background image

1083293-UIM-D-1116

Johnson Controls Unitary Products

25

SECTION VII: COMBUSTION AIR AND 

VENT SYSTEM

COMBUSTION AIR AND VENT SAFETY

This Category IV, dual certified direct vent furnace is designed for resi-
dential application. It may be installed without modification to the con-
densate system in a basement, garage, equipment room, alcove, attic
or any other indoor location where all required clearance to combusti-
bles and other restrictions are met. The combustion air and the venting
system must be installed in accordance with Section 5.3, Air for Com-
bustion and Ventilation, of the National Fuel Gas Code Z223.1/NFPA 54
(latest edition), or Sections 7.2, 7.3 or 7.4 of CSA B149.1, National Gas
and Propane Codes (latest edition) or applicable provisions of the local
building code and these instructions.

COMBUSTION AIR/VENT PIPE SIZING

The size of pipe required will be determined by the furnace model, the
total length of pipe required and the number of elbows required.

Table 7 lists the maximum equivalent length of pipe allowed for each
model of furnace. The equivalent length of pipe for each elbow installed
is listed in Table 9. The equivalent length of the vent system is the total
length of straight pipe PLUS the equivalent length of all of the elbows.

The following rules must also be followed:

1.

Drain, waste, and vent (DWV) elbows with a long radius (sweep)
are recommended. Standard DWV elbows may be used, but since
they have a longer equivalent length, they will reduce the total
length of pipe that will be allowed. Short radius (plumbing or pres-
sure) elbows are not allowed for venting. The standard dimensions
of the acceptable elbows are shown in Figure 29.

2.

The maximum equivalent length listed in Table 7 is for the vent
piping and the air intake piping separately. For example, if the
table allows 65 equivalent feet for a particular model, then the vent
can have 65 equivalent feet of pipe, AND the combustion air intake
can have another 65 equivalent feet of pipe.

3.

Three vent terminal elbows (two for the vent and one for the com-
bustion air intake) are already accounted for and need not be
included in the equivalent length calculation.

4.

All PVC or ABS combustion air and vent pipe must conform to
American National Standards Institute (ANSI) and American Soci-

ety for Testing and Materials (ASTM) standards D1785 (Schedule
40 PVC), D2665 (PVC-DWV), F891 (PVC-DWV Cellular Core),
D2261 (ABS-DWV) or F628 (Schedule 40 ABS). Pipe cement and
primer must conform to ASTM Standard D2546 (PVC) or D2235
(ABS). If ABS pipe is to be used, any joint where ABS pipe is
joined to PVC pipe must be glued with cement that is approved for
use with BOTH materials. Metallic materials must not be used for
venting or air intake.

5.

If a flexible connector is used in the vent system, it must be made
of a material that is resistant to acidic exposure and to at least
225° F temperature. Flexible connectors are also allowed in the
combustion air pipe.

6.

All models are supplied with 2" (5.1 cm) vent connections. When

the pipe must be increased to 3" (7.6 cm) diameter, the transition
from 2" to 3" must be done as close to the furnace as possible.
The 2” to 3” increase should be installed in the vertical position as
to not create an area that will pool water.

7.

In Canada, vents shall be certified to ULC S636, Standard for
Type BH Gas Venting Systems.

8.

In Canada, the first three feet (91.4 cm) of the vent must be readily
accessible for inspection.

9.

For single pipe systems it is recommended to install the combus-
tion air coupling provided and install approximately 18” (46 cm) of
PVC pipe on the furnace.

10. Minimum vent length is five feet for all models.

POLYPROPYLENE VENT/INTAKE PIPING

The ULC S636 approved polypropylene (PP) vent piping materials
listed below have been tested and approved for use with this furnace.
DO NOT mix parts made by different manufacturers. The entire vent/air
intake system must be made from pipe, fittings and termination made
by the same manufacturer. Only single-wall rigid polypropylene pipe is
approved for these furnaces. Use of flexible polypropylene pipe is not
allowed.

Selkirk Polyflue (Hart & Cooley) part numbers

Horizontal concentric termination - 2" - 2PF-HCT

Horizontal concentric termination - 3" - 3PF-HCT

Locking band - PF-LB

Consult the Polyflue installation instructions for assembly details.

For other Polyflue pipe and fitting part numbers, visit website 

www.polyflue.com

Duravent Polypro part numbers

Adapter to air intake coupling - 2PPS-ADL

Adapter connector - PPS-PAC

Twin pipe horizontal termination - 2" - 2PPS-HTPL

Twin pipe horizontal termination - 3" - 3PPS-HTPL

Consult the Polypro installation instructions for assembly details.

For other Polypro pipe and fitting part numbers, visit website

www.duravent.com

Centrotherm Innoflue

Adapter to air intake coupling - ISAGL0202

Adapter to draft inducer blower - ISAAL0202

Low profile wall termination - 2" - ISLPT0202

Low profile wall termination - 3" - ISLPT0303

Consult the Innoflue installation instructions for assembly details.

For other Innoflue pipe and fitting part numbers, visit website 

www.centrotherm.us.com

IMPORTANT

The “VENT SYSTEM” must be installed as specified in these instruc-
tions for Residential and non-HUD Modular Homes. The direct vent
system is the only configuration that can be installed in a non-HUD
Modular Home.

 WARNING

 This furnace may not be common vented with any other appliance,
since it requires separate, properly sized air intake and vent lines.
The furnace shall not be connected to any type of B, BW or L vent or
vent connector, and not connected to any portion of a factory-built or
masonry chimney
The furnace shall not be connected to a chimney flue serving a sepa-
rate appliance designed to burn solid fuel.

 CAUTION

When combustion air pipe is installed above a suspended ceiling or
when it passes through a warm and humid space, the pipe may need
insulated if two feet or more of pipe is exposed.
Vent piping must be insulated if it will be subjected to freezing tem-
peratures such as routing through unheated areas or through an
unused chimney.

!

!

Содержание TM9M

Страница 1: ...Variable Speed or PSC Modulating Furnace 16 Thermostat Chart Single Stage Heat Pump Variable Speed or PSC Modulating Furnace 17 Thermostat Chart Two Stage Heat Pump Variable Speed or PSC Modulating Fu...

Страница 2: ...The air filter must be replaced upon substantial completion of the construction process Clean furnace duct work and components upon substantial completion of the construction process and verify furna...

Страница 3: ...urisdiction In the United States and Canada follow all codes and standards for the following using the latest edition available STEP 1 Safety US National Fuel Gas Code NFGC NFPA 54 ANSI Z223 1 and the...

Страница 4: ...in every dwelling building or structure used in whole or in part for resi dential purposes including those owned or operated by the Com monwealth and where the side wall exhaust vent termination is l...

Страница 5: ...shall be attached in such a manner as to prevent leaks DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These flanges are rotated down for shipment In order to use the flanges...

Страница 6: ...When lifting the furnace support the ends of the furnace rather than lifting by the cabinet flanges at the return air openings bottom or sides or supply air opening It is acceptable to use the primary...

Страница 7: ...coils are factory shipped for installation in either upflow or down flow applications with no conversion Position the coil casing over or under the furnace opening as shown in Figure 7 after configur...

Страница 8: ...coil and the top of the duct Refer to Table 2 COIL FURNACE ASSEMBLY HD SERIES COILS Horizontal duct coils are referred to as HD series coils This coil must be connected using a supply duct transition...

Страница 9: ...Q DGGLWLRQDO 6833 1 RPEXVWLRQ LU QOHW 5 7851 1 9HQW RQQHFWLRQ 2XWOHW 9HQW RQQHFWLRQ 2XWOHW 9HQW RQQHFWLRQ 2XWOHW Table 3 Cabinet and Duct Dimensions BTUH kW Input Nominal CFM m3 min Cabinet Size Cabin...

Страница 10: ...Gas piping may be connected from either side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace Refer to Figures 13 and 16 DANGER An overpressure protection device...

Страница 11: ...rger 43 orifices which will bring the input rate back up to approxi mately 76 000 BTU H which is what it should be for that furnace at 6 000 feet SECTION V ELECTRICAL POWER ELECTRICAL POWER CONNECTION...

Страница 12: ...iring to connect the Y and C terminals on the furnace control board to the proper wires on the con densing unit unit outside The 24 volt 40 VA transformer is sized for the furnace components only and...

Страница 13: ...Full Stage Heat Clipping Jumper W914 for electric heat on thermostat is not necessary C 24 Volt Common Y Compressor SINGLE STAGE AIR CONDITIONER Y Compressor Contactor SINGLE STAGE AIR CONDITIONER C...

Страница 14: ...ommon R 24 Volt Hot Y1 Single Stage Compressor MODULATING FURNACE CONTROL G Fan MODULATING FURNACE Y Y2 Second or Full Stage Compressor DHUM Dehumidification Open on Humidity Rise W Modulating Heat Mo...

Страница 15: ...is not necessary C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor MODULATING FURNACE CONTROL G Fan MODULATING FURNACE Y Y2 Second or Full Stage Compressor DHUM Dehumidification Open on Humidi...

Страница 16: ...ND DEFROST CONTROL X L Malfunction Light W Auxiliary Heat SINGLE STAGE HEAT PUMP Y2 Second Stage Compressor Step 9 of Thermostat Installer Configuration Menu must be set to Pump OFF Step 1 of Thermost...

Страница 17: ...sing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot W1 OUT First Stage Heat W2 OUT Second Stage Heat Y2 OUT Second Stage Compressor Y1 Single Stage Compressor X L Malfunction Light Y2 Second S...

Страница 18: ...Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR AUX Auxiliary Heat Step 1 of Thermostat Installer Configuration Menu must be set to HP2 Selection of GAS ELEC switch on thermostat not necessary Thermostat...

Страница 19: ...the burners will stop fir ing as soon as the W signal is removed 2 Defrost Cycle When both a W signal and a Y2 signal are pres ent the modulating firing rate will operate at a constant 80 firing rate...

