Constant volume high static
Note:
•
MCA = minimum circuit ampacity
•
f/b = fuse/breaker
•
Fuse is a dual element, time delay type
•
Breaker is a HACR type per NEC
Table 15: YV28 to YV50 Constant volume high static without power exhaust
Comp. 1
Comp. 2
Min
disconnect
rating
Min
disconnect
rating/120V
trans
Size
(tons)
Nominal
unit
voltage
RLA LRA RLA LRA
OD fan
motors
each
FLA
OD fan
motors
each
LRA
Supply
blower
motor
FLA
Supply
blower
motor
LRA
120 V
trans
FLA
MCA
A
Max
f/b
size
A
FLA
LRA
MCA
with
120 V
trans
A
Max
f/b
size
with
120V
trans
A
FLA
LRA
208-3-60 41.0 304 41.0 304
4.0
21.0
36.0
234.0
14.4
144
175
154
926
159
175
171
940
230-3-60 41.0 304 41.0 304
4.2
21.0
36.0
234.0
13.0
145
175
155
926
158
175
170
939
460-3-60 19.2 147 19.2 147
2.1
10.5
18.0
117.0
6.5
70
80
75
453
76
90
82
460
YV28
(27.5)
575-3-60 16.7 122 16.7 122
1.6
7.8
14.2
95.9
5.2
58
70
62
371
63
80
68
376
208-3-60 44.2 315 44.2 315
4.0
21.0
36.0
234.0
14.4
151
175
161
948
166
200
178
962
230-3-60 44.2 315 44.2 315
4.2
21.0
36.0
234.0
13.0
152
175
162
948
165
200
177
961
460-3-60 22.4 158 22.4 158
2.1
10.5
18.0
117.0
6.5
77
90
82
475
83
100
89
482
YV30
(30)
575-3-60 18.6 136 18.6 136
1.6
7.8
14.2
95.9
5.2
62
80
66
399
68
80
72
404
208-3-60 48.1 351 48.1 351
4.0
21.0
36.0
234.0
14.4
160
200
170 1020 175
200
187 1034
230-3-60 48.1 351 48.1 351
4.2
21.0
36.0
234.0
13.0
161
200
171 1020 174
200
186 1033
460-3-60 24.7 197 24.7 197
2.1
10.5
18.0
117.0
6.5
82
100
87
553
88
110
95
560
YV35
(35)
575-3-60 22.4 135 22.4 135
1.6
7.8
14.2
95.9
5.2
71
90
75
397
76
90
81
402
208-3-60 48.1 351 48.1 351
4.0
21.0
48.0
312.0
14.4
172
200
184 1098 187
225
201 1112
230-3-60 48.1 351 48.1 351
4.2
21.0
48.0
312.0
13.0
173
200
185 1098 186
225
200 1111
460-3-60 24.7 197 24.7 197
2.1
10.5
24.0
156.0
6.5
88
110
94
592
94
110
102
599
YV40
(40)
575-3-60 22.4 135 22.4 135
1.6
7.8
19.1
126.0
5.2
76
90
81
427
81
100
87
432
208-3-60 67.3 485 67.3 485
7.2
39.6
48.0
312.0
14.4
228
275
243 1440 243
300
260 1455
230-3-60 67.3 485 67.3 485
6.8
39.6
48.0
312.0
13.0
227
275
241 1440 240
300
256 1453
460-3-60 32.7 215 32.7 215
3.4
19.8
24.0
156.0
6.5
111
125
118
665
118
150
126
672
YV50
(50)
575-3-60 26.3 175 26.3 175
2.7
15.8
19.1
126.0
5.2
89
110
95
539
94
110
101
544
Table 16: YV28 to YV50 Constant volume high static with on/off power exhaust
Comp. 1
Comp. 2
Min
disconnect
rating
Min
disconnect
rating/120V
trans
Size
(tons)
Nominal
unit
voltage
RLA LRA RLA LRA
OD fan
motors
each
FLA
OD fan
motors
each
FLA
Supply
blower
motor
FLA
Supply
blower
motor
LRA
Power
exhaus
t VFD
FLA
Power
exhaus
t motor
LRA
120 V
trans
FLA
MCA
A
Max
f/b
size
A
FLA
LRA
MCA
with
120 V
trans
