JOHNSON CONTROLS
96
FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
SECTION 5 - COMMISSIONING
Remote / local operation
change
Power on
Initialize self-check
mechanism
Chilled and cooling water
pump interlock start
Chilled and cooling
water pump interlock
established
Solution pump and
refrigerant pump start
Steam control valve or steam drain
control valve, steam drain solenoid
valve, steam shut off valve(option)
open
Hold the lower limit
of the Control Valve
Local start operation
Remote start operation
Air conditioning machine
and cooling tower fan run
Defective signal output
Remote
Local
No
3 minutes
10 minutes
Yes
Time up
Temperature control
running
FIGURE 36 -
COOLING START DIAGRAM
Stop operation
Dilution time count
Steam control valve or steam drain
control valve, steam drain solenoid
valve, steam shut off valve(option)
close
Dilution time increasing
Chilled water
/ refrigerant
supercooling
Dilution
time stops
increasing
Yes
Solution pump /
refrigerant pump
stop running
Dilution time up
No
Solution pump /
refrigerant pump
continue running
HT-Gen.
pressure low
No
Pass 30 minutes
after dilution starts
No
No
Yes
Yes
Solution pump /
refrigerant pump
stop
Chilled / cooling
water pump
interlock stop
Absorption chiller
stops
Air conditioning
machine / cooling
tower fan stop
FIGURE 37 -
COOLING STOP DIAGRAM
Yes
1
1
Содержание YHAU-CW
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 20: ...JOHNSON CONTROLS 20 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 43: ...JOHNSON CONTROLS 43 SECTION 4 TECHNICAL DATA 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 130: ...JOHNSON CONTROLS 130 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...