5132210-UIM-H-0916

Johnson Controls Unitary Products

9

COMPRESSORS

The compressor used in this product is specifically designed to operate
with R-410A Refrigerant and cannot be interchanged.

The compressor uses polyolester (POE oil), Mobile 3MA POE. This oil
is extremely hydroscopic, meaning it absorbs water readily. POE oil can
absorb 15 times as much water as other oils designed for HCFC and
CFC refrigerants. If refrigerant circuit is opened, take all necessary pre-
cautions to avoid exposure of the oil to the atmosphere.

POE (polyolester) compressor lubricants are known to cause long term
damage to some synthetic roofing materials.

Procedures which risk oil leakage include, but are not limited to, com-
pressor replacement, repairing refrigerant leaks, replacing refrigerant
components such as filter drier, pressure switch, metering device or
coil.

Units are shipped with compressor mountings which are factory-
adjusted and ready for operation.

GAS HEAT

These single stage gas-fired heaters have direct spark ignition.

GAS PIPING

Proper sizing of gas piping depends on the cubic feet per hour of gas
flow required, specific gravity of the gas and the length of run. National
Fuel Gas Code Z223.1 or CSA B149.1 should be followed in all cases
unless superseded by local codes or gas company requirements. Refer
to Tables 7 and 8.

The BTU content of the gas may differ with locality. The value should be
checked with the local gas utility.

GAS CONNECTION

The gas supply line should be routed through the 1-5/8” hole located on
the right side of the unit. See Figure 3 for the location. The unit is sup-
plied with a rubber grommet that fits in this hole and is used to seal
around the gas pipe. THIS GROMMET MUST BE INSTALLED IN
ORDER TO PREVENT LEAKAGE OF AIR AND WATER INTO THE
HEATING/CONTROLS COMPARTMENT.

Gas piping requirements:

1.

A drip leg and a ground joint union must be installed in the gas pip-
ing.

2.

When required by local codes, a manual shut-off valve may have to
be installed outside of the unit.

3.

Use wrought iron or steel pipe for all gas lines. Pipe thread sealant
should be applied sparingly to male threads only.

4.

All piping should be cleaned of dirt and scale by hammering on the
outside of the pipe and blowing out the loose dirt and scale. Before
initial start-up, be sure that all of the gas lines external to the unit
have been purged of air.

5.

The gas supply should be a separate line and installed in accor-
dance with all applicable safety codes. After the gas connections
have been completed, open the main shut-off valve admitting nor-
mal gas pressure to the gas valve. Check all joints for leaks with
soap solution or other material suitable for the purpose. NEVER
USE AN OPEN FLAME.

 CAUTION

This system uses R-410A Refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.

 CAUTION

Do not leave the system open to the atmosphere. Unit damage could
occur due to moisture being absorbed by the POE oil in the system.
This type of oil is highly susceptible to moisture absorption

 CAUTION

Exposure, even if immediately cleaned up, may cause embrittlement
(leading to cracking) to occur in one year or more. When performing
any service that may risk exposure of compressor oil to the roof, take
precautions to protect roofing.

 CAUTION

Do not loosen compressor mounting bolts.

NOTICE

There may be a local gas utility requirement specifying a minimum
diameter for gas piping. All units require a 1/2 inch pipe connection at
the gas valve.

!

!

!

!

Table 7: 

Natural Gas Pipe Sizing Chart

1

1. Maximum capacity of pipe in cubic feet of gas per hour (based upon a pres-

sure drop of 0.3 inch water column and 0.6 specific gravity gas).

Length

In Feet

Nominal Inches Iron Pipe Size

1/2”

3/4”

1”

1-1/4”

10

132

278

520

1,050

20

92

190

350

730

30

73

152

285

590

40

63

130

245

500

50

56

115

215

440

60

50

105

195

400

70

46

96

180

370

80

43

90

170

350

90

40

84

160

320

100

38

79

150

305

Table 8: 

Propane (LP) Gas Pipe Sizing Chart

1

1. Maximum capacity of pipe in thousands of BTU per hour (based upon a 

pressure drop of 0.5 inch water column).

Length

In Feet

Nominal Inches Iron Pipe Size

1/2”

3/4”

1”

1-1/4”

10

275

567

1071

2,205

20

189

393

732

1496

30

152

315

590

1212

40

129

267

504

1039

50

114

237

448

913

60

103

217

409

834

70

96

196

378

771

80

89

185

346

724

90

83

173

322

677

100

78

162

307

630

 CAUTION

If flexible stainless steel tubing is allowed by the authority having
jurisdiction, wrought iron or steel pipe must be installed at the gas
valve and extend a minimum of two (2) inches outside of the unit cas-
ing.

 WARNING

Natural gas may contain some propane. Propane being an excellent
solvent, will quickly dissolve white lead or most standard commercial
compounds. Therefore, a special pipe thread sealant must be
applied when wrought iron or steel pipe is used. Shellac base com-
pounds such as gaskoloc or stalastic, and compounds such as Rec-
torseal # 5, Clyde’s or John Crane may be used.

!

!

Содержание PHG4 Series

Страница 1: ...or installation Only gas piping electric power and duct connections are required at the point of installation The gas fired heaters have spark ignition The refrigerant system is fully charged with R 4...