A
Max
f/b
size
with
120V
trans
A
FLA
LRA
208-3-60 41.0 304 41.0 304
4.0
21.0
36.0
234
4.0
21.0
14
152
175
163
968
167
200
180
982
230-3-60 41.0 304 41.0 304
4.2
21.0
36.0
234
4.2
21.0
13
153
175
165
968
166
200
180
981
460-3-60 19.2 147 19.2 147
2.1
10.5
18.0
117
2.1
10.5
7
74
90
79
474
80
90
87
481
YV28
(27.5)
575-3-60 16.7 122 16.7 122
1.6
7.8
14.2
95.94
1.6
7.8
5
61
75
66
387
67
80
72
392
208-3-60 44.2 315 44.2 315
4.0
21.0
36.0
234
4.0
21.0
14
159
200
171
990
174
200
187 1004
230-3-60 44.2 315 44.2 315
4.2
21.0
36.0
234
4.2
21.0
13
161
200
172
990
174
200
187 1003
460-3-60 22.4 158 22.4 158
2.1
10.5
18.0
117
2.1
10.5
7
81
100
87
496
88
100
94
503
YV30
(30)
575-3-60 18.6 136 18.6 136
1.6
7.8
14.2
95.94
1.6
7.8
5
66
80
70
415
71
80
76
420
208-3-60 48.1 351 48.1 351
4.0
21.0
36.0
234
4
21.0
14
168
200
180 1062 183
225
196 1076
230-3-60 48.1 351 48.1 351
4.2
21.0
36.0
234
4.2
21.0
13
169
200
181 1062 182
225
196 1075
460-3-60 24.7 197 24.7 197
2.1
10.5
18.0
117
2.1
10.5
7
86
110
92
574
93
110
99
581
YV35
(35)
575-3-60 22.4 135 22.4 135
1.6
7.8
14.2
95.94
1.6
7.8
5
74
90
79
413
79
100
85
418
208-3-60 48.1 351 48.1 351
4.0
21.0
48.0
312
7.2
39.6
14
187
225
201 1177 201
225
217 1192
230-3-60 48.1 351 48.1 351
4.2
21.0
48.0
312
6.8
39.6
13
187
225
201 1177 200
225
216 1190
460-3-60 24.7 197 24.7 197
2.1
10.5
24.0
156
3.4
19.8
7
95
110
102
632
101
125
109
638
YV40
(40)
575-3-60 22.4 135 22.4 135
1.6
7.8
19.1
126
2.7
15.8
5
81
100
87
459
87
100
93
464
208-3-60 67.3 485 67.3 485
7.2
39.6
48.0
312
7.2
39.6
14
243
300
260 1520 257
300
276 1534
230-3-60 67.3 485 67.3 485
6.8
39.6
48.0
312
6.8
39.6
13
240
300
257 1520 253
300
272 1533
460-3-60 32.7 215 32.7 215
3.4
19.8
24.0
156
3.4
19.8
7
118
150
126
705
124
150
134
711
YV50
(50)
575-3-60 26.3 175 26.3 175
2.7
15.8
19.1
126
2.7
15.8
5
94
110
101
571
100
125
107
576
Installation Manual: YORK
®
Sun™ Select YV28 to YV50
42
Johnson Controls Ducted Systems
Содержание Sun Select YV28
Страница 2: ...Tested in accordance with ...
Страница 104: ...Start up sheet Installation Manual YORK Sun Select YV28 to YV50 104 Johnson Controls Ducted Systems ...
Страница 105: ...Installation Manual YORK Sun Select YV28 to YV50 105 Johnson Controls Ducted Systems ...
Страница 106: ...Installation Manual YORK Sun Select YV28 to YV50 106 Johnson Controls Ducted Systems ...
Страница 107: ...Installation Manual YORK Sun Select YV28 to YV50 107 Johnson Controls Ducted Systems ...
Страница 108: ...Installation Manual YORK Sun Select YV28 to YV50 108 Johnson Controls Ducted Systems ...
Страница 109: ...Installation Manual YORK Sun Select YV28 to YV50 109 Johnson Controls Ducted Systems ...