VFD Two-stage medium static
Note:
•
MCA = minimum circuit ampacity
•
f/b = fuse/breaker
•
Fuse is a dual element, time delay type
•
Breaker is a HACR type per NEC
Table 21: YV28 to YV50 VFD two-stage medium static without power exhaust
Comp. 1
Comp. 2
Min
disconnect
rating
Min
disconnect
rating/120V
trans
Size
(tons)
Nominal
unit
voltage
RLA LRA RLA LRA
OD fan
motors
each
FLA
OD fan
motors
each
LRA
Supply
blower
motor
FLA
Supply
blower
motor
LRA
120 V
trans
FLA
MCA
A
Max
f/b
size
A
FLA
LRA
MCA
with
120 V
trans
A
Max
f/b
size
with
120V
trans
A
FLA
LRA
208-3-60 41.0 304 41.0 304
4.0
21.0
28.0
173.44
14.4
136
175
145
865.4
151
175 161.5 879.8
230-3-60 41.0 304 41.0 304
4.2
21.0
28.0
173.44
13.0
137
175
146
865.4
150
175 160.8 878.4
460-3-60 19.2 147 19.2 147
2.1
10.5
14.0
86.72
6.5
66
80
70
422.7
72
90
77.4 429.2
YV28
(27.5)
575-3-60 16.7 122 16.7 122
1.6
7.8
11.0
71.77
5.2
55
70
58
347.0
60
75
64.4 352.2
208-3-60 44.2 315 44.2 315
4.0
21.0
28.0
173.44
14.4
143
175
152
887.4
158
200 168.8 901.8
230-3-60 44.2 315 44.2 315
4.2
21.0
28.0
173.44
13.0
144
175
153
887.4
157
200 168.1 900.4
460-3-60 22.4 158 22.4 158
2.1
10.5
14.0
86.72
6.5
73
90
77
444.7
79
100
84.8 451.2
YV30
(30)
575-3-60 18.6 136 18.6 136
1.6
7.8
11.0
71.77
5.2
59
75
63
375.0
64
80
68.8 380.2
208-3-60 48.1 351 48.1 351
4.0
21.0
28.0
173.44
14.4
152
200
161
959.4
167
200 177.8 973.8
230-3-60 48.1 351 48.1 351
4.2
21.0
28.0
173.44
13.0
153
200
162
959.4
166
200 177.1 972.4
460-3-60 24.7 197 24.7 197
2.1
10.5
14.0
86.72
6.5
78
100
83
522.7
84
100
90.0 529.2
YV35
(35)
575-3-60 22.4 135 22.4 135
1.6
7.8
11.0
71.77
5.2
68
90
72
373.0
73
90
77.5 378.2
208-3-60 48.1 351 48.1 351
4.0
21.0
42.0
234
14.4
166
200
177 1020.0 181
225 193.9 1034.4
230-3-60 48.1 351 48.1 351
4.2
21.0
42.0
234
13.0
167
200
178 1020.0 180
225 193.2 1033.0
460-3-60 24.7 197 24.7 197
2.1
10.5
21.0
117
6.5
85
100
91
553.0
91
110
98.1 559.5
YV40
(40)
575-3-60 22.4 135 22.4 135
1.6
7.8
18.0
95.94
5.2
75
90
80
397.1
80
100
85.6 402.3
208-3-60 67.3 485 67.3 485
7.2
39.6
42.0
234
14.4
222
275
236 1362.4 237
300 252.8 1376.8
230-3-60 67.3 485 67.3 485
6.8
39.6
42.0
234
13.0
221
275
234 1362.4 234
300 249.3 1375.4
460-3-60 32.7 215 32.7 215
3.4
19.8
21.0
117
6.5
108
125
115
626.2
115
125 122.5 632.7
YV50
(50)
575-3-60 26.3 175 26.3 175
2.7
15.8
18.0
95.94
5.2
88
110
94
509.1
93
110
99.6 514.3
Table 22: YV28 to YV50 VFD two-stage medium static on/off power exhaust
Comp. 1
Comp. 2
Min
disconnect
rating
Min
disconnect
rating/120V
trans
Size
(tons)
Nominal
unit
voltage
RLA LRA RLA LRA
OD fan
motors
each
FLA
OD fan
motors
each
FLA
Supply
blower
motor
FLA
Supply
blower
motor
LRA
Power
exhaus
t VFD
FLA
Power
exhaus
t motor
LRA
120 V
trans
FLA
MCA
A
Max
f/b
size
A
FLA
LRA
MCA
with
120 V
trans
A
Max
f/b
size
with
120V
trans
A
FLA
LRA
208-3-60 41.0 304 41.0 304
4.0
21.0
28.0
173.4
4.0
21.0
14.4
144
175
154
907
159
175
171
922
230-3-60 41.0 304 41.0 304
4.2
21.0
28.0
173.4
4.2
21.0
13.0
145
175
155
907
158
175
170
920
460-3-60 19.2 147 19.2 147
2.1
10.5
14.0
86.7
2.1
10.5
6.5
70
80
75
444
76
90
82
450
YV28
(27.5)
575-3-60 16.7 122 16.7 122
1.6
7.8
11.0
71.8
1.6
7.8
5.2
58
70
62
363
63
80
68
368
208-3-60 44.2 315 44.2 315
4.0
21.0
28.0
173.4
4.0
21.0
14.4
151
175
161
929
166
200
178
944
230-3-60 44.2 315 44.2 315
4.2
21.0
28.0
173.4
4.2
21.0
13.0
153
175
163
929
166
200
178
942
460-3-60 22.4 158 22.4 158
2.1
10.5
14.0
86.7
2.1
10.5
6.5
77
90
82
466
84
100
90
472
YV30
(30)
575-3-60 18.6 136 18.6 136
1.6
7.8
11.0
71.8
1.6
7.8
5.2
62
80
66
391
68
80
72
396
208-3-60 48.1 351 48.1 351
4.0
21.0
28.0
173.4
4
21.0
14.4
160
200
170 1001 175
200
187 1016
230-3-60 48.1 351 48.1 351
4.2
21.0
28.0
173.4
4.2
21.0
13.0
161
200
172 1001 174
200
187 1014
460-3-60 24.7 197 24.7 197
2.1
10.5
14.0
86.7
2.1
10.5
6.5
82
100
87
544
89
110
95
550
YV35
(35)
575-3-60 22.4 135 22.4 135
1.6
7.8
11.0
71.8
1.6
7.8
5.2
71
90
75
389
76
90
81
394
208-3-60 48.1 351 48.1 351
4.0
21.0
42.0
234.0
7.2
39.6
14.4
181
225
194 1099 195
225
210 1114
230-3-60 48.1 351 48.1 351
4.2
21.0
42.0
234.0
6.8
39.6
13.0
181
225
194 1099 194
225
209 1112
460-3-60 24.7 197 24.7 197
2.1
10.5
21.0
117.0
3.4
19.8
6.5
92
110
98
593
98
110
106
599
YV40
(40)
575-3-60 22.4 135 22.4 135
1.6
7.8
18.0
95.9
2.7
15.8
5.2
80
100
86
429
85
100
92
434
208-3-60 67.3 485 67.3 485
7.2
39.6
42.0
234.0
7.2
39.6
14.4
237
300
253 1442 251
300
269 1456
230-3-60 67.3 485 67.3 485
6.8
39.6
42.0
234.0
6.8
39.6
13.0
234
300
250 1442 247
300
265 1455
460-3-60 32.7 215 32.7 215
3.4
19.8
21.0
117.0
3.4
19.8
6.5
115
125
123
666
121
150
130
672
YV50
(50)
575-3-60 26.3 175 26.3 175
2.7
15.8
18.0
95.9
2.7
15.8
5.2
93
110
100
541
99
110
106
546
Installation Manual: YORK
®
Sun™ Select YV28 to YV50
46
Johnson Controls Ducted Systems
Содержание Sun Select YV28
Страница 2: ...Tested in accordance with ...
Страница 104: ...Start up sheet Installation Manual YORK Sun Select YV28 to YV50 104 Johnson Controls Ducted Systems ...
Страница 105: ...Installation Manual YORK Sun Select YV28 to YV50 105 Johnson Controls Ducted Systems ...
Страница 106: ...Installation Manual YORK Sun Select YV28 to YV50 106 Johnson Controls Ducted Systems ...
Страница 107: ...Installation Manual YORK Sun Select YV28 to YV50 107 Johnson Controls Ducted Systems ...
Страница 108: ...Installation Manual YORK Sun Select YV28 to YV50 108 Johnson Controls Ducted Systems ...
Страница 109: ...Installation Manual YORK Sun Select YV28 to YV50 109 Johnson Controls Ducted Systems ...