25
J1
on
on
off
off
J2
on
off
on
off
∆
Tcon(
ºC
)
0
-4
-2
0
9.7.7 Outdoor unit current control in heating mode.
Remark:
I1HEAT
I2 HEAT
I3 HEAT
9K Model
5.2 A
6.4 A
7.5 A
12K Model
5.2 A
6.4 A
7.5 A
9.7.8 Indoor heat exchanger high temperature protection.
If T2
>
60
ºC
, the compressor will stop and not resume until T2
<
48
ºC
.
9.7.9 Defrosting mode.
1) Condition of defrosting.
Condition 1:
If T4
>
0
ºC
,
When the units are running, if the following two items are satisfied the units start defrosting:
a) The units runs with T3
<
3
ºC
for 40 minutes and T3 keeps lower than -6
ºC
for more than 3
minutes.
b) The units runs with T3
<
3
ºC
for 80 minutes and T3 keeps lower than -4
ºC
for more than 3
minutes.
Condition 2:
If T4
<
0
ºC
,
The program judges according to the condition 1, if the two items are satisfied, then judges if T2 has
descended for more than 5
ºC
, if it has the machine starts defrosting, or continues to judge T2 and will
not defrost until T2 drops more than 5
ºC
.
Condition 3:
No matter what value T4 is, if the machine runs with T3
<
3
ºC
for more than 120 minutes and T3
keeps lower than -2
ºC
for more than 3 minutes, the machine will defrost, no matter if T2 drops for more than 5
ºC
or not.
2) Condition of ending defrosting.
If any one of following items is satisfied, defrosting will finish and the machine will turn to normal heating
mode.
a) T3 rises to be higher than 12
ºC
.
b) T3 rises to be higher than 8
ºC
and remains for 80 seconds.
c) The machine has run for 10 minutes in defrosting.
I3HEAT
I2HEAT
I1HEAT
comp. pause
freq. descends if curr. rises;
freq. remains if curr. descends
running normally
ou
tdoor
unit cur
rent
2) Temperature difference (
∆
Tcon) choice.
After power on, the machine will self-diagnose, and if there are no J1 and J2 jump wires,
∆
Tcon will be set
as 0
ºC
.
Содержание RVHC-09
Страница 1: ...High Wall Inverter RVHC 09 to 12 SERVICE MANUAL RVHC 09 RVHC 12 SM RVHC 09 12GB 03 07...
Страница 8: ...5 3 Dimension 3 1 Indoor Unit RVKC 09 RVKC 12...
Страница 9: ...6 3 2 Outdoor Unit RVJC 09 RVJC 12 762 275...
Страница 11: ...8 5 Refrigerant cycle diagram...
Страница 12: ...9 6 Wiring diagram 6 1 Indoor Unit RVKC 09 RVKC 12...
Страница 13: ...10 6 2 Outdoor Unit RVJC 09 RVJC 12...
Страница 34: ...31 LED1 LED4 LED5 LED6...
Страница 41: ...www johnsoncontrols com SM RVHC 09 12GB 03 07...