Product Conveyance Installation
10
3.2
Electric Connection
Before wiring, please check voltage, frequency, and phase and confirm whether they are correct. Power connection
should be installed according to electric schematic diagram. Earth lead should be connected firmly. Wiring
diagram is as Fig.1. The recommended wire size is as below sheet.
Several different models of unit sharing a single temperature controller are not prohibited.
Wire Size recommended is based on 40
℃
ambient temperature. Only copper wire can be used.
Please follow the local electrical codes and wiring standards in all cases.
A circuit breaker should be installed to the supply power.
Fig.1 Wiring Diagram:
Detail Connection for –XTB2:
Model
Power
Wire
Size
Recommended Breaker
(with earth leakage
protection)
YECFC01
230V ~50/60Hz
1.0 mm
2
5A 2P C Type
YECFC02
230V ~50/60Hz
1.0 mm
2
5A 2P C Type
YECFC03
230V ~50/60Hz
1.0 mm
2
5A 2P C Type
YECFC04
230V ~50/60Hz
1.0 mm
2
10A 2P C Type
YECFC05
230V ~50/60Hz
1.0 mm
2
10A 2P C Type
!