YCAE100/130X
Notes
1. External interlock is short-circuited or is linked to external facilities before operation;
2. Water pump control is connected by factory before delivery if hydro kit is selected;
3. 45-130 models: SF1 (DI12/XTB2:80K&93) -- Factory installation; SF2 (DI5/XTB2:80E&85) --
Short-circuited before delivery; 160-260 models: SF1 (DI12/XTB2:80K&93)
– Short-circuited
before delivery; SF2 (DI5/XTB2:80E&85) -- Factory installation;
4. For digital input signals (SF1/SF2, SC/H, SRE, SEL), the loop resistance should be less than
100Ω when the external contact closes. The voltage at both ends of DI switch is 12VDC when DI
switch/signal opens;
5. For output signals, the output from the control board is active signal with 230VAC, and the
accepted Amps capacity is 1A; For pump/alarm output, a relay (KWP/KAL) has been connected
to the output port on control board before delivery to transfer active signal to free contact, and the
contact capacity is 1A @250VAC.
6. For additional information, please see wiring diagram.
It is possible that multiple sources of power can be supplying the unit power panel.
To prevent serious injury or death, the technician should verify that NO LETHAL
VOLTAGES are present inside the panel AFTER disconnecting power, PRIOR to
working on equipment.