2) If the compressor stops caused by room temperature rising, indoor fan will be forced to run 127 seconds
with breeze. During this period, anti-cold-wind is disabled. After this, anti-cold –wind function is available.
3) If the machine runs in rating capacity test mode, indoor fan runs with rating speed, and anti-cold-wind is
disabled.
9.7.4 Indoor fan speed can be set as high, medium, low or auto grade,but anti-cold-wind function is preferential.
Auto fan action in heating mode.
9.7.6 After start the operation frequency of compressor submits to following rule:
1) When the machine runs, if
∆
Th stays in a zone for 3 minutes, action of frequency is as follow:
Zone A: Elevate current frequency one grade, and not stop until the maximum grade.
Zone B: Elevate or keep or descend current frequency.
Zone H: Compressor stops after running with F1 for 60 minutes or when
∆
Th
>
6
ºC
.
Remark:
∆
Tcon can be changed among 0, -2,- 4ºC, the default is 0ºC
A
5.0
4.5
1.0
0.5
H
B
ºC
∆
Th=(r
o
om tem
p
) – (
sett
ing
T
em
p
) –
∆
Tc
on
44
38
37
34
33
24
17
setting fan speed
low fan
breeze
super breeze
fan stop
Evaporator te
m
p
∆
T=(oom te
m
p)
– (setting
T
emp)
medium
2.5
2.0
1.5
1.0
ºC
low
high
9.7 Heating mode
9.7.1 Indoor fan action:
1) Anti-cold-wind function.
Содержание RVHC-09
Страница 1: ...High Wall Inverter RVHC 09 to 12 SERVICE MANUAL RVHC 09 RVHC 12 SM RVHC 09 12GB 03 07...
Страница 8: ...5 3 Dimension 3 1 Indoor Unit RVKC 09 RVKC 12...
Страница 9: ...6 3 2 Outdoor Unit RVJC 09 RVJC 12 762 275...
Страница 11: ...8 5 Refrigerant cycle diagram...
Страница 12: ...9 6 Wiring diagram 6 1 Indoor Unit RVKC 09 RVKC 12...
Страница 13: ...10 6 2 Outdoor Unit RVJC 09 RVJC 12...
Страница 34: ...31 LED1 LED4 LED5 LED6...
Страница 41: ...www johnsoncontrols com SM RVHC 09 12GB 03 07...