COMPETENT PERSONS TROUBLESHOOTING GUIDE
PROBLEM
POSSIBLE CAUSE
ACTION
POSSIBLE CAUSE
ACTION
No display on panel -
Mains supply to control system OFF. Switch on main supply if safe to do so.
unit will not start
Emergency stop device off.
Check if control panel emergency stop switch
and any remote emergency stop devices are in
the OFF position. Turn to ON position (1) if safe
to do so.
Under voltage relay tripped.
Check mains supply.
No supply to - T2.
Check emergency stop switch fuses.
No 24VAC supply to power board.
Check wiring from - T2 to powerboard and fuse.
No +12V output from powerboard.
Replace powerboard or isolate excessive load on
the board.
NO RUN PERM displayed
No liquid flow through the cooler.
Ensure that liquid pumps are running. Valves are
(No run permissive)
correctly set and flow is established.
Flow switch contacts are not made.
Check that the flow switch is functional and is
installed according to the manufacturer’s instructions.
Note: On some systems the pump starter may be wired
to the unit and controlled to start by
the unit.
SYS # HIGH OIL TEMP
Poor airflow through the condenser
Check for airflow restrictions caused by blockages on
coils.
intake faces of air coils.
Measured temperature incorrect.
Check sensor calibration, location and wiring.
Chiller FAULT: LOW
Ambient air temperature is lower
Use the ‘ambient temp.’ key to display the
AMBIENT TEMP displayed than the programmed operating
temperature and confirm that the displayed value is
limit.
approximately correct. The warning message should
clear when the ambient air temperature rises above
the programmed operating limit.
Check the programmed settings are correct for the
options fitted to the unit.
Measured temperature is incorrect.
Check sensor calibration, location and wiring.
Chiller FAULT: HIGH
Ambient air temperature is higher
Use the ‘ambient temp.’ key to display the
AMBIENT TEMP displayed than the programmed operating limit. temperature and confirm that the displayed value is
approximately correct. The warning message should
clear when the ambient air temperature falls below
the programmed operating limit.
Check that the programmed settings are correct for
the options fitted to the unit.
Resid. heat is not being dissipated.
Check fan is operating correctly and the rotation is
correct. Check for airflow recirculation.
Measured temperature is incorrect.
Check sensor calibration, location and wiring.
Chiller FAULT: LOW
Leaving liquid drops below the
Check for restrictions in the liquid flow line.
WATER TEMP displayed
programmed low limit faster than the Check that the liquid flow is stable.
unit can unload.
Unit is not unloading.
Check the supply to the unloader valve solenoid.
Check that the compressor unloads correctly.
Measured temperature is incorrect.
Check sensor calibration, location and wiring.
Chiller FAULT: VAC
Check mains supply is stable and within allowable
UNDERVOLTAGE
Poor mains supply voltage.
limits.
displayed.
Check for voltage dip on compressor start.
Troubleshooting
Содержание YCAS 0138EB
Страница 36: ...36 JOHNSON CONTROLS POWER AND CONTROL PANEL LAYOUTS WYE DELTA TYPICAL FIG 8 POWER PANEL SECTION 00263VIP 4...
Страница 50: ...50 JOHNSON CONTROLS This page intentionally left blank...
Страница 61: ...61 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank 7...
Страница 64: ...64 JOHNSON CONTROLS Technical Data ELEMENTARY DIAGRAM FIG 18 ELEMENTARY DIAGRAM ACROSS THE LINE START...
Страница 68: ...68 JOHNSON CONTROLS Technical Data ELEMENTARY DIAGRAM FIG 21 ELEMENTARY DIAGRAM WYE DELTA START...
Страница 70: ...70 JOHNSON CONTROLS Technical Data FIG 22A CONTROL PANEL COMPONENT LOCATIONS...
Страница 71: ...71 JOHNSON CONTROLS FORM 201 18 NM7 LD03280 FIG 22B POWER PANEL COMPONENT LOCATION 7...
Страница 72: ...72 JOHNSON CONTROLS Technical Data LEGEND LD03281...
Страница 73: ...73 JOHNSON CONTROLS FORM 201 18 NM7 LD03282 LD03283 LD03284 7...
Страница 74: ...74 JOHNSON CONTROLS Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06256 LD03231 LD03232...
Страница 75: ...75 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR TERMINAL BOX LD03233 7...
Страница 76: ...76 JOHNSON CONTROLS LD03285 Technical Data...
Страница 77: ...77 JOHNSON CONTROLS FORM 201 18 NM7 3 4 5 6 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06840A 7...
Страница 113: ...113 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR COMPONENTS CONT D FIG 40 COMPRESSOR COMPONENTS LD03669 7...
Страница 114: ...114 JOHNSON CONTROLS COMPRESSOR COMPONENTS CONT D FIG 41 COMPRESSOR COMPONENTS LD03670 Technical Data...
Страница 181: ...181 JOHNSON CONTROLS FORM 201 18 NM7 NOTES...
Страница 182: ...182 JOHNSON CONTROLS This page intentionally left blank...
Страница 183: ...183 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank...