P5417052
21
(1) Standard condensate connection is on the rear of the unit, viewed from the discharge grilles. The
condensate connection can also be connected to the left side of the unit.
Refer to the section 5.2.7 for details.
7.
Condensate Piping
Unit: inch (mm)
Model
A
B
C
f
D
TIWM006B21S
TIWM008B21S
TIWM012B21S
22-3/8
(568)
4-3/16
(107)
1-3/4
(45)
2-9/16
(65)
TIWM015B21S
TIWM018B21S
TIWM024B21S
TIWM030B21S
21-5/8
(550)
5-9/16
(141)
1-5/8
(42)
3-1/8
(80)
Do not run condensate piping into underground areas near sanitary or sewage lines where toxic
and corrosive gas can seep into the system. This creates a pathway for the flow of poisonous gas to
penetrate inhabited areas.
● Check to ensure that the condensate piping discharges moisture properly. If connected incorrectly, it can
cause structural damage to indoor wall and ceiling surfaces and damage to furniture and carpeting.
● Avoid sloping the condensate piping upward as it will impede drainage. Otherwise, moisture will settle back
into the unit and it may cause the water leakage when unit operation stops.
● Do not connect condensation drainage with sanitary or sewer lines or any other condensate piping.
● When the main condensate piping is connected with other indoor units, the connected position of each
indoor unit must be higher than the main pipe. The pipe size of the main condensate piping must be large
enough according to the unit size and number of units.
● After performing condensate piping work and electrical wiring, check to ensure that water outflow is as
smooth as in the following procedure.
NOTICE
● In order to properly condensate water, mount the indoor unit on a slight incline to the condensate piping
connection side. (Installed 1/16 to 1/8 inch (2 to 3mm) relative to the unit level.)
● When the left side piping is selected, the condensate piping outlet should be on the left side.
If it is not on the left side and the mounting plate is secured onto the wall with right down slope, the
condensate could flow back into the unit, causing a leak from the condensate pan.
NOTICE
A
B
C
(φ
D)
Condensate Piping
Connection (VP16)
Exterior Contour for Indoor Unit
Hole for
Rear Piping