290699-YIM-B-0607
Unitary Products Group
29
TABLE 16: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTIPLIER
208
208
0.75
240
230
0.92
480
460
0.92
600
575
0.92
TABLE 17: VOLTAGE LIMITATIONS
1
1.
Utilization Range “A” in accordance with ARI Standard
110.
POWER SUPPLY
VOLTAGE
MIN.
MAX.
208/230-3-60
187
252
460-3-60
432
504
575-3-60
540
630