NOTES:
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the
largest motor plus 100% of the rated load amps for all other loads included in the cir-
cuit, per N.E.C. Article 430-24. If the optional Factory Mounted Control Transformer
is provided, add the following MCA values to the electrical tables for the system
providing power to the transformer: -17, add 2.5 amps; -28, add 2.3 amps; -40, add
1.5 amps, -46, add 1.3 amps; -58, add 1 amps.
2. The minimum recommended disconnect switch is based on 115% of the rated load
amps for all loads included in the circuit, per N.E.C. Article 440.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor
plus 100% of the rated load amps for all other loads included in the circuit to avoid
nuisance trips at start-up due to lock rotor amps. It is not recommended in applica-
tions where brown outs, frequent starting and stopping of the unit, and/or operation
at ambient temperatures in excess of 95ºF (35ºC) is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest mo-
tor plus 100% of the rated load amps for all other loads included in the circuit, per
N.E.C. Article 440-22.
5.
Circuit breakers must be UL listed and CSA certified and maximum size is based on
225% of the rated load amps for the largest motor plus 100% of the rated load amps
for all other loads included in the circuit. Otherwise, an HACR-type circuit breakers
must be used. Maximum HACR circuit breaker rating is based on 225% of the rated
load amps for the largest motor plus 100% of the rated load amps for all other loads
included in the circuit.
6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can
be accommodated by the unit wiring lugs. The (2) preceding the wire range indi-
cates the number of termination points available per phase of the wire range speci-
fied. Actual wire size and number of wires per phase must be determined based on
the National Electrical Code,
using copper connectors only
. Field wiring must
also comply with local codes.
7.
A ground lug is provided for each compressor system to accommodate a field
grounding conductor per N.E.C. Table 250-95. A control-circuit-grounding lug is also
supplied.
8.
The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100,
and is intended for isolating the unit for the available power supply to perform main-
tenance and troubleshooting. This disconnect is not intended to be a Load Break
Device.
9. Field Wiring by others which complies to the National Electrical Code & Local Codes.
Electrical Notes (Cont'd)
Содержание YCAL Series
Страница 4: ...JOHNSON CONTROLS FORM 150 67 EG1 219 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 47: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 47 Unit Dimensions Cont d YCAL0028 LD18674...
Страница 55: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 55 45 1 8 18 1 2 LD18682 Unit Dimensions Cont d YCAL0052...
Страница 57: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 57 Unit Dimensions Cont d YCAL0056 45 1 8 16 3 4 LD18684...
Страница 63: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 63 Unit Dimensions Cont d YCAL0022 SI LD18692...
Страница 73: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 73 Unit Dimensions Cont d YCAL0052 SI 424 LD18702...
Страница 88: ...JOHNSON CONTROLS FORM 150 67 EG1 219 88 Power Wiring Single Circuit ld18707...
Страница 89: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 89 Power Wiring Single Circuit Cont d...
Страница 90: ...JOHNSON CONTROLS FORM 150 67 EG1 219 90 Power Wiring Single Circuit Cont d...
Страница 91: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 91 LD18746 Power Wiring Dual Circuit...
Страница 92: ...JOHNSON CONTROLS FORM 150 67 EG1 219 92 Factory wired with optional transformer LD03611 Control Wiring...