 FIGURE 15:  

R-410A Quick Reference Guide

R-410A QUICK REFERENCE GUIDE

Refer to Installation Instructions for specific installation requirements

R-410A refrigerant operates at 50 - 70 percent higher pressures than R-22. Be sure that servicing 
equipment and replacement components are designed to operate with R-410A. 
R-410A refrigerant cylinders are rose colored. 
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400, or DOT BW400.
Recovery equipment must be rated for R-410A.
DO NOT  use R-410A service equipment on R-22 systems. All hoses, gages, recovery cylinders, charging 
cylinders and recovery equipment must be dedicated for use on R-410A systems only.
Manifold sets must be at least 700 psig high side, and 180 psig low side, with 550 psig retard.
All hoses must have a service pressure rating of 800 psig.
Leak detectors must be designed to detect HFC refrigerants.
Systems must be charged with liquid refrigerant. Use a commercial type metering device 
in the manifold hose.
R-410A can only be used with POE type oils.
POE type oils rapidly absorb moisture from the atmosphere.
Vacuum pumps will 

not

 

remove moisture from R-410A refrigerant oils.

Do not use liquid line driers with a rated working pressure rating less than 600 psig.
Do not install suction line driers in the liquid line.
A liquid line drier is required on every unit.
Do not use a R-22 TXV. If a TXV is to be used, it must be a R-410A TXV.
Never open system to atmosphere when under a vacuum.
If system must be opened for service, evacuate system then break the vacuum with dry nitrogen 
and replace all filter driers.

Содержание PCG6B42

Страница 1: ...Feet Per Hour 20 SECTION I GENERAL INFORMATION These are electric cooling gas heating units designed for outdoor instal lation Only gas piping electric power and duct connections are required for ins...

Страница 2: ...ation in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids i...

Страница 3: ...stallation only 2 Condenser coils must have an unlimited supply of air Where a choice of location is possible position the unit on either north or east side of building 3 Suitable for mounting on roof...

Страница 4: ...the spreader bars exceed the largest dimension across the unit Units may be moved or lifted with a forklift Slotted openings in the base rails are provided for this purpose WARNING Do not permit over...

Страница 5: ...rances1 2 Direction Distance in Direction Distance in Top3 36 Power Entry Right Side 36 Side Opposite Ducts 36 Left Side 24 Duct Panel 0 Bottom4 1 NOTES 1 A 1 clearance must be provided between any co...

Страница 6: ...is required Filters must always be used and must be kept clean When filters become dirt laden insufficient air is delivered by the blower the unit efficiency is decreased operating costs are increased...

Страница 7: ...uld be field provided for the unit If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram Electrical service must be sized properly...

Страница 8: ...stages 2 2 2 2 2 2 2 2 2 2 Temperature Rise Range High Fire F 40 70 40 70 40 70 40 70 Temperature Rise Range Low Fire F 25 55 25 55 25 55 25 55 Max Static Pressure w c 0 5 0 5 0 5 0 5 Max Outlet Air T...

Страница 9: ...value should be checked with the local gas utility Direct Drive Indoor Fan Data Fan Size Inch 11 x 10 11 x 10 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Centrifugal Motor HP each 1 2 3...

Страница 10: ...imum capacity of pipe in cubic feet of gas per hour based upon a pres sure drop of 0 3 inch water column and 0 6 specific gravity gas Length In Feet Nominal Inches Iron Pipe Size 1 2 3 4 1 1 1 4 10 13...

Страница 11: ...nches WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM 36065 High Cool A 1371 1354 1303 1257 1209 1148 1084 1008 934 878 B 1293 1246 1206 1152 1098 1028 938...

Страница 12: ...1645 1612 1572 1520 1477 1419 1384 1327 B 1506 1468 1441 1404 1358 1302 1259 1203 1159 1101 C 1322 1278 1238 1191 1138 1077 1030 975 920 859 D 1251 1205 1157 1107 1051 987 938 884 824 761 Low Heat A 1...

Страница 13: ...0 872 810 High Heat A 2114 2046 1974 1914 1874 1815 1745 1696 1645 1582 B 1982 1930 1887 1844 1806 1752 1697 1643 1604 1545 C 1785 1746 1720 1687 1647 1596 1551 1494 1459 1402 D 1614 1578 1554 1520 14...

Страница 14: ...0 1232 1181 1135 C 1410 1361 1307 1255 1204 1155 1100 1044 992 938 D 1323 1270 1213 1156 1104 1052 993 933 880 821 Low Heat A 1594 1553 1507 1462 1415 1369 1321 1274 1223 1178 B 1323 1270 1213 1156 11...

Страница 15: ...oved the control de energizes the inducer without post purge and returns to standby If the pressure switch does not close within 5 seconds of inducer ener gizing the control board flashes 3 on the LED...

Страница 16: ...trol faults reset after 60 minutes or power interruption Cooling operations are available during a heating lockout High Temperature Limit Switch Any time the high temperature limit switch is open less...

Страница 17: ...door blower runs at the HIGH COOL speed based on the COOL jumper setting If a call for HEAT occurs W1 or W1 W2 the circulating blower runs at the heat speed based on the HEAT jumper setting When the t...

Страница 18: ...t operate follow the instructions To Turn Off Gas To Appliance and call service technician or gas supplier To Turn Off Gas To Unit 1 Set the thermostat to the OFF position 2 Turn off all electric powe...

Страница 19: ...the high fire manifold pressure or the low fire manifold pressure 1 Refer to Figure 10 for location of pressure regulator adjustment cap and adjustment screws on main gas valve 2 Turn gas and electric...

Страница 20: ...d on the 1 cubic foot dial to make a revolution with just a 100 000 BTUH furnace running Using this information locate 38 seconds in the first column of Table 17 Read across to the column headed 1 Cub...

Страница 21: ...ten as necessary to keep the coil clean If water is used to clean the coil be sure that the power to the unit is shut off prior to cleaning TROUBLESHOOTING FIGURE 12 Measuring External Static Pressure...

Страница 22: ...ONAL FAULT CODES NORMAL OPERATION GREEN HEARTBEAT Normal Operation Standby mode AMBER HEARTBEAT Call for furnace heat active RAPID GREEN FLASHES Control in Factory Test mode 4 AMBER FLASHES No G from...

Страница 23: ...PLACED WITH TYPE 105 C 600 VOLT WIRE OR EQUIVALENT AND CLEARLY RENUMBERED FOR IDENTIFICATION VERIFY PROPER OPERATION AFTER SERVICING 3 FACTORY WIRED FOR 230 VOLT THREE PHASE SUPPLY POWER FOR 208 VOLT...

Страница 24: ...Manifold sets must be at least 700 psig high side and 180 psig low side with 550 psig retard All hoses must have a service pressure rating of 800 psig Leak detectors must be designed to detect HFC re...

Страница 25: ...L2 to L3 L1 to L3 Total amperes L1 L2 L3 Compressor amperes L1 L2 L3 Measured voltage R and C outdoor unit control board Electrical Connections Inspection Check all that apply Equipment Data Addition...

Страница 26: ...cle Test Operate the unit through continuous fan cycles from the thermostat noting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any pro...