Johnson Controls Ducted Systems

FAULT CODE DISPLAY

The control shall provide status codes using the LED. Status codes
indicate the state of operation of the unit but do not represent a fault.
The table below describes the LED displays during status codes. Status
codes will not be displayed when a fault code is present.

The control shall provide fault codes using the Status LED. The table
below describes the LED displays during fault codes. Unless otherwise
specified, the control shall provide flashes that are a 1/3 second on and
1/3 second off for fault codes. The control shall only display a single
fault code on the LED. The control shall display the fault code on the
LED repeatedly with a 2 second off period between repetitions of the
fault code. If multiple fault codes are present at the same time, the LED
shall display only the most recent fault. 

The table below shows a number that represents the number of flashes
for the specified code. For instance, a flash code entry of 3 indicates
that the control will energize the output for three 1/3 second on, 1/3 sec-
ond off flashes, wait two seconds, then energize the output for three
more 1/3 second on, 1/3 second off flashes and repeat.

Demand Defrost

The control maintains proper airflow through the outdoor coil during
heating operation by melting frost and ice that may form on the coil.
Frost may accumulate unevenly in different sections of the coil because
of the arrangement of the refrigeration circuit within the coil. The control
may initiate a defrost cycle even when the coil is not completely cov-
ered with frost. This is normal operation.

The control regulates the defrost operation of the heat pump based on
accumulated compressor run time, outdoor coil temperature, and out-
door ambient temperature. The control will cause the heat pump unit to
operate in the normal heating mode until it determines that a defrost
cycle is needed.

All defrost timings are based on accumulated compressor run time.

 FIGURE 14: 

Demand Defrost Control Module

$

'()5267&859(

7(67

& 5

2 < : :RXW

+36

/36

59

&0

&2,/

$0%

67$786/('

TABLE 13: 

Status Code Display

No power to the control

No Faults active 
Nothing energized

OFF

Compressor Operation 
Active 

No Faults active 
M energized

ON

Control normal operation –
no call for compressor

No faults active 
Y not present

2s ON/2s OFF

Control normal operation –
in ASCD period

No faults active, 
Y present, ASCD 
timer not expired

0.1 sec ON/0.1 sec OFF

TABLE 14: 

Status

Description

STATUS LED

High -pressure switch fault (not in lockout yet)

2 Flashes

System in high-pressure switch lockout 
(last mode of operation was normal compressor 
operation)

3 Flashes

System in high-pressure switch lockout 
(last mode of operation was defrost)

4 Flashes

System in low-pressure switch lockout 
(last mode of operation was normal compressor 
operation)

5 Flashes

Low Voltage (<19.2VAC) preventing further 
relay outputs for > 2 seconds

6 Flashes

Low Voltage (<16VAC) stopped current relay 
outputs for > 2 seconds

7 Flashes

Coil sensor failure (Open or Shorted)

8 Flashes

Outdoor ambient sensor failure (Open or Shorted)

9 Flashes

Control Failure

10 Flashes

Содержание TH4 Series

Страница 1: ...2 B 32 42 s Gen2 21 LIST OF TABLES Maximum Minimum Operating Limit Conditions 2 R 410A Saturation Properties 8 YHE18 Heat Charging Charts 8 YHE24 Heat Charging Charts 8 YHE30 Heat Charging Charts 9 YH...

Страница 2: ...on the UPGNET web site Provide adequate structural support for the unit ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 410A unit it is required that the outdoor uni...

Страница 3: ...HU EUDFH XQGHU FHQWHU RI FRPSUHVVRU 127 QVXUH DGHTXDWH ZDOO VXSSRUW 87 21 6SHFLDO FDUH PXVW EH WDNHQ WR DYRLG UHFLUFXODWLRQ RI GLVFKDUJH DLU WKURXJK RXWGRRU FRLO FIGURE 2 Alternative Installation Clea...

Страница 4: ...taken not to damage the couplings or kink the tubing Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary If soft copper must be used care must be...

Страница 5: ...ide the grommet back into original position 6 Protect the vapor valve with a wet rag and braze the vapor line con nection to the outdoor unit The nitrogen flow should be exiting the system from the va...

Страница 6: ...place on TXV and install liq uid line to the top of the thermal expansion valve Adjust assembly so liquid line aligns with hole in access panel Hand tighten the liq uid line and apply an additional 1...

Страница 7: ...e for the indoor unit s static pressure vs CFM or to a curve chart CHARGING THE UNIT The factory charge in the outdoor unit includes enough charge for the unit 15 ft 4 6 m of refrigerant piping and th...

Страница 8: ...80 60 70 80 60 70 80 60 70 80 60 70 80 450 Liquid Pressure PSIG 381 427 472 351 394 436 336 384 432 318 363 409 274 324 375 276 318 361 600 Liquid Pressure PSIG 345 389 434 319 355 404 308 354 400 294...

Страница 9: ...58 303 348 1400 Liquid Pressure PSIG 309 351 393 292 336 381 285 332 379 272 315 357 255 299 342 246 290 335 Suction Pressure PSIG 136 109 96 80 60 52 YHE TH4 RHP14L35 CF CM CU42 AE42 AVC42 RFCX42CE C...

Страница 10: ...oor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1400 Liquid Pressure PSIG 336 384 433 312 359 406 293 344 395 279 321 364 230 290 349 248 282 316 1600 Liquid Pressure PSIG 320...

Страница 11: ...cess panel FIELD CONNECTIONS POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and within sight of the unit 2 Remove the screws at the top and sides of the corner cover Sl...

Страница 12: ...ton be supplied at all times To see connection diagrams of all UPG equipment the Low Voltage System Wiring document is available online at www upgnet com in the Product Catalog Section INDOOR CUBIC F...

Страница 13: ...ing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 11 TEST...

Страница 14: ...rrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulates...

Страница 15: ...ur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal d...

Страница 16: ...te flash code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will ca...

Страница 17: ...OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUST CONFOR...

Страница 18: ...RAL 1 2 3 4 5 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE HEATER HPS HIGH PRESS SWITCH HS HEATER SWITCH CS COIL SENSOR LPS LOW PRESS SWITCH RV REVERSING VALVE SC START CAPAC...

Страница 19: ...LE PERSONAL INJURY TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCA...

Страница 20: ...RICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE...

Страница 21: ...TOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE HEATER HPS HIGH PRESS SWITCH HS HEATER SWITCH CS COIL SENSOR LPS LOW PRESS SWITC...

Страница 22: ...5604542 UIM B 0419 22 Johnson Controls Ducted Systems NOTES...

Страница 23: ...ta Venting if applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas pi...

Страница 24: ...ON OFF or the appropriate Value for the fields that apply to the defrost control board installed Run Time Time and Temperature board only 30 60 or 90 minutes Bonnet Sensor Present HEAT Refrigerant Ch...

Отзывы: