FORM 201.24-EG1
13
YORK INTERNATIONAL
SAMPLE SELECTION
Water Cooled Condenser (YCWS)
GIVEN – Chill 200 GPM of water from 56ºF to 44ºF and
0.0001 evaporator fouling factor with 85ºF to 95ºF con-
densing water available. Fouling factor of 0.0005 spe-
cial field for the condenser.
FIND – The required unit size capacity, kW, EER, and
water pressure drop.
SOLUTION:
1. Chilled water range = 56ºF - 44ºF = 12ºF and correc-
tion factors are 1.0133 for Tons and 0.9993 for kW for
the cooler.
GPM x Chilled Water Range
2. Capacity (tons) =
24
=
200 x 12
= 100TR
24
2. From the rating, a model YCWS0120SC has a ca-
pacity range required. For the cooler leaving water
temperature of 44ºF and a condenser leaving water
temperature of 95ºF, the unit capacity rating table in-
dicates:
Tons = 110.3
KW = 86.2
EER = 15.4
Correcting for the 12ºF chilled water range and the 0.0005
condenser-fouling factor:
Tons
= 110.3 x 1.0133 x 0.9961 = 111.3TR
KW
= 86.2 x 0.9993 x 1.0065 = 86.7
The unit is suitable.
3. Determine the average full load kW and EER at 95.0
Tons
95.0 X (86.7) = 74KW
111.3
Tons x 12 = 95.0 X 12 = 15.4
EER =
Kw
74
4. Determine the cond. Heat rejection as follows:
Heat Rejection (MBH) = (Tons x 12) + (kW x 3.415)
= (95.0 x 12) + (74 x 3.415)
= 1140 + 253
= 1393
5. Determine GPM condensing water as follows:
GPM Condenser Water =
MBH x2
Cond Water Range
6. From curves on pages 10 and 11, the pressure drops
with 200GPM through the cooler and 288 through the
condenser of the Model YCWS120SC
Cooler Pressure Drop at 200 GPM = 2.9ft
Condenser Pressure Drop at 288 GPM = 5.5ft
Содержание STYLE A YCWS
Страница 44: ...44 YORK INTERNATIONAL Typical Control Panel Wiring...
Страница 45: ...FORM 201 24 EG1 45 YORK INTERNATIONAL...
Страница 49: ...FORM 201 24 EG1 49 YORK INTERNATIONAL...
Страница 50: ...50 YORK INTERNATIONAL...
Страница 51: ...FORM 201 24 EG1 51 YORK INTERNATIONAL...
Страница 52: ...Form 201 24 EG1 701 New Release RPC 3M 701 4 16 Codes DXS ET...