162
JOHNSON CONTROLS
If an unacceptable value is entered at any stage, the
following message is displayed for a few seconds and
the entered value is ignored:
The following section shows examples of each program-
mable value display in the order in which they appear
after pressing the Program key, together with guidance
on programming each parameter.
The programmable values under the
Program Key must be checked and prop‑
erly programmed when commissioning
the chiller. Failure to properly program
these values may cause damage to the
Chiller or operating problems.
8.2
PROGRAM KEY –
USER PROGRAMMABLE VALUES
High Discharge Pressure Cut-Out
The Discharge Pressure Cutout is a microprocessor
backup for the mechanical high pressure cutout located
in each refrigerant circuit. This safety is bypassed for the
first 5 seconds of operation after which if the cutout point
is exceeded for 3 seconds, the system will shut down.
D I S C H A R G E P R E S S U R E
C U T O U T = 3 9 5 . 0 P S I G
8. PROGRAM KEY
8.1 GENERAL
The Program key is used to program 12 system operating
parameters including cutout points for safeties, antici-
patory unload points to avoid faults, and anti-recycle
timer duration.
When the Program key is pressed, the following mes-
sage will be displayed to indicate the display is in the
Program Mode:
Pressing the ENTER Key causes the display to show
the operator in what language the control panel message
are displayed.
The operator may select 5 display message languages.
The options are English, Spanish, French, German and
Italian. The
or
keys can be used to select the de-
sired language.
Pressing the Enter key repeatedly allows scrolling
through the programmable displays.
As each value is displayed, it may be reprogrammed
using the 12 Entry keys and
Keys. New values
will be programmed into memory when the Enter key
is pressed and the display will scroll on to the next
programmable value.
P R O G R A M M O D E
D I S P L A Y L A N G U A G E
E N
G L I S H
O U T O F R A N G E
T R Y A G A I N !
29023A
Micro Panel Contents
Содержание YCAS 0138EB
Страница 36: ...36 JOHNSON CONTROLS POWER AND CONTROL PANEL LAYOUTS WYE DELTA TYPICAL FIG 8 POWER PANEL SECTION 00263VIP 4...
Страница 50: ...50 JOHNSON CONTROLS This page intentionally left blank...
Страница 61: ...61 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank 7...
Страница 64: ...64 JOHNSON CONTROLS Technical Data ELEMENTARY DIAGRAM FIG 18 ELEMENTARY DIAGRAM ACROSS THE LINE START...
Страница 68: ...68 JOHNSON CONTROLS Technical Data ELEMENTARY DIAGRAM FIG 21 ELEMENTARY DIAGRAM WYE DELTA START...
Страница 70: ...70 JOHNSON CONTROLS Technical Data FIG 22A CONTROL PANEL COMPONENT LOCATIONS...
Страница 71: ...71 JOHNSON CONTROLS FORM 201 18 NM7 LD03280 FIG 22B POWER PANEL COMPONENT LOCATION 7...
Страница 72: ...72 JOHNSON CONTROLS Technical Data LEGEND LD03281...
Страница 73: ...73 JOHNSON CONTROLS FORM 201 18 NM7 LD03282 LD03283 LD03284 7...
Страница 74: ...74 JOHNSON CONTROLS Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06256 LD03231 LD03232...
Страница 75: ...75 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR TERMINAL BOX LD03233 7...
Страница 76: ...76 JOHNSON CONTROLS LD03285 Technical Data...
Страница 77: ...77 JOHNSON CONTROLS FORM 201 18 NM7 3 4 5 6 3 4 5 6 7 8 5 6 3 4 7 8 9 10 LD06840A 7...
Страница 113: ...113 JOHNSON CONTROLS FORM 201 18 NM7 COMPRESSOR COMPONENTS CONT D FIG 40 COMPRESSOR COMPONENTS LD03669 7...
Страница 114: ...114 JOHNSON CONTROLS COMPRESSOR COMPONENTS CONT D FIG 41 COMPRESSOR COMPONENTS LD03670 Technical Data...
Страница 181: ...181 JOHNSON CONTROLS FORM 201 18 NM7 NOTES...
Страница 182: ...182 JOHNSON CONTROLS This page intentionally left blank...
Страница 183: ...183 JOHNSON CONTROLS FORM 201 18 NM7 This page intentionally left blank...