In the U.S. only, furnace shall not be connected to a chimney
flue serving a separate appliance designed to burn solid fuel.
Check the rating plate and power supply to be sure that
electrical characteristics match. All models use nominal 240
vac, 1 Ø, 60 Hz. power supply. A neutral conductor is also
required to provide 120 volts for the furnace controls.
A furnace installed in a residential garage must be located so
that all burners and burner ignition devices are located no less
than 18" above the garage floor, and located or protected to
prevent damage by vehicles.
The size of the unit should be based on an acceptable heat loss
calculation for the structure. ACCA, Manual J or other approved
methods may be used.
The furnace should be located using these guidelines:
1. Where a minimum amount of vent piping and elbows will
be required.
2. As centralized with the air distribution as possible.
3. Where adequate combustion air will be available.
4. In an area where ventilation facilities provide for safe limits of
ambient temperature under normal operating conditions.
5. Where it will not interfere with proper air circulation in the
confined space.
6. Where the vent will not be blocked or restricted.
7. Where sufficient space is provided to allow proper service
access. Minimum recommended service clearances are
as follows:
•
Twenty-four (24) inches between the front of the furnace
and an adjacent wall or another appliance, when access
is required for servicing and cleaning.
•
Eighteen (18) inches at the side where access is required
for passage to the front when servicing or for inspection
or replacement of flue/vent connections.
8. Where it will not interfere with the cleaning, servicing or
removal of other appliances.
9. Where the following minimum clearances (in inches) to
combustibles can be maintained:
Location Upflow
Top
1
Front
6
Vent Piping
6*
Rear
0
Sides
0
Floor
Combustible
Closet
Yes
Alcove
Yes
Attic
Yes
Line Contact
No
* May be 1" for Type B-1/BH vent
UNIT INSTALLATION
COMBUSTION AIR
All installations must comply with Section 5.3, Air for Combus-
tion and Ventilation of the National Fuel Gas Code, ANSI
Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or .2
Installation Code - latest editions.
The following must be considered to obtain proper air for
combustion and ventilation in confined spaces:
1. Air Source from Inside the Building -
Two permanent openings, one within 12 inches of the top
of the confined space and one within 12 inches of the
bottom, shall each have a free area of not less than one
square inch per 1,000 Btuh of total input rating of all
appliances located in the space. The openings shall com-
municate freely with interior areas having adequate infil-
tration from the outside.
NOTE: At least 100 square inches free area shall be
used for each opening.
2. Air Source from Outdoors -
Two permanent openings, one within 12 inches of the top
of the confined space and one within 12 inches of the
bottom, shall communicate directly, or by means of ducts,
with the outdoors or to such crawl or attic spaces that freely
communicate with the outdoors.
a. Vertical Ducts - Each opening must have a free area of
not less than one square inch per 4,000 Btuh of total
input of all appliances located in the space.
EXAMPLE:
Total Input of All Appliances
= Square Inches Free Area
4000
b. Horizontal Ducts - Each opening must have a free area
of not less than one square inch per 2,000 Btuh of total
input of all appliances located in the space.
NOTE: Ducts must have the same cross-sectional area
as the free area in the opening to which they are con-
nected. The minimum dimension of rectangular ducts
shall be three inches.
3. Louvers, Grilles and Screens
a. In calculating free area, consideration must be given to
the blocking effects of louvers, grilles and screens.
b. If the free area of a specific louver or grille is not known,
refer to Table 1 to estimate free area.
TABLE 1 - ESTIMATED FREE AREA
4. Special Combustion and Ventilation Considerations
Operation of a mechanical exhaust, such as an exhaust
fan, kitchen ventilation system, clothes dryer or fireplace
may create conditions requiring special attention to avoid
unsatisfactory operation of gas appliances.
NOMENCLATURE
P 4 UC B30 N 122 06 A
Style
Voltage Code
06 = 240 -1-60
Nominal Capacity
(MBH Output)
Heating Fuel
N = Natural, L = Low Nox
Type drive & CFM (x100)
B = Belt
Product Identifier
UC = Upflow
Product Generation
Product Category
P = Furnace
Wood or Metal
Louvers or Grilles
Wood 20-25%*
Metal 60-70%*
Screens**
1/4 in. mesh or larger 100%
* Do not use less than 1/4 in. mesh
** Free area or louvers and grilles varies widely; installer
should follow louver or grille manufacturer’s instructions.
650.64-N4
Unitary Products Group
3