246699-YTG-D-1208
12
Johnson Controls Unitary Products
TABLE 3: DF CAPACITY RATINGS
Size
(Tons)
Model
Cooling Capacity
ARI Ratings
*
CFM
Sound
Rating
(dB)
†
Nominal
Electric
Heat
Capacity
‡
(kW)
Gas Heat Capacity
Gas
Line
Size
(in. OD)
MBH
EER
IPLV
Input
(MBH)
Output
(MBH)
Seasonal
Efficiency
(%)
Temp.
Rise
(°F)
078
(6-1/2)
Cooling
Only
75
10.4
11.0
2600
84
-
-
-
-
-
-
Electric
Heat
9, 18, 24,
36
-
-
-
-
-
Gas Heat
-
120
96
80
20-50
3/4
Gas Heat
-
180
144
80
35-65
3/4
090
(7-1/2)
Cooling
Only
87
10.5
11.6
2516
84
-
-
-
-
-
-
Electric
Heat
18, 36
-
-
-
-
-
Gas Heat
-
120
96
80
15-45
3/4
Gas Heat
-
180
144
80
30-60
3/4
102
(8-1/2)
Cooling
Only
99
10.4
10.39
3055
84
-
-
-
-
-
-
Electric
Heat
9, 18, 24,
36
-
-
-
-
-
Gas Heat
-
120
96
80
15-45
3/4
Gas Heat
-
180
144
80
30-60
3/4
120
(10)
Cooling
Only
115
10.4
10.0
4000
90
-
-
-
-
-
-
Electric
Heat
18, 24, 36,
54
-
-
-
-
-
Gas Heat
-
180
144
80
20-50
3/4
Gas Heat
-
240
192
80
35-65
3/4
*
Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
†
Rated in accordance with ARI 270 standard.
‡
See Table 17.
TABLE 4: UNIT VOLTAGE LIMITATIONS
POWER RATING
MIN.
MAX.
208/230-3-60
187
252
460-3-60
432
504
575-3-60
540
630