JOHNSON CONTROLS
FORM 150.67-EG1 (219)
10
Accessories and Options
All accessories and options are factory mounted unless otherwise noted.
ELECTRICAL OPTIONS
Single-Point Supply Terminal Block – Standard
. Includes enclosure, terminal-block
and interconnecting wiring to the compressors. Separate external protection must be sup-
plied, by others, in the incoming compressor-power wiring. (Do not include this option if
either the SinglePoint NonFused Disconnect Switch or Single-Point Circuit Breaker op-
tions have been included.)
Single-Point Non-Fused Disconnect Switch
– Unit-mounted disconnect switch with ex-
ternal, lockable handle (in compliance with Article 440-14 of N.E.C.), can be supplied to
isolate the unit power voltage for servicing. Separate external fusing must be supplied,
by others in the power wiring, which must comply with the National Electrical Code and/
or local codes.
Single-Point Circuit Breaker
– A unit mounted circuit breaker with external, lockable
handle (in compliance with N.E.C. Article 440-14), can be supplied to isolate the power
voltage for servicing. (This option includes the Single-Point Power connection.)
Control Transformer
– Converts unit power voltage to 115-1-60 or 115-1-50 if 50Hz is
selected (0.5 or 1.0 KVA capacity). Factory mounting includes primary and secondary wir-
ing between the transformer and the control panel.
Power Factor Correction Capacitors
– Will correct unit compressor power factors to
0.90-0.95.
CONTROL OPTIONS
Ambient Kit (Low)
– Standard units will operate to 25°F (-4°C). This accessory includes
all necessary components to permit chiller operation to 0°F (-18°C). (This option includes
the Discharge Pressure Transducer/Readout Capability option.) For proper head pres-
sure control in applications below 25°F (-4°C), where wind gusts may exceed five mph, it
is recommended that Optional Condenser Louvered Enclosure Panels also be included.
Ambient Kit (High)
– Required if units are to operate when the ambient temperature is
above 110°F (43°C). Includes discharge pressure transducers. (This option includes the
Discharge Pressure Transducer / ReadoutCapability option.) (
Field-Mounted
.)
Language LCD And Keypad Display
– Spanish, French, and German unit LCD controls
and keypad display available. Standard language is English.
Discharge Pressure Transducers And Readout Capability
– The addition of pressure
transducers allows models to sense and display discharge pressure. This is recommend-
ed for glycol chilling applications. (This option is included with either the low or high ambi-
ent kits.)
Suction Pressure Transducers
– Permits unit to sense and display suction pressure.
This capability is standard.
Содержание YCAL Series
Страница 4: ...JOHNSON CONTROLS FORM 150 67 EG1 219 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 47: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 47 Unit Dimensions Cont d YCAL0028 LD18674...
Страница 55: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 55 45 1 8 18 1 2 LD18682 Unit Dimensions Cont d YCAL0052...
Страница 57: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 57 Unit Dimensions Cont d YCAL0056 45 1 8 16 3 4 LD18684...
Страница 63: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 63 Unit Dimensions Cont d YCAL0022 SI LD18692...
Страница 73: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 73 Unit Dimensions Cont d YCAL0052 SI 424 LD18702...
Страница 88: ...JOHNSON CONTROLS FORM 150 67 EG1 219 88 Power Wiring Single Circuit ld18707...
Страница 89: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 89 Power Wiring Single Circuit Cont d...
Страница 90: ...JOHNSON CONTROLS FORM 150 67 EG1 219 90 Power Wiring Single Circuit Cont d...
Страница 91: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 91 LD18746 Power Wiring Dual Circuit...
Страница 92: ...JOHNSON CONTROLS FORM 150 67 EG1 219 92 Factory wired with optional transformer LD03611 Control Wiring...