SECTION 4 - TECHNICAL DATA
FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
4
CONTACT SPECIFICATION
Absorption Chiller Control
Panel - External Output
Terminal
Digital Signal
Max. Open/Close Voltage: AC250 V/DC30 V
Max. Open/Close Current: 2A/1 Point (Resistance Load)
Max. Common Current: 8 A (Resistance Load)
Analog Signal
Allowed Resistance Load: 550 Ohm
External - Absorption Chiller
Control Panel
Digital Signal
Rating Voltage/Current: DC24 V/7 m A
Additional Information
1. Supply power source to absorption chiller
is de-
signed as 3 phase 3 line.
2. If you need information about breaker capa
city, see
.
3.
If you need information about the contact specifica
-
Table 14 - Contact Specifications on page
4. Connect the following absorption chiller interlocks.
If it is marked with an "*", be sure the connection
is made.
a. Operating interlock
* Chilled water pump operation interlock
•
Air handling unit interlock
b. Cooling water pump interlock
* Cooling water pump interlock
c. Normally monitoring interlock
• Seismoscope relay
• Abnormal room temperature sensor
TABLE 14 -
CONTACT SPECIFICATIONS
5. For terminal base position information, see
6. Use a shield wire which has a maximum exten-
sion of 650 feet and more than 0.0027 inch.
7.
Terminals that are not shown in the figures
have already been connected in the factory.
Содержание YHAU-CW
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 20: ...JOHNSON CONTROLS 20 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 43: ...JOHNSON CONTROLS 43 SECTION 4 TECHNICAL DATA 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 130: ...JOHNSON CONTROLS 130 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...