background image

JOHNSON CONTROLS

6

FORM 145.05-SU2 (1207)

ALL UNITS

ON / OFF – MANUAL SWITCH

To turn the unit ON turn the ON/AUTO/OFF toggle 

switch, located below the User Interface, from the OFF 

to ON position.

Field Wiring

None required.

Programming

None required.

ON / OFF – INTERNAL CLOCK

To turn the unit ON, turn the ON/AUTO/OFF toggle 

switch (located below the User Interface) from the OFF 

to AUTO position.  The unit will then be switched to 

ON based on the ON/OFF schedule programmed in the 

User Interface.

Field Wiring

None required.

Programming

Go to the 

“Daily Sched” 

section of the User Interface.  

Change the 

“Daily Schedule Status”

 to ON.  Program 

the 

“Start”

 and 

“Stop”

 times for each day of the 

week.

ON / OFF – COMMUNICATED

To turn the unit ON, turn the ON/AUTO/OFF toggle 

switch (located below the User Interface) from the OFF 

to AUTO position.  The unit will then be switched to 

ON based on a communicated input from the BAS 

system.

Field Wiring

Connect the (+) wire of a shielded twisted pair to the 

(+) terminal of the Network Port.  Connect the (-) wire 

of a shielded twisted pair to the (-) terminal of the 

Network Port.

Programming

Go to the 

“Daily Sched” 

section of the User Interface.  

Change the 

“Daily Schedule Status”

 to OFF.

CONDENSER WATER VALVE MINIMUM POSITION

This parameter establishes the minimum position of 

the condenser water valve any time the unit is in the 

ON mode.

Field Wiring

None required.

Programming

The following item must be programmed through the 

Setpoints

” section of the User Interface:

 

“ Cond Valve Min”

 – This parameter can be 

set between 0 and 100%.  The default value is 

15%.

COMMUNICATED VFD FAN SPEED CONTROL

This feature can be ordered from the factory for units 

that will be twinned together and share a common 

supply duct.  The feature allows a front end BAS system 

to monitor the VFD fan speed of the lead unit and 

communicate a VFD fan speed to the second unit.

Field Wiring

Connect the (+) wire of a shielded twisted pair to the 

(+) terminal of the Network Port.  Connect the (-) wire 

of a shielded twisted pair to the (-) terminal of the 

Network Port.

Programming

The following item must be programmed through the 

Setpoints

” section of the User Interface:

• 

“Fan Sp BAS En” 

– To use this feature this pa-

rameter must be set to ON.

Содержание VERSECON YSWU Series

Страница 1: ...AIR CONDITIONING UNITS New Release Form 145 05 SU2 1207 VERSECON Indoor Upflow Self Contained Air Conditioner YSWU 10 105 Ton Water Cooled Indoor Downflow Self Contained Air Conditioner YSWD 10 105 T...

Страница 2: ...ls This individual will also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in...

Страница 3: ...t YORK Applied Systems Service office It is the responsibility of operating service personnel to verify the applicability of these documents to the equipment in question If there is any question in th...

Страница 4: ...SUPPLY AIR AND RETURN AIR TEMPERATURE CONTROL 8 SUPPLY FAN OPERATION 9 SUPPLY FAN DUCT STATIC PRESSURE 9 FLEXSYS 10 COOLING SUPPLY AIR TEMPERATURE CONTROL 10 COOLING RETURN AIR TEMPERATURE CONTROL 10...

Страница 5: ...d by the User Interface should be diagnosed as referenced in the Installation Operation and Maintenance manual refer to Faults and Alarms in the Service section of the manual QUICK START GUIDE VERSECO...

Страница 6: ...t Connect the wire of a shielded twisted pair to the terminal of the Network Port Programming Go to the Daily Sched section of the User Interface Change the Daily Schedule Status to OFF CONDENSER WATE...

Страница 7: ...e return air temperature the unit will try to maintain COOLING SUPPLY AIR AND RETURN AIR TEMPERATURE CONTROL This feature allows the unit to control the staging of the compressor based on either the t...

Страница 8: ...Temp En must be set to ON The default is OFF AC Econ R A SP set point must be pro grammed The default value is 75 0 F This is the return air temperature the unit will try to maintain COOLING SUPPLY AI...

Страница 9: ...C The default value is 1 0 WC of SPSensors The control has the capability to use one or two duct static sensors If a single sensor is used this value would be set to 1 If two sensors are used this val...

Страница 10: ...temperature the unit will try to maintain COOLING SUPPLY AIR AND RETURN AIR TEMPERATURE CONTROL This feature allows the unit to control the staging of the compressor based on either the temperature di...

Страница 11: ...ed to Avg the control will compare the average of the two sensors to the Fan S A Pres SP and control the speed of the VFD based on these values SUPPLY AIR PROVING SET POINT The Unit Control monitors t...

Страница 12: ...of the User Interface AC S A Dew En must be set to ON FLEXSYS DEW POINT TEMPERATURE CONTROL AC S A Dew Min set point must be pro grammed The default value is 48 0 F This is the lowest supply air tempe...

Страница 13: ...a return air temperature The default value is OFF Econ Valve Min This parameter establishes the minimum position of the water side econo mizer valve The parameter can be set between 0 and 100 The defa...

Страница 14: ...A Econ En This parameter must be set to ON The default value is OFF Econ S A Tmp En This parameter must be set to ON if you want the water side economizer to be controlled by a supply air temperature...

Страница 15: ...1 Heat R A Tmp En must be set to ON The default is OFF Heat R A Tmp SP set point must be pro grammed It can be set between 40 0 F and 90 0 F The default value is 72 0 F This is the return air tempera...

Страница 16: ...value is 72 0 F This is the return air temperature the unit will try to maintain Tele 800 861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed...

Отзывы: