background image

Unitary Products Group

5

246681-YTG-B-0607

CROSS LEAKAGE IN UERV’S (PURGE SECTORS)

The issue of cross leakage in rotary wheel based UERV's 
used in space conditioning applications is often misunder-
stood. As a result, many systems are installed with purge 
sectors and the additional fan capacity required to allow 
these sectors to function when in fact they are unnecessary. 
A better understanding of the rational for the purge sector, 
and its history, allows us to dispense with the purge sector, its 
added first cost and continuing cost of operation.

A purge sector minimizes the carry over cross leakage from 
the exhaust into the supply (outside air) air stream by shunt-
ing a portion of the supply air back into the exhaust air stream 
across the seal separating the exhaust and supply. This is 
required in industrial applications where the exhaust carries 
contaminants. This typically results in air volume being 15% 

to 20% higher to get the desired air intake, and the cost asso-
ciated with it.

In space conditioning applications, where the ventilation is 
operating to maintain acceptable indoor air quality, there are 
no contaminants in concentrations large enough to cause 
concern. Cross leakage in the UERV system results in a 
small amount of the exhaust air, typically less than 5% in bal-
anced airflow, returning to the space. This is not contami-
nated air, as some would suggest. It is however air that 
effectively never left the space. The operation cost of moving 
this air is far less than that required for a purge sector. Do not 
use the York UERV's in applications that have concentrations 
of contaminants.

OPTIONAL ACCESSORIES - FIELD 
INSTALLED

UERV Equipment Support

 - 8 inch (203 mm) high base for 

support of the exhaust and intake end of the UERV. Must be 
ordered separately from the UERV.

Equipment Support

UERV Part 

No.

VR006

1ES0401

VR/P011

1ES0402

VR/P020

1ES0402

VR/P028

1ES0402

Equipment Support

UERV Part 

No.

VR036

1ES0403

VR046

1ES0403

VR062

1ES0404

VR074

VR122

Roof Curb

 - A 14 or 24 inch (355 or 610 mm) roof curb is 

required to match supply and exhaust openings of the UERV 
with the rooftop units. York provides a full line of roof curbs to 
match the specified unit. See specification pages for required 
curb. Must be ordered separately from UERV.

Stand Alone Balancing Damper

 - Balancing dampers are 

used with VO and VS models when ERV is connected to the 
rooftop unit, not to ductwork on the roof.

TABLE 1: UERV OUTSIDE AIR CFM SELECTION BY CFM

Unit-Tons

300-550

600-1000

1100-1700

1500-2800

2800-3600

3400-4600

4800-5600

5500-6200

6000-8000

8000-13000

Rooftop

1.5 - 6

1.5 - 6

Stand Alone type ERV’s are available for all tonnage sizes.

7.5 - 12.5

7.5 - 12.5

7.5 - 12.5

15 - 25

15 - 25

15 - 25

15 - 25

15 - 25

30 - 50

30 - 50

Upflow

1.5 - 5

1.5 - 5

Horizontal

1.5 - 5

1.5 - 5

Stand Alone ERV’s are available for equipment room applications.

Содержание V* Series

Страница 1: ...omizermode when outside sensorcallsfor economizer operation 3 12 5 ton packaged units equipped with economizers U S Patent 5 548 970 Pivoting wheel models used with packaged unit with econo mizer Sequ...

Страница 2: ...078 THROUGH 150 18 7 UERV DIMENSIONAL DATA 180 THROUGH 300 18 8 MILLENNIUM UNIT VR074 AND VR122 19 9 STAND ALONE UERV S FOR SIDE BY SIDE DUCT ARRANGEMENTS 21 10 STAND ALONE UERV S FOR OVER AND UNDER...

Страница 3: ...P DU L 20 064 080 092 Z05 P UR P XU PXU V 16 075 Z05 P UR P XU PXU V 20 095 Y05 P UR P XU PXU V 20112 130 X05 P DH P XD V 20 075 V05 N AH N VS B G2FD 14 20 048S 060S 061H Z03 P HU P DU P DU V P HU P D...

Страница 4: ...ecovery ven tilators This standard deals specifically with the ratings of the Energy Recovery Wheel that is incorporated into the Energy Recovery Ventilator ERV All of the York ERV s have an ARI certi...

Страница 5: ...rning to the space This is not contami nated air as some would suggest It is however air that effectively never left the space The operation cost of moving this air is far less than that required for...

Страница 6: ...op Start Jog SSJ M3 MOA SSJ and Pressure Sensor PS M4 MOA and PS S1 Stop Start Jog SSJ S2 SSJ and Pressure Sensor PS P1 Pressure Sensor PS NOTE denotes only options available for VR074 VR122 HOW TO SE...

Страница 7: ...018 060 D NP 024 048 D NZ 024 060 1 5 5 300 550 VR006A05H 110v 1ph 1 500 65 64 208 230v 1ph 9 208 240v 3ph 2 460v 3ph 4 DM 036 072 DF 036 072 DH 036 060 BQ 036 060 3 6 300 550 VR006A06H 110v 1ph 1 50...

Страница 8: ...2200 VR028A15M 208 230v 3ph 2 1950 71 70 460v 3ph 4 575v 3ph 5 2200 2800 VR028A15H 208 230v 3ph 2 2600 65 63 460v 3ph 4 575v 3ph 5 2800 3600 VR036A15H 208 230v 3ph 2 3100 65 63 460v 3ph 4 575v 3ph 5 3...

Страница 9: ...78 102 BP 090 See note 2 7 5 8 5 600 1000 1900 VP011B12H 208 230v 3ph 2 900 73 72 460v 3ph 4 575v 3ph 5 1100 1700 3000 VP020B12H 208 230v 3ph 2 1600 65 64 460v 3ph 4 575v 3ph 5 DM 078 DM 120 150 DF 07...

Страница 10: ...Cooling 65 Curb A C Unit Curb Height in Shipping Weight lbs Net Weight lbs Note 1 A stepdown transformer is provided to stepdown high voltage primary to 115 volt secondary 10 1 59 9 90 500 6 2 1 02 0...

Страница 11: ...w Cooling 81 73 72 67 70 100 Airflow Heating 76 68 68 61 65 75 Airflow Heating 81 73 72 67 71 100 Airflow Cooling 76 68 68 61 64 75 Airflow Cooling 81 73 72 67 70 Curb A C Unit Curb Hgt in Shipping We...

Страница 12: ...2 4 Full Load Amps Pivoting 9 4 4 3 6 Service Factor 1 15 1 15 Wheel Electrical Data Motor hp 1 phase 0 17 0 17 Potential Volts 200 208 230 200 208 230 Motor Speed rpm 1725 1725 Full Load Amps 1 1 1 1...

Страница 13: ...0 50 Potential Volts 200 208 230 200 208 230 Motor Speed rpm 1725 1725 Full Load Amps 2 7 2 7 Total Electrical MCA Stationary 22 4 10 9 8 4 16 1 18 6 6 6 OCPD Stationary 30 15 9 20 12 9 Wheel Data Whe...

Страница 14: ...0 5 Potential Volts 200 208 230 200 208 230 Motor Speed rpm 1150 1150 Full Load Amps 1 2 1 2 Total Electrical MCA Stationary 34 5 17 12 22 11 8 7 OCPD Stationary 40 25 15 30 15 12 Wheel Data Wheel Dep...

Страница 15: ...otential Volts 200 208 230 200 208 230 Motor Speed rpm 1075 1075 Full Load Amps 1 2 2 7 Total Electrical MCA Stationary 36 8 17 5 13 6 34 5 17 12 7 OCPD Stationary 50 25 20 40 25 15 Wheel Data Wheel D...

Страница 16: ...7 52 22 6 19 OCPD 50 20 15 70 30 25 Wheel Data Wheel Depth x Diameter in 3 x 58 3 x 74 Construction Media Type Segmented Pies Polymeric Segmented Pies Polymeric Enthalpy Wheel Airflow Data Nominal Air...

Страница 17: ...B HA HH HP 018 060 Optional Eqpt Support Exhaust Blower Outdoor Air Intake Blower Enthalpy Wheel A B C D VR006B05H VR006A05H B HA HH HP 018 060 FIGURE 5 UERV DIMENSIONAL DATA 036 THROUGH 072 14 High C...

Страница 18: ...851 44 75 1137 60 38 1533 600 1000 1100 1700 37 25 946 37 5 953 FIGURE 7 UERV DIMENSIONAL DATA 180 THROUGH 300 Model Number Unit Size A B C D CFM 1500 2200 180 300 180 180 300 180 180 300 180 180 300...

Страница 19: ...the ERV Exhaust Blowers See blower performance charts for airflow at various external static pressures FIGURE 8 MILLENNIUM UNIT VR074 AND VR122 74 75 24 59 61 23 82 13 20 92 Model Number CFM Descript...

Страница 20: ...CFM 6000 910 1060 1200 1300 1400 6500 955 1095 1225 1360 1430 7000 1000 1130 1260 1380 1475 7500 1040 1170 1290 1400 1500 8000 1080 1200 1315 1425 1530 RPM Range Low 910 1320 Standard Unit High 1325...

Страница 21: ...Roof curbs are available for the UERV s 5 CFM at 0 0 external static pressure Series Model Number VS006 1RC0480 VS011 VS020 VS028 VS036 VS046 VS062 300 550 23 25 x 32 5 34 69 24 75 24 63 8 00 20 00 2...

Страница 22: ...12 00 27 00 Features and Notes 4 Roof curbs are available for the UERV s 600 1000 UERV with Horizontal Ductwork UERV Roof Curbs Dimensional Data UERV Data 2 60 5 00 2 56 11 00 18 32 39 50 8 00 3 59 18...

Страница 23: ...side for access Dimensions 4 Static test ports are provided for verification of CFM 5 Filter rack accepts 1 or 2 filters and comes with flex connector to air handler Features 3 Access panels located o...

Страница 24: ...urn Series for 600 1 000 CFM UERV for Ducted Applications The U11 ducted series is designed intake and exhaust air is ducted to the UERV Applications with long duct runs may require booster fans Duct...

Страница 25: ...XU P XU V 20 112 130 Upflow Only P DH P XD V 16 075 VH 006 X05H Horz Only P DH P XD V 20 075 Horz Only P DH P XD V 20 112 VH 006 W05H Horz Only N AH N VS D G2FD 14 20 048S 060S 061H VH 006 V05H VU 006...

Страница 26: ...rifugal blower It shall have ball bearings and adjustable belt drive Motor mount base shall permit ease of motor changeover and belt tension adjust ment On pivoting wheel models exhaust blowers shall...

Страница 27: ...space thermostat sends a signal to the RTU for cool ing heating or fan only operation 2 The ERV is activated with the supply blower of the RTU The intake blower the exhaust blower and the wheel rotat...

Страница 28: ...ed operation or 1 and 2 if in low speed operation are outputting 110 volts to B26 exhaust blower motor though J P151 plug assembly 3 Verify B26 wheel motor C25 capacitor is good Replace the capacitor...

Страница 29: ...blower motor 4 On direct drive models verify B26 wheel motor C25 capacitor is good Replace if necessary 5 If all of the above are operational the exhaust motor is bad Replace it with new motor UERV h...

Страница 30: ...at the contacts are closed 3 Verify power to B26 exhaust blower motor though J P151 plug assembly 4 On direct drive models verify B26 wheel motor C25 capacitor is good Replace if necessary 5 If all of...

Страница 31: ...A130 circuit board terminals TB 37 numbers 1 and 3 Terminal 1 is the hot and 3 is the common side of the power source from activation power source a c unit energy management control etc Typically 1 wo...

Страница 32: ...change without notice Printed in U S A 246681 YTG B 0607 Copyright by Unitary Products Group 2007 All rights reserved Supersedes 246681 036 21360 004 A 0105 Unitary 5005 Norman Products York OK Group...

Отзывы: