5604542-UIM-B-0419
8
Johnson Controls Ducted Systems
CHARGING WITH GAUGES
All units include a cooling charging chart for cooling. The heating
charging charts in Table 3 through Table 10 in this document use the
chart corresponding to the installed indoor coil. It can also be obtained
at
www.upgnet.com
under the Service Application Data section.
Before using gauges, confirm that your gauges are accurate by
comparing the gauges against a calibrated pressure gauge that
has been calibrated against a national standard. If a calibrated
pressure gauge is not available, place a R-410A virgin refrigerant
container in a conditioned space long enough to come to tempera-
ture equilibrium with the surroundings. Then measure the tem-
perature of the air and the pressure of the refrigerant and compare
it to the following table:
:
Before measuring the pressures, use the method above to check the air
flow and then consult the table and match the liquid pressure to that air
flow.
Reference the heat charging charts in Table 3 through Table 10
.
CAUTION
Refrigerant charging should only be carried out by a qualified air con-
ditioning contractor.
CAUTION
Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.
!
!
TABLE 2:
R-410A Saturation Properties
Temp
(°F)
Pressure
(Psig)
Temp
(°F)
Pressure
(Psig)
Temp
(°F)
Pressure
(Psig)
40
119
75
218
110
365
45
130
80
236
115
391
50
143
85
255
120
418
55
156
90
274
125
447
60
170
95
295
130
477
65
185
100
317
–
–
70
201
105
341
–
–
TABLE 3:
YHE18 Heat Charging Charts
YHE/TH4/RHP14L18
CF/CM/CU18, AP18B, AE18B, AVC18B, RFCX18B(P,E)
CFM
Ambient Temperature (°F)
60
47
40
30
17
10
Indoor Temperature (°F)
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
450
Liquid Pressure (PSIG)
381
427 472 351 394 436
336
384
432
318
363 409 274
324
375
276
318
361
600
Liquid Pressure (PSIG)
345
389 434 319 355 404
308
354
400
294
338 382 263
308
354
259
300
342
750
Liquid Pressure (PSIG)
309
352 395 286 329 372
281
325
369
270
313 356 251
292
333
243
283
322
-
Suction Pressure (PSIG)
136
111
97
80
59
52
YHE/TH4/RHP14L18
CF/CM/CU24, AP24B, AE24B, AVC24B, RFCX24BE
CFM
Ambient Temperature (°F)
60
47
40
30
17
10
Indoor Temperature (°F)
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
450
Liquid Pressure (PSIG)
387
434 480 357 400 444
342
390
439
323
370 416 278
330
381
280
324
367
600
Liquid Pressure (PSIG)
351
396 441 324 361 411
314
360
407
299
344 389 267
313
360
264
306
347
750
Liquid Pressure (PSIG)
315
358 402 291 335 378
286
330
375
275
318 362 256
297
339
247
288
328
-
Suction Pressure (PSIG)
145
119
104
85
63
55
TABLE 4:
YHE24 Heat Charging Charts
YHE/TH4/RHP14L24
CF/CM/CU24, AP24B, AE24B, AVC24B, RFCX24B(P,E)
CFM
Ambient Temperature (°F)
60
47
40
30
17
10
Indoor Temperature (°F)
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
600
Liquid Pressure (PSIG)
399
449 498 368 418 467
353
401
449
332
380 427 298
344
389
286
331
375
800
Liquid Pressure (PSIG)
359
407 454 335 366 431
322
358
415
306
352 397 280
323
365
269
312
354
1000
Liquid Pressure (PSIG)
319
365 410 301 348 394
292
337
382
280
324 367 262
302
342
253
293
333
-
Suction Pressure (PSIG)
136
109
96
80
60
52
YHE/TH4/RHP14L24
CF/CM/CU30, AP30, AE30, AVC30, RFCX30B(P,E)
CFM
Ambient Temperature (°F)
60
47
40
30
17
10
Indoor Temperature (°F)
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
600
Liquid Pressure (PSIG)
378
425 472 349 396 443
335
380
426
315
360 405 283
326
369
271
313
356
800
Liquid Pressure (PSIG)
340
385 430 318 347 409
305
339
393
290
333 376 265
306
346
255
295
336
1000
Liquid Pressure (PSIG)
302
346 389 285 329 374
277
320
362
265
307 348 248
286
324
240
278
316
-
Suction Pressure (PSIG)
136
111
97
80
59
52