YORK INTERNATIONAL
4
FORM 201.19-W1 (304)
ELECTRICAL NOTES
NOTES:
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all
other loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is pro vid ed, add the following to the
system #1 MCA values in the YCAS Tables: -17, add 15 amps; -28, add 12 amps; -40, add 7 amps; -46, add 6 amps; -58, add 5 amps.
2. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the circuit,
per N.E.C. 440 - 12A1.
3. Minimum recommended fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs. Minimum fuse rating = (1.5
x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit, per
N.E.C. 440-22. Maximum fuse rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
5. Minimum recommended circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit. Minimum circuit breaker rating
= (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per
U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other com pres sor RLAs + ( # fans x each fan motor
FLA).
7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), or (3) indicate
the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must be determined
based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based on the National Electric
Code and using
copper conductors
only. Field wiring must also comply with local codes.
8. A ground lug is provided for each compressor system to accommodate
fi
eld grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.
9. The
fi
eld supplied disconnect is a “Disconnecting Means” as de
fi
ned in N.E.C. 100.B, and is intended for isolating the unit from the available
power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
10.Two-Compressor machines with single-point power connection, and equipped with Star (Wye)-Delta Compressor motor start must also include
factory-provided individual system circuit breakers in each motor control center. All 3 & 4 Compressor machines equipped with Star-Delta
com pres sor motor start must also include factory-provided individual system circuit breakers in each motor control center.
11. Consult factory for Electrical Data on units equipped with “High Static Fan” option. High Static Fans are 3.8 kW each.
12.FLA for “Low Noise Fan” motors: 200V = 8.0A, 230V = 7.8A, 380V = 4.4A, 460V = 3.6A, 575V = 2.9A.
13.Group Rated breaker must be HACR type for cU.L. Machines.
NOTES & LEGEND
LEGEND
ACR-LINE ACROSS THE LINE START
C.B. CIRCUIT BREAKER
D.E. DUAL ELEMENT FUSE
DISC SW DISCONNECT SWITCH
FACT CB FACTORY-MOUNTED CIRCUIT BREAKER
FLA FULL LOAD AMPS
HZ HERTZ
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MIN NF MINIMUM NON-FUSED
RLA RUNNING LOAD AMPS
S.P. WIRE SINGLE-POINT WIRING
Y-
∆
WYE-DELTA START
X-LRA ACROSS-THE-LINE INRUSH LOCKED ROTOR AMPS
Y-LRA WYE-DELTA INRUSH LOCKED ROTOR AMPS
VOLTAGE CODE
-17 = 200-3-60
-28 = 230-3-60
-40 = 380-3-60
-46 = 460-3-60
-58 = 575-3-60
NO. OF
CONTROL MCA MAX DUAL NON-FUSED
COMPRESSORS
POWER (MAX LOAD ELEMENT DISCONNECT
SUPPLY CURRENT) FUSE SIZE SWITCH SIZE
2 115V-1Ø 20A 20A 20A
CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMER)
Содержание Millennium YCAS0130EC
Страница 5: ...YORK INTERNATIONAL 5 FORM 201 19 W1 304 This page intentionally left blank...
Страница 20: ...YORK INTERNATIONAL 20 FORM 201 19 W1 304 ELEMENTARY DIAGRAM FIG 6 ELEMENTARY DIAGRAM WYE DELTA START LD09480...
Страница 23: ...YORK INTERNATIONAL 23 FORM 201 19 W1 304 LD09239 FIG 8 CONTROL PANEL COMPONENT LOCATION CONTROL PANEL...
Страница 25: ...YORK INTERNATIONAL 25 FORM 201 19 W1 304 LEGEND LD09241...
Страница 26: ...YORK INTERNATIONAL 26 FORM 201 19 W1 304 LD03282 LD03283 2 ACE MOTOR PROTECTOR MODULE LD03284...
Страница 28: ...YORK INTERNATIONAL 28 FORM 201 19 W1 304 COMPRESSOR TERMINAL BOX LD09243 FIG 11 COMPRESSOR TERMINAL BOX...
Страница 31: ...YORK INTERNATIONAL 31 FORM 201 19 W1 304 NOTES...