Mounting holes (11/16” diameter) are provided in the steel channel for bolting the unit to
its foundation. See
Unit Dimensions on page 42
.
For ground level installations, precautions should be taken to protect the unit from tam-
pering by or injury to unauthorized persons. Screws on access panels will prevent casual
tampering; however, further safety precautions, such as unit enclosure options, a fenced-
in enclosure, or locking devices on the panels may be advisable. Check local authorities
for safety regulations.
CHILLED LIQUID PIPING
The chilled liquid piping system should be laid out so that the circulating pump discharges
into the cooler. The inlet and outlet cooler liquid connections are given in
Unit Dimensions
on page 42
.
Hand stop valves are recommended for use in all lines to facilitate servicing. Drain con-
nections should be provided at all low points to permit complete drainage of the cooler
and system piping.
The cooler must be protected by a strainer, preferably of 40 mesh, fitted as close as
possible to the liquid inlet connection, and provided with a means of local isolation. The
cooler must not be exposed to flushing velocities or debris released during flushing. It is
recommended that a suitably sized bypass and valve arrangement is installed to allow
flushing of the piping system. The bypass can be used during maintenance to isolate the
heat exchanger o other units.
Pressure gauge connections are recommended for installation in the inlet and outlet water
lines. Gauges are not furnished with the unit and are to be furnished by other suppliers.
The chilled liquid lines that are exposed to outdoor ambients should be wrapped with a
supplemental heater cable and covered with insulation. As an alternative, ethylene glycol
should be added to protect against freezeup during low ambient periods.
A flow switch is available as an accessory on all units. The flow switch (or its equivalent)
must be installed in the leaving water piping of the cooler.
Application Data (Cont'd)
Содержание YCAL Series
Страница 4: ...JOHNSON CONTROLS FORM 150 67 EG1 219 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 47: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 47 Unit Dimensions Cont d YCAL0028 LD18674...
Страница 55: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 55 45 1 8 18 1 2 LD18682 Unit Dimensions Cont d YCAL0052...
Страница 57: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 57 Unit Dimensions Cont d YCAL0056 45 1 8 16 3 4 LD18684...
Страница 63: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 63 Unit Dimensions Cont d YCAL0022 SI LD18692...
Страница 73: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 73 Unit Dimensions Cont d YCAL0052 SI 424 LD18702...
Страница 88: ...JOHNSON CONTROLS FORM 150 67 EG1 219 88 Power Wiring Single Circuit ld18707...
Страница 89: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 89 Power Wiring Single Circuit Cont d...
Страница 90: ...JOHNSON CONTROLS FORM 150 67 EG1 219 90 Power Wiring Single Circuit Cont d...
Страница 91: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 91 LD18746 Power Wiring Dual Circuit...
Страница 92: ...JOHNSON CONTROLS FORM 150 67 EG1 219 92 Factory wired with optional transformer LD03611 Control Wiring...