background image

5005562-YTG-A-0215

Johnson Controls Unitary Products

13

AIRFLOW PERFORMANCE

Airflow - Side Duct Application

Model

Motor Speed

External Static Pressure (Inches WC)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

24050

Low (1)

732

667

624

567

517

470

415

369

Low/Medium (2)

818

771

723

674

628

579

530

482

Medium (3)

823

774

721

676

631

583

533

505

Medium/High (4)

994

948

906

865

823

778

739

700

High (5)

1148

1108

1071

1035

996

960

925

901

24075

Low (1)

887

847

802

750

705

664

613

563

Low/Medium (2)

978

941

898

850

803

759

713

667

Medium (3)

1171

1114

1074

1039

993

949

906

864

Medium/High (4)

1349

1297

1265

1224

1185

1146

1107

1063

High (5)

1487

1462

1392

1331

1318

1281

1241

1201

30050

Low (1)

700

657

599

554

512

461

411

365

Low/Medium (2)

906

868

825

779

735

692

650

608

Medium (3)

992

951

911

868

826

787

747

712

Medium/High (4)

1075

1032

1000

958

918

874

837

800

High (5)

1136

1089

1053

1018

978

941

903

869

30075

Low (1)

1076

1020

984

943

903

859

819

779

Low/Medium (2)

1102

1048

1010

974

934

890

850

810

Medium (3)

1191

1140

1112

1076

1038

1000

958

919

Medium/High (4)

1201

1225

1187

1151

1118

1080

1041

1002

High (5)

1370

1329

1283

1271

1209

1176

1143

1109

36050

Low (1)

1003

952

904

851

790

730

674

633

Low/Medium (2)

1180

1133

1085

1042

995

942

889

834

Medium (3)

1259

1209

1166

1126

1084

1032

980

928

Medium/High (4)

1314

1271

1229

1186

1144

1097

1049

998

High (5)

1506

1471

1403

1389

1345

1305

1262

1216

36075

Low (1)

1225

1174

1131

1090

1046

993

941

888

Low/Medium (2)

1259

1209

1166

1126

1084

1032

980

928

Medium (3)

1314

1271

1229

1186

1144

1097

1049

998

Medium/High (4)

1348

1306

1259

1222

1179

1133

1086

1036

High (5)

1506

1471

1403

1389

1345

1305

1262

1216

36100

Low (1)

1342

1302

1260

1217

1178

1134

1082

1034

Low/Medium (2)

1425

1368

1332

1293

1251

1208

1163

1113

Medium (3)

1554

1503

1465

1423

1386

1346

1302

1257

Medium/High (4)

1658

1599

1588

1530

1495

1454

1414

1373

High (5)

1966

1914

1862

1810

1757

1705

1653

1600

42075

Low (1)

1315

1266

1229

1194

1156

1117

1080

1036

Low/Medium (2)

1436

1382

1342

1304

1262

1220

1179

1131

Medium (3)

1458

1406

1365

1327

1286

1244

1203

1155

Medium/High (4)

1573

1523

1484

1445

1408

1367

1327

1279

High (5)

1966

1914

1862

1810

1757

1705

1653

1600

42100

Low (1)

1436

1382

1342

1304

1262

1220

1179

1131

Low/Medium (2)

1544

1492

1455

1416

1376

1336

1294

1248

Medium (3)

1573

1523

1484

1445

1408

1367

1327

1279

Medium/High (4)

1681

1640

1599

1557

1517

1478

1436

1393

High (5)

1935

1887

1834

1788

1743

1701

1651

1591

48065

Low (1)

1046

1009

980

946

915

878

844

779

Low/Medium (2)

1295

1250

1213

1172

1133

1087

1045

964

Medium (3)

1620

1564

1517

1466

1418

1360

1308

1206

Medium/High (4)

1798

1722

1669

1620

1572

1527

1480

1413

High (5)

2146

2085

2025

1960

1872

1862

1798

1735

Continued on next page.

Содержание PCG4A24

Страница 1: ...ate of the art computerized process system are used to insure product quality Refrigerant charge and component part numbers are verified via computers during assembly Vital run test statistics such as system pressure motor cur rents air velocity and temperature unit vibration and gas system safeties are monitored and recorded by the system to insure unit performance Equal size side supply and retu...