Страница 2: ...mproper installation adjustment alteration service or mainte nance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer servi...

Страница 3: ...o a unit to meet local codes they are to be installed at the dealer s and or customer s expense Size of unit for proposed installation should be based on heat loss heat gain calculation made according...

Страница 4: ...are provided for this purpose WARNING Do not attach supply and return duct work to the bottom of the unit base pan as the drain pan could be compromised WARNING Excessive exposure of this furnace to...

Страница 5: ...ection Distance in Direction Distance in Top3 3 Units must be installed outdoors Over hanging structure or shrubs should not obstruct condenser air discharge outlet 36 Power Entry Right Side 36 Side O...

Страница 6: ...n the return air ductwork or install a Filter Frame Kit A filter rack and high velocity filters are standard on three phase units Filters must always be used and must be kept clean When filters become...

Страница 7: ...rate branch circuit fed directly from the main distribution panel and properly fused Refer to Figures 7 and 8 for typical field wiring and to the appropriate unit wiring diagram for control circuit an...

Страница 8: ...51 1 4 Width 35 3 4 35 3 4 45 3 4 45 3 4 45 3 4 45 3 4 Height 47 49 49 49 53 55 Operating WT lbs 394 404 449 453 498 505 532 534 551 559 564 577 581 588 Compressors Type Scroll Scroll Scroll Scroll Sc...

Страница 9: ...5 The gas supply should be a separate line and installed in accor dance with all applicable safety codes After the gas connections have been completed open the main shut off valve admitting nor mal ga...

Страница 10: ...leaks to check all connections A fire or explosion may result causing property damage personal injury or loss of life Table 9 High Altitude Gas Orifice Sizing ELEVATION ABOVE SEA LEVEL FEET GAS TYPE...

Страница 11: ...864 780 Medium High 4 1349 1297 1265 1224 1185 1146 1107 1063 975 High 5 1487 1462 1392 1331 1318 1281 1241 1201 1121 30050 Low 1 700 657 599 554 512 461 411 365 273 Low Medium 2 906 868 825 779 735...

Страница 12: ...1858 1807 1749 1710 1667 1629 1589 1546 1460 Medium 3 2054 1998 1934 1890 1843 1801 1757 1710 1616 Medium High 4 2195 2144 2098 2049 2003 1955 1883 1868 1838 High 5 2445 2388 2306 2293 2235 2178 2129...

Страница 13: ...w 1 1032 999 970 938 910 879 843 808 737 Low Medium 2 1272 1236 1204 1165 1129 1081 1037 968 829 Medium 3 1611 1574 1518 1494 1439 1405 1357 1266 1083 Medium High 4 1892 1777 1771 1701 1639 1617 1565...

Страница 14: ...ings are selected If the heat pump and gas heating sections are run at the same time HI LIMIT trips may occur A Y call without an O call from the indoor thermostat is primary heat pump heat A W call f...

Страница 15: ...frost cycle is initiated A temperature inhibit feature prohibits defrost if the coil temperature is above 40 F A forced defrost feature puts the system into a defrost period every 6 hours and 4 minute...

Страница 16: ...g 8 on the LED Post Purge The control board runs the induced draft motor for a 15 second post purge period and then de energizes the inducer If a call for heat occurs during post purge the control fin...

Страница 17: ...hich automatically lights the burners 5 Remove the access panel 6 Turn the gas valve switch to the OFF position 7 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the in...

Страница 18: ...within the range shown on the rating plate and the data in Table 6 After the temperature rise has been determined the CFM can be calcu lated as follows Direct Drive Blower All units have direct drive...

Страница 19: ...as in your particular locality Contact your gas company for this information since it varies widely from city to city Table 19 Gas Rate Cubic Feet Per Hour1 Seconds for9 One Rev Size of Test Dial 1 2...

Страница 20: ...VOLTAGE 19 2 VAC PREVENTING FURTHER RELAY OUTPUTS FOR 2 SECONDS LOW VOLTAGE 16 VAC STOPPED CURRENT RELAY OUTPUTS FOR 2 SECONDS LIQUID LINE SENSOR FAILURE OPEN OR SHORTED OUTDOOR AMBIENT SENSOR FAILUR...

Страница 21: ...EVENTING FURTHER RELAY OUTPUTS FOR 2 SECONDS LOW VOLTAGE 16 VAC STOPPED CURRENT RELAY OUTPUTS FOR 2 SECONDS LIQUID LINE SENSOR FAILURE OPEN OR SHORTED OUTDOOR AMBIENT SENSOR FAILURE OPEN OR SHORTED CO...

Страница 22: ...Manifold sets must be at least 700 psig high side and 180 psig low side with 550 psig retard All hoses must have a service pressure rating of 800 psig Leak detectors must be designed to detect HFC re...

Страница 23: ...le timer Measured voltage L1 to L2 L2 to L3 L1 to L3 Total amperes L1 L2 L3 Compressor amperes L1 L2 L3 Measured voltage R and C outdoor unit control board Electrical Connections Inspection Check all...

Страница 24: ...U H Measured BTU H Clock Gas Meter Nat Gas Supply Air Dry Bulb Temp Temp Rise Return Air Dry Bulb Temp Manifold Pressure at 100 Firing Rate w c Inlet Gas Pressure w c LP Gas Conversion Kit LP Conversi...

Отзывы: