246681-YTG-B-0607
8
Unitary Products Group
Note 1:
Complete York ERV model number includes the electrical information. Example: DM180 needing 2800 CFM
outside of air at 230 volts/3 phase. Model would be a VR028A15H2AAA1.
Note 2:
For VR074 and VR122 units used with an economizer must have the Start-Stop-Jog (SSJ) option.
TABLE 3: PERFORMANCE - 15 THROUGH 25 TON UNITS
Use this table to determine ventilation and size requirements. Table shows York packaged units and matching ERV model,
Air Flow Range, and ARI rated Net Effectiveness at 100% of rated CFM.
“R” Series Stationary Wheel for Units without Economizers
York
Packaged Unit
Model No.
Unit
Size
(Tons)
ERV CFM
Range
Matching ERV
Model
Voltage &
Phase
Voltage
Code
Nominal ARI Data (Total
CFM
Net Effectiveness
Heating
Cooling
DM 180
DH 180
BP 180
15
1500-2200
VR028A15M
208/230v-3ph
2
1950
71%
70%
460v-3ph
4
575v-3ph
5
2200-2800
VR028A15H
208/230v-3ph
2
2600
65%
63%
460v-3ph
4
575v-3ph
5
2800-3600
VR036A15H
208/230v-3ph
2
3100
65%
63%
460v-3ph
4
575v-3ph
5
3400-4600
VR046A15H
208/230v-3ph
2
3900
65%
63%
460v-3ph
4
575v-3ph
5
4800-5600
VR062A15M
208/230v-3ph
2
4125
71%
70%
460v-3ph
4
575v-3ph
5
5500-6200
VR062A15H
208/230v-3ph
2
5500
65%
63%
460v-3ph
4
575v-3ph
5
DM 240
DM 300
DH 240
BP 240
BQ 240
DJ 180
DJ 210
DJ 240
DJ 300
DR 180
DR 240
DR 300
15 - 25
2200-2800
VR028A25H
208/230v-3ph
2
2600
65%
63%
460v-3ph
4
575v-3ph
5
2800-3600
VR036A25H
208/230v-3ph
2
3100
65%
63%
460v-3ph
4
575v-3ph
5
3400-4600
VR046A25H
208/230v-3ph
2
3900
65%
63%
460v-3ph
4
575v-3ph
5
4800-5600
VR062A25M
208/230v-3ph
2
4125
71%
70%
460v-3ph
4
575v-3ph
5
5500-6200
VR062A25H
208/230v-3ph
4
5500
65%
63%
460v-3ph
5
575v-3ph
2
(See note 2)
(See
note 2)
6000-8000
VR074A40*
208/230v-3ph
2
6600
65%
63%
460v-3ph
4
575v-3ph
5
8000-13000
VR122A40*
208/230v-3ph
2
10800
65%
63%
460v-3ph
4
575v-3ph
5