Страница 2: ...tactor and relays for simple application and troubleshooting Mate n lock plug connectors are used The electrical control box is not located in the compressor compartment The controls are mounted to allow the separate access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures All wiring internal to the unit is color number coded Protected...

Страница 3: ...Capacity BTUx1000 24 24 000 BTU etc 9 Revision Level A original release B second release Examples PHG4B421002X1A is a dual fuel 14 SEER 3 1 2 ton large cabinet single stage heat 100 000 BTU gas heat 230 volt single phase low NOx model first generation first release FAN MOTOR CONDENSER FAN COIL GUARD PANEL CONDENSER COIL Behind Panel CONTROL BOARD TRANSFORMER HIGH VOLTAGE CONTACTOR PRESSURE SWITCH ...

Страница 4: ...providing 0 through 50 of outdoor air field supplied Closes on power loss includes hood and screen assembly Rectangle to Round Horizontal Adapter S1 1AK0109 S1 1AK0108 Kit includes one supply and one return air rectangle to round duct adapter Adapters are preformed and designed to fit over current horizontal duct openings on the base unit Transition is from rectangle to 12 round for the 1AK0108 ki...

Страница 5: ...l shall be double inlet type with forward curved blades dynamically balanced to operate smoothly throughout the entire range of operation Airflow design shall be constant air volume Bearings shall be sealed and permanently lubricated for longer life and no maintenance Fan assembly shall be a slide out design for easy removal and cleaning Indoor blower motors shall be equipped with a standard high ...

Страница 6: ...ating WT lbs 359 366 379 386 415 422 426 442 446 495 503 508 522 530 535 Compressors Type Recip Recip Recip Scroll Scroll Scroll Condenser Coil Data Face area Sq Ft 15 1 17 0 15 1 17 0 23 8 26 0 Rows 1 1 2 2 2 2 Fins per inch 22 22 22 22 22 22 Tube diameter 3 8 3 8 3 8 3 8 3 8 3 8 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced Evaporator Coil Data Face area Sq Ft ...

Страница 7: ... 1 13 4 11 4 12 2 8 4 12 3 12 6 9 9 10 3 7 4 K W 2 50 2 49 2 45 2 53 2 59 2 39 2 39 2 36 2 45 2 52 2 27 2 29 2 28 2 37 2 45 COOLING PERFORMANCE DATA PACKAGED UNIT MODEL NO PCG4A30 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1200 1000 800 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 41 0 43 6 43 2 44 9 48 3 37 8 41 0 40 8 43 8 47 9 34 5...

Страница 8: ...17 2 17 9 16 7 17 6 13 8 18 2 18 0 17 0 17 4 13 0 K W 4 05 3 90 3 79 3 90 4 01 3 81 3 74 3 66 3 77 3 88 3 57 3 58 3 53 3 65 3 76 COOLING PERFORMANCE DATA PACKAGED UNIT MODEL NO PCG4A42 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1600 1400 1200 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 49 4 50 2 50 2 55 5 61 9 46 5 48 6 48 5 53 7 59 ...

Страница 9: ...27 3 26 2 24 6 27 4 20 3 27 0 25 5 25 4 25 9 19 4 K W 4 76 4 76 4 76 4 79 4 80 4 76 4 77 4 76 4 79 4 80 4 76 4 77 4 76 4 79 4 79 COOLING PERFORMANCE DATA PACKAGED UNIT MODEL NO PCG4B60 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1600 1400 1200 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 63 1 65 4 65 2 68 7 72 9 60 4 64 1 64 4 68 0 71 ...

Страница 10: ...e Direction Distance in Direction Distance in Top3 3 Units must be installed outdoors Over hanging structure or shrubs should not obstruct condenser air discharge outlet 48 Power Entry Right Side 42 Side Opposite Ducts 36 Left Side 36 Duct Panel 12 Bottom4 4 Units may be installed on combustible floors made from class A B or C roof covering materials 1 HIGH VOLTAGE CONNECTION 7 8 HIGH VOLTAGE CONN...

Страница 11: ...1 57 3 49 6 30 75 60 5 61 6 64 8 66 9 60 9 56 0 49 7 36 74 58 5 61 8 65 4 66 5 60 7 54 8 49 8 42 74 63 5 63 9 62 3 65 64 54 1 46 6 48 74 63 5 63 9 62 3 65 64 54 1 46 6 60 76 72 3 65 0 63 9 64 60 55 5 49 0 Model Voltage Compressor OD Fan Motor Supply Blower Motor MCA1 Amps 1 Minimum Circuit Ampacity Max Fuse2 Breaker3 Size Amps 2 Maximum Over Current Protection per standard UL 1995 3 Fuse or HACR c...

Страница 12: ...0075 391 386 27 15 107 97 88 94 36050 420 415 27 16 112 102 97 104 36075 427 422 27 16 114 104 98 106 36100 431 426 27 16 116 107 98 105 42075 447 442 27 16 120 109 103 111 42100 451 446 27 16 121 111 104 111 48065 500 495 26 20 132 130 115 118 48100 508 503 26 20 134 132 117 120 48125 513 508 26 20 136 133 118 121 60065 527 522 26 21 137 134 123 127 60100 535 530 26 21 139 136 125 129 60125 540 5...

Страница 13: ...89 834 Medium 3 1259 1209 1166 1126 1084 1032 980 928 Medium High 4 1314 1271 1229 1186 1144 1097 1049 998 High 5 1506 1471 1403 1389 1345 1305 1262 1216 36075 Low 1 1225 1174 1131 1090 1046 993 941 888 Low Medium 2 1259 1209 1166 1126 1084 1032 980 928 Medium 3 1314 1271 1229 1186 1144 1097 1049 998 Medium High 4 1348 1306 1259 1222 1179 1133 1086 1036 High 5 1506 1471 1403 1389 1345 1305 1262 12...

Страница 14: ...1480 1413 Medium 3 1922 1863 1804 1754 1724 1658 1612 1559 Medium High 4 2001 1952 1890 1839 1820 1742 1696 1651 High 5 2146 2085 2025 1960 1872 1862 1798 1735 60065 Low 1 1073 1043 1009 988 963 941 917 892 Low Medium 2 1329 1292 1250 1223 1192 1165 1136 1105 Medium 3 2054 1998 1934 1890 1843 1801 1757 1710 Medium High 4 2195 2144 2098 2049 2003 1955 1883 1868 High 5 2445 2388 2306 2293 2235 2178 ...

Страница 15: ... Medium 3 1262 1223 1181 1137 1091 1044 994 952 Medium High 4 1324 1282 1245 1202 1161 1112 1067 1018 High 5 1517 1475 1447 1400 1357 1318 1275 1232 36075 Low 1 1231 1186 1146 1103 1069 1030 977 912 Low Medium 2 1270 1225 1189 1140 1098 1046 1008 960 Medium 3 1317 1286 1245 1198 1151 1110 1064 1024 Medium High 4 1358 1317 1275 1238 1197 1148 1105 1057 High 5 1517 1475 1447 1400 1357 1318 1275 1232...

Страница 16: ...1469 1419 Medium 3 1912 1875 1805 1787 1750 1713 1672 1636 Medium High 4 2105 2014 2006 1931 1898 1845 1793 1739 High 5 2131 2058 1998 1949 1892 1840 1788 1728 60065 Low 1 1026 999 989 950 907 907 886 862 Low Medium 2 1263 1230 1192 1165 1167 1101 1099 1071 Medium 3 1987 1933 1861 1817 1820 1715 1725 1651 Medium High 4 2114 2050 2047 1974 1899 1889 1920 1866 High 5 2369 2308 2249 2183 2126 2088 20...

Страница 17: ...AR DUCT DIMENSIONS Inches Model A B C D 24 30 36 42 10 21 5 4 94 4 34 48 60 14 13 5 5 3 56 D 16 C A B A A0298 001 Model A B 24 30 36 42 9 6 22 48 60 13 6 14 15 6 A B A 4 3 A0299 001 6 ROOF CURB INSTALLATION REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION A0324 001 ...

Страница 18: ...odel shown UNIT TYPICAL ROOF CURB INSTALLATION Gas model shown A0325 001 SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT TO GAS SUPPLY LINE MANUAL GAS SHUTOFF VAVLE CONDENSATE DRAIN SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT TO GAS SUPPLY LINE MANUAL GAS SH...

Отзывы: