MOTOR SPECIFICATIONS

•1450 RPM

•380/415-3-50

•Solid base

•56 Frame

•Inherently protected

•Permanently lubricated

ball bearings

MAINTENANCE

FILTERS — The filters must be replaced as often as necessary
to assure good air flow and filtering action.

EVAPORATOR COIL — Do not allow dirt to accumulate on the
evaporator coil or other parts of the evaporator air circuit. Clean
as often as necessary to assure good system performance.
Use a brush, vacuum cleaner attachment or other suitable
means.

LUBRICATION — The bearings for the blower shaft and the
blower motors are permanently lubricated and should not re-
quire additional lubricant.

DRAIN PAN — The drain pan should be inspected regularly
to assure proper drainage.

BELTS — Maintain belt tension to extend belt life. Replace
when signs of failure begin to appear.

POWER AND CONTROL WIRING

Install electrical wiring in accordance with appli-
cable national, local and municipal codes. The
unit should be grounded in accordance with
these codes.

Route the power wires into the unit through one
of the

7

8

" (22.2mm) dia.knockouts in the panel

with the supply air opening and connect them to
the terminals on blower motor contactor 10M.
Route the control wires into the unit through the
other

7

8

" (22.2mm) dia.knockout and connect

them to the terminals on block 4TB. Refer to
the unit drawing in Figure 7 for the locations of
these knockouts.

If the unit includes an electric heat accessory,
route the power wires into heater control box in-
stead of the unit. Refer to the electric heat in-
structions for additional installation information.

Refer to Table 4 to size the disconnect switch,
the power wiring and the fuses. Refer to Figure
8 for typical field wiring.

NOTE: Three phase motor rotation may be incor-

rect when the unit is first started up. Re-
verse phase (leads L1 and L2) at
contactor to obtain the correct rotation.

FIG 8 - TYPICAL FIELD WIRING (Cooling only)

TERMINALS ON BLOCK 3TB OF
THE BLOWER UNIT

TERMINALS ON
1-STAGE COOLING
THERMOSTAT
2TH0870124

Motor

(HP/kW)

Blower

Range
(RPM)

Adjustable Motor Pulley

Fixed Blower Pulley

Belt

Pitch Dia

(In./mm)

Bore

(In./mm)

Pitch Dia.

(In./mm)

Bore

(In./mm)

Designation

Pitch Lg.

(In./mm)

3 / 2.2

615/800

3.4 - 4.4 / 86

- 112

7

8

/ 22.2

8.0 / 203

1 / 25

A54

55.3 / 1405

TABLE 7 - BLOWER MOTOR AND DRIVE DATA

Subject to change without notice.   Printed in U.S.A
Copyright

by York International Corporation

5005

York

Drive

035-12124-000 Rev. A (0501)
Supersedes: 550.39-N5YI (894)

Unitary

Products

Group

Norman

OK

73069

Содержание WORLD 50 HZ K3EU180A50

Страница 1: ...n as a unit is received it should be inspected for possible damage during transit If damage is evident the extent of the damage should be noted on the carrier s delivery receipt A separate request for...

Страница 2: ...the skid These units can be rigged with slings under the bottom skid CAUTION Spreader bars should be used to prevent slings from crushing the unit panels and frame Before rigging any unit determine i...

Страница 3: ...n Pack fiber glass insulation and a sealing material such as Per magum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility Support all refrigerant l...

Страница 4: ...the refrigerant connections The line should be in sulated where moisture drippage will be objectionable or cause damage to the area Seal the unused drain connec tion with a suitable mastic The 3 76mm...

Страница 5: ...dry coil the refrigerant system should be de energized while the test is being run 4 Knowing the pressure drop across a dry coil the actual air flow through the unit can be determined from the curve i...

Страница 6: ...2 2 20 2 68 404 2 46 2 99 311 2 73 1 Unit resistance is based on a wet evaporator coil and clean filters 2 Available static pressure in IWG Pa to overcome the resistance of the duct system and any acc...

Страница 7: ...tom 4 NOTES 1 Overall dimension of the unit will vary if an electric heater a supply air plenum or a base is used 2 This dimension is required for removal of the DX coil Only 26 660mm is required for...

Страница 8: ...terminals on blower motor contactor 10M Route the control wires into the unit through the other 7 8 22 2mm dia knockout and connect them to the terminals on block 4TB Refer to the unit drawing in Figu...

Отзывы: