YORK INTERNATIONAL
18
FORM 201.19-W1 (304)
WIRING DIAGRAM
WYE-DELTA START
FIG. 4 –
WIRING DIAGRAM – WYE-DELTA START
NOTES:
1. Field wiring to be in accordance with the current edi tion of
the National Electrical Code as well as all oth er ap pli ca ble
codes and speci
fi
cations.
2. Numbers along the right side of a diagram are line iden ti -
fi
ca tion numbers. The numbers at each line in di cate the line
number lo ca tion of relay contacts. An unlined contact loca-
tion signi
fi
es a nor mal ly closed contact. Numbers adjacent
to circuit lines are the cir cuit iden ti
fi
ca tion numbers.
3. Any customer supplied contacts must be suitable for
switching 24VDC. (Gold contacts rec om mend ed.) Con-
trol Wiring must not be run in the same conduit with any
line voltage wiring.
4. To cycle unit on and off automatically with contact
shown, install a cycling device in series with the
fl
ow
switch (FSLW). See Note 3 for contact rating and wiring
speci
fi
cations. Also refer to cau tions on page 21.
5. To stop unit (Emergency Stop) with contacts other than
those shown, install the stop contact between 5 and 1. If
a stop device is not installed, a jumper must be con nect ed
between ter mi nals 5 and 1. De vice must have a min i mum
contact rating of 100VA at 115 volts A.C.
6. Alarm contacts are for annunciating alarm/unit mal func -
tion. Con tacts are rated at 115V, 100VA, re sis tive load only,
and must be suppressed at load by user.
7. See Installation, Operation and Maintenance Man u al when
op tion al equipment is used.
8. Control panel to be securely connected to earth ground.
LEGEND
Transient Voltage Suppression
Terminal Block for Customer Connections
Terminal Block for Customer Low Voltage
(Class 2) Connections. See Note 2
Terminal Block for YORK Connections Only
Wiring and Components by YORK
Optional Equipment
Wiring and/or Components by Others
T S
7.
LD09231
7.
LD09232
Содержание Millennium YCAS0130EC
Страница 5: ...YORK INTERNATIONAL 5 FORM 201 19 W1 304 This page intentionally left blank...
Страница 20: ...YORK INTERNATIONAL 20 FORM 201 19 W1 304 ELEMENTARY DIAGRAM FIG 6 ELEMENTARY DIAGRAM WYE DELTA START LD09480...
Страница 23: ...YORK INTERNATIONAL 23 FORM 201 19 W1 304 LD09239 FIG 8 CONTROL PANEL COMPONENT LOCATION CONTROL PANEL...
Страница 25: ...YORK INTERNATIONAL 25 FORM 201 19 W1 304 LEGEND LD09241...
Страница 26: ...YORK INTERNATIONAL 26 FORM 201 19 W1 304 LD03282 LD03283 2 ACE MOTOR PROTECTOR MODULE LD03284...
Страница 28: ...YORK INTERNATIONAL 28 FORM 201 19 W1 304 COMPRESSOR TERMINAL BOX LD09243 FIG 11 COMPRESSOR TERMINAL BOX...
Страница 31: ...YORK INTERNATIONAL 31 FORM 201 19 W1 304 NOTES...