Страница 20: ...rain and drain hose located in the loose parts bag The intake drain hose is to be installed by con necting it to the inlet pipe coupling and to the collector box as shown in Figure 25 27 and 28 The dr...

Страница 21: ...ff so that no sagging loops will collect and hold condensate which will cause the furnace to not operate Shorten pressure switch hose Re route and shorten pressure switch hose Shorten rain gutter hose...

Страница 22: ...tch hose to this position NOTE May require the longer hose that is provided with wider cabinets Move condensate drain hose to this position May exit either side of the cabinet Move rain gutter hose to...

Страница 23: ...ch hose to this position NOTE May require the longer hose that is provided with wider cabinets Change condensate drain connection to the 90 fitting provided Move condensate drain hose to this position...

Страница 24: ...tting provided Move condensate drain hose to this position Move rain gutter hose to this position Change condensate drain connection to the 90 fitting provided Move condensate drain hose to this posit...

Страница 25: ...mbustion air pipe 6 All models are supplied with 2 5 1 cm vent connections When the pipe must be increased to 3 7 6 cm diameter the transition from 2 to 3 must be done as close to the furnace as possi...

Страница 26: ...5 80 000 4 125 100 000 2 20 100 000 2 NA 100 000 3 80 100 000 3 60 100 000 4 145 100 000 4 125 120 000 3 80 120 000 3 60 120 000 4 145 120 000 4 125 Elevation 4001 5000 Elevation 8001 9000 Model Input...

Страница 27: ...AIR VENTING FIGURE 29 Dimensions TABLE 8 Elbow Dimensions Elbow A Dimension Illustrated in Figure 29 2 Standard 2 5 16 3 Standard 3 1 16 2 Sweep 3 1 4 3 Sweep 4 1 16 TABLE 9 Equivalent Length of Fitti...

Страница 28: ...ements of the gas supplier 12 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 30 5 cm or in accordance with local insta...

Страница 29: ...furnace must have a separate vent pipe Under NO circumstances can the two vent pipes be tied together The combustion air side of the two pipe configuration shown in Figures 32 and 33 can be installed...

Страница 30: ...entering the terminal Also the terminal assembly should be located as far as possible from a swimming pool or a location where swimming pool chemicals might be stored Be sure the terminal assembly fol...

Страница 31: ...inlet opening to which it connects 4 The duct shall terminate within 12 30 5 cm above and within 24 61 cm horizontally from the burner level of the appliance having the largest input 5 A square or re...

Страница 32: ...tion provides an adequate supply of air for combustion and ventilation VENT BLOWER ROTATION For ease of venting the vent blower may be rotated 90 in either direc tion For upflow installations the vent...

Страница 33: ...rapid green signal indicating that the furnace is still in TEST MODE 9 When startup tests are completed turning off power to the board will take the furnace out of TEST MODE and will restore normal op...

Страница 34: ...116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 4...

Страница 35: ...actory set to deliver an air temperature rise near the midpoint of the nameplate temperature rise range If more air is desired lower tem perature rise move the jumper to the 10 position If less air is...

Страница 36: ...sample for analysis it is permissible to drill a small hole in the plastic flue pipe for a sample probe provided that the vent piping is PVC and the hole is properly sealed afterwards If using a poly...

Страница 37: ...1175 1129 1077 1011 925 837 120D20 High 2701 2620 2533 2429 2338 2227 2112 1993 1861 1706 Medium High 2125 2083 2046 1994 1955 1901 1857 1737 1621 1497 Medium Low 1664 1664 1547 1619 1580 1554 1468 1...

Страница 38: ...ed with a high temperature limit control mounted to the left side of the furnace vestibule panel This limit switch will open and shut off gas to the burners if it detects excessive air temperature in...

Страница 39: ...th inducer pressure below pressure switch setpoint switch is closed when it should be open Check pressure switch and pressure transducer Three Red Flashes Pressure switch open with inducer pressure ab...

Страница 40: ...seconds The LED will flash three green flashes when the memory has been cleared then will resume the normal slow green flash after a five second pause SECTION XI REPLACEMENT PARTS LIST DESCRIPTION MOT...

Страница 41: ...ID plug missing OR not connected properly None Slow Green Rapid Green Slow Amber Rapid Amber 2 Amber 3 Amber 4 Amber 5 Amber 6 Amber Steady Red 1 Red 2 Red 3 Red 4 Red 5 Red 6 Red 7 Red 8 Red 9 Red 1...

Страница 42: ...1083293 UIM D 1116 42 Johnson Controls Unitary Products NOTES...

Страница 43: ...neutral Ground wire is connected Line voltage value to furnace volts AC Low voltage value between R and C on furnace control board volts AC Thermostat Type Other System Equipment and Accessories Owne...

Страница 44: ...Calculated input in btuh clock the gas meter Nat Gas Only Manifold Gas Pressure in w c furnace must be in TEST mode for setup Inlet Gas Pressure in w c LP Gas Conversion Kit Part Used Burner flame in...

Отзывы: