SECTION 5 - COMMISSIONING
JOHNSON CONTROLS
3
Form 155.31-CL1.EN.UL
ISSUE DATE: 1
2
/
21
/201
8
F.
Evacuate Nitrogen Charge
1. Remove the plug in the purge line. ..........................
2. Release the Nitrogen gas until the high-tempera-
ture generator compound gas reads approximately
0.005 MPa.G (0.725 PSI) .........................................
3. Reinstall the plug in the purge line. ..........................
4. Navigate to the Control Panel Setting screen. .........
5. Press the Purge Pump
ON
button ...........................
6. Check the oil level in the purge pump ......................
7. Using the vacuum pump, evacuate the Nitrogen
gas until the high-temperature generator compound
gauge indicates almost -0.1 MPa.G (-14.5 PSI) ......
8. Close all open manual valves ..................................
9. Press the Purge Pump
OFF
button. .........................
10. Turn the power switch (MCB) off. .............................
11. Replace or add oil to the purge pump ......................
G. Panel Checks
1. The thermal relays conform to the factory inspec-
tion sheet ................................................................
2. The interlock and answerback signals for the fol-
lowing work properly:
a. Chilled water pump ..............................................
b. Cooling water pump .............................................
3. The indicators on the control panel are correct ........
4. The temperature setting parameters for capac-
ity control are correct ...............................................
5. Date and time reflect the local time zone .................
6. The rotation direction is correct for the following:
a. Solution circulation pump ....................................
b. Solution spray pump ............................................
7. The water flow suspension switch works properly ...
START UP CHECKLIST
A.
Operation Check
1. Manually start each water pump. ............................
2. Confirm the water box covers do not leak during
water pump operation. .............................................
3. Stop each water pump manually. .............................
4. Set each water pump operation mode to automatic
mode ........................................................................
5. Navigate to the Setting screen. ................................
6. Press the Manual Purge
ON
button. ........................
7. Purge non-condensable gas from the absorber
continuously. Use the procedure detailed in SEC-
TION 7 - MAINTENANCE of the manual ................
8. Open the refrigerant manual blow valve. .................
9. Navigate to the Control Panel Setting screen. ........
10. Press the Control Valve Mode
Manual
button. ........
11. Make sure that the Refrigerant Pump
Auto
button
is pressed. ................................................................
12. Verify that the steam control valve is closed. ...........
13. Press the
OPER.
button on the Control Panel Set-
ting screen. ..............................................................
14. Check that the following start properly:
a. Solution circulation pump ....................................
b. Solution spray pump ............................................
c. Refrigerant pump .................................................
15. Check for abnormal noise or vibration .....................
16. Gradually
open the steam control valve
or
steam drain control valve
.....
..............
.......................
17. Press the Control Valve Mode
Auto
button. ............
18.
Check that the steam control valve
or steam drain
control valve
works automati
cally according to the
chilled water outlet tempera
ture ............................
NOTES:
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
Содержание YHAU-CW
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 20: ...JOHNSON CONTROLS 20 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 43: ...JOHNSON CONTROLS 43 SECTION 4 TECHNICAL DATA 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 130: ...JOHNSON CONTROLS 130 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...