5005562-YTG-A-0215
14
Johnson Controls Unitary Products
1. Airflow tested with dry coil conditions, without air flitters, at 230 volts
2. Applications above 0.8" w.c. external static pressure are not recommended.
3. Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
4. Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
48100
Low (1)
1620
1564
1517
1466
1418
1360
1308
1206
Low/Medium (2)
1694
1630
1580
1530
1482
1430
1380
1292
Medium (3)
1798
1722
1669
1620
1572
1527
1480
1413
Medium/High (4)
1835
1758
1703
1653
1604
1558
1511
1442
High (5)
2146
2085
2025
1960
1872
1862
1798
1735
48125
Low (1)
1620
1564
1517
1466
1418
1360
1308
1206
Low/Medium (2)
1798
1722
1669
1620
1572
1527
1480
1413
Medium (3)
1922
1863
1804
1754
1724
1658
1612
1559
Medium/High (4)
2001
1952
1890
1839
1820
1742
1696
1651
High (5)
2146
2085
2025
1960
1872
1862
1798
1735
60065
Low (1)
1073
1043
1009
988
963
941
917
892
Low/Medium (2)
1329
1292
1250
1223
1192
1165
1136
1105
Medium (3)
2054
1998
1934
1890
1843
1801
1757
1710
Medium/High (4)
2195
2144
2098
2049
2003
1955
1883
1868
High (5)
2445
2388
2306
2293
2235
2178
2129
2077
60100
Low (1)
1730
1682
1628
1592
1552
1517
1479
1439
Low/Medium (2)
1858
1807
1749
1710
1667
1629
1589
1546
Medium (3)
2054
1998
1934
1890
1843
1801
1757
1710
Medium/High (4)
2195
2144
2098
2049
2003
1955
1883
1868
High (5)
2445
2388
2306
2293
2235
2178
2129
2077
60125
Low (1)
2063
2008
1943
1899
1851
1809
1763
1717
Low/Medium (2)
2130
2084
2032
1983
1927
1951
1860
1815
Medium (3)
2195
2144
2098
2049
2003
1955
1883
1868
Medium/High (4)
2275
2252
2169
2154
2112
2065
1989
1976
High (5)
2445
2388
2306
2293
2235
2178
2129
2077
Airflow - Side Duct Application (Continued)
Model
Motor Speed
External Static Pressure (Inches WC)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM