5604542-UIM-B-0419

Johnson Controls Ducted Systems

9

TABLE 5: 

YHE30 Heat Charging Charts

YHE/TH4/THE/RHP14L30

AE30, RFCX30BE

CFM

Ambient Temperature (°F)

60

47

40

30

17

10

Indoor Temperature (°F)

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

800

Liquid Pressure (PSIG)

379 428 477

355

404

453

317

380

442

326

373

420

302 343 384

295 336 378

1000

Liquid Pressure (PSIG)

349 397 445

329

365

425

306

360

414

304

350

396

285 324 364

278 318 358

1200

Liquid Pressure (PSIG)

320 366 413

303

350

396

294

340

385

282

327

373

268 306 345

262 301 339

-

Suction Pressure (PSIG)

130

106

94

78

59

52

YHE/TH4/THE/RHP14L30

CF/CM/CU(36,42), AP/AVC30, AP/AE/AVC36, RFCX30BP, RFCX36B(P,E), RFCX36CE, RFCX42CE 

CFM

Ambient Temperature (°F)

60

47

40

30

17

10

Indoor Temperature (°F)

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

800

Liquid Pressure (PSIG)

366 413 460

343

390

437

306

366

426

315

360

405

291 331 370

284 324 364

1000

Liquid Pressure (PSIG)

337 383 429

317

352

410

295

347

399

293

338

382

275 313 351

268 307 346

1200

Liquid Pressure (PSIG)

308 353 398

292

337

382

284

328

372

272

316

360

258 295 332

252 290 327

-

Suction Pressure (PSIG)

127

104

92

76

57

51

TABLE 6: 

YHE35 Heat Charging Charts 

YHE/TH4/RHP14L35

CF/CM/CU36, AE36, AVC36, RFCX36(B,C)E

CFM

Ambient Temperature (°F)

60

47

40

30

17

10

Indoor Temperature (°F)

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

1000

Liquid Pressure (PSIG)

353

401

449 331

378

424

319 368 417 301

349

397

280

325

370

271

316

362

1200

Liquid Pressure (PSIG)

331

376

421

311

344

403

302 338 398 287

332

377

268

312

356

258

303

348

1400

Liquid Pressure (PSIG)

309

351

393 292

336

381

285 332 379 272

315

357

255

299

342

246

290

335

-

Suction Pressure (PSIG)

136

109

96

80

60

52

YHE/TH4/RHP14L35

CF/CM/CU42, AE42, AVC42, RFCX42CE

CFM

Ambient Temperature (°F)

60

47

40

30

17

10

Indoor Temperature (°F)

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

1000

Liquid Pressure (PSIG)

342

389

436 321

367

412

310 357 404 293

339

385

272

316

359

263

307

351

1200

Liquid Pressure (PSIG)

321

365

409 302

334

391

293 328 386 278

322

366

260

303

346

251

294

338

1400

Liquid Pressure (PSIG)

300

341

382 283

327

370

277 322 368 264

306

347

248

290

332

238

282

325

-

Suction Pressure (PSIG)

136

109

96

80

60

52

YHE/TH4/RHP14L35

CF/CM/CU48

CFM

Ambient Temperature (°F)

60

47

40

30

17

10

Indoor Temperature (°F)

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

1000

Liquid Pressure (PSIG)

337

383

429 316

361

406

305 352 398 288

334

379

268

311

354

259

302

346

1200

Liquid Pressure (PSIG)

317

360

403 298

329

385

289 323 380 274

317

361

256

298

340

247

290

333

1400

Liquid Pressure (PSIG)

296

336

376 279

322

365

273 317 362 260

301

342

244

286

327

235

278

321

-

Suction Pressure (PSIG)

136

109

96

80

60

52

TABLE 7: 

YHE36 Heat Charging Charts

YHE/THE/TH4/RHP14L36

CF/CM/CU48, AP(37,48) AE/AVC(42,48), RFCX37CP, RFCX42CE, RFCX48CE, RFCX48D(P,E)

CFM

Ambient Temperature (°F)

60

47

40

30

17

10

Indoor Temperature (°F)

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

1000

Liq. Pressure (Subcool)

344 391 439 322

368

414

314 359 404 298 343

388

275

318

362

259 300

342

1200

Liq. Pressure (Subcool)

322 367 413 302

347

393

295 339 384 282 326

370

260

304

348

249 290

332

1400

Liq. Pressure (Subcool)

301 344 387 283

328

373

277 320 364 267 310

353

245

289

334

240 281

322

-

Suction Pressure (PSIG)

121

91

92

69

53

45

Содержание TH4 Series

Страница 1: ...2 B 32 42 s Gen2 21 LIST OF TABLES Maximum Minimum Operating Limit Conditions 2 R 410A Saturation Properties 8 YHE18 Heat Charging Charts 8 YHE24 Heat Charging Charts 8 YHE30 Heat Charging Charts 9 YH...

Страница 2: ...on the UPGNET web site Provide adequate structural support for the unit ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 410A unit it is required that the outdoor uni...

Страница 3: ...HU EUDFH XQGHU FHQWHU RI FRPSUHVVRU 127 QVXUH DGHTXDWH ZDOO VXSSRUW 87 21 6SHFLDO FDUH PXVW EH WDNHQ WR DYRLG UHFLUFXODWLRQ RI GLVFKDUJH DLU WKURXJK RXWGRRU FRLO FIGURE 2 Alternative Installation Clea...

Страница 4: ...taken not to damage the couplings or kink the tubing Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary If soft copper must be used care must be...

Страница 5: ...ide the grommet back into original position 6 Protect the vapor valve with a wet rag and braze the vapor line con nection to the outdoor unit The nitrogen flow should be exiting the system from the va...

Страница 6: ...place on TXV and install liq uid line to the top of the thermal expansion valve Adjust assembly so liquid line aligns with hole in access panel Hand tighten the liq uid line and apply an additional 1...

Страница 7: ...e for the indoor unit s static pressure vs CFM or to a curve chart CHARGING THE UNIT The factory charge in the outdoor unit includes enough charge for the unit 15 ft 4 6 m of refrigerant piping and th...

Страница 8: ...80 60 70 80 60 70 80 60 70 80 60 70 80 450 Liquid Pressure PSIG 381 427 472 351 394 436 336 384 432 318 363 409 274 324 375 276 318 361 600 Liquid Pressure PSIG 345 389 434 319 355 404 308 354 400 294...

Страница 9: ...58 303 348 1400 Liquid Pressure PSIG 309 351 393 292 336 381 285 332 379 272 315 357 255 299 342 246 290 335 Suction Pressure PSIG 136 109 96 80 60 52 YHE TH4 RHP14L35 CF CM CU42 AE42 AVC42 RFCX42CE C...

Страница 10: ...oor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1400 Liquid Pressure PSIG 336 384 433 312 359 406 293 344 395 279 321 364 230 290 349 248 282 316 1600 Liquid Pressure PSIG 320...

Страница 11: ...cess panel FIELD CONNECTIONS POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and within sight of the unit 2 Remove the screws at the top and sides of the corner cover Sl...

Страница 12: ...ton be supplied at all times To see connection diagrams of all UPG equipment the Low Voltage System Wiring document is available online at www upgnet com in the Product Catalog Section INDOOR CUBIC F...

Страница 13: ...ing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 11 TEST...

Страница 14: ...rrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulates...

Страница 15: ...ur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal d...

Страница 16: ...te flash code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will ca...

Страница 17: ...OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUST CONFOR...

Страница 18: ...RAL 1 2 3 4 5 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE HEATER HPS HIGH PRESS SWITCH HS HEATER SWITCH CS COIL SENSOR LPS LOW PRESS SWITCH RV REVERSING VALVE SC START CAPAC...

Страница 19: ...LE PERSONAL INJURY TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCA...

Страница 20: ...RICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE...

Страница 21: ...TOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE HEATER HPS HIGH PRESS SWITCH HS HEATER SWITCH CS COIL SENSOR LPS LOW PRESS SWITC...

Страница 22: ...5604542 UIM B 0419 22 Johnson Controls Ducted Systems NOTES...

Страница 23: ...ta Venting if applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas pi...

Страница 24: ...ON OFF or the appropriate Value for the fields that apply to the defrost control board installed Run Time Time and Temperature board only 30 60 or 90 minutes Bonnet Sensor Present HEAT Refrigerant Ch...

Отзывы: