows calibration of the
Economizer PRV feedback potentiometer.
Operations
Access Level Required: SERVICE
Navigates to the Economizer Operation screen.