background image

JOHNSON CONTROLS

18

FORM 160.00-O1 (1020)

can reach 158°F.  If this message does occur, make 

certain you have an adequate level of coolant, check 

to be sure the cooling pump is operating when the unit 

is running, and check the strainer in the primary of the 

heat exchanger for clogs and silt.

Message:   

HIGH CONVERTER HEATSINK TEMP

Reference  “High Phase A (B,C) Heatsink Temp”  above.  

This shutdown requires a manual reset via the Reset 

push-button on the VSD logic board.

Message:   

105% MOTOR CURRENT OVERLOAD

This shutdown is generated by the VSD logic board 

and it indicates that a motor overload has occurred. 

The shutdown is generated when the VSD logic board 

has detected that at least one of the three output phase 

currents has exceeded 105% of the programmed  100% 

job full load amps (FLA) value. The 100% job FLA 

setpoint may be viewed by pressing the “Options” key. 

This shutdown requires a manual reset via the Reset 

push-button on the VSD logic board.

Message:   

BUS OVER-VOLTAGE FAULT

The VSD’s DC link voltage is continuously monitored 

and if the level exceeds 745 VDC, a Bus Over-Voltage 

shutdown is initiated. If this shutdown occurs, it will be 

necessary to look at the level of the 460 VAC applied to 

the drive.  The specified voltage range is 414 to 508.  If 

the incoming voltage is in excess of 508, steps should be 

taken to reduce the voltage within the specified limits.

Message:   

MAIN BOARD POWER SUPPLY

This shutdown is generated by the VSD logic board 

and it indicates that the low voltage power supplies for 

the logic boards have dropped below their allowable 

operating limits. The power supplies for the logic boards 

are derived from the secondary of the 120 to 24 VAC 

transformer (Fig. 2) which in turn is derived from the 480 

to 120 VAC control transformer (Fig. 1). This message 

usually means that power to the VSD was removed.

Message:   

LOW DC BUS VOLTAGE FLT

 

If the DC link drops below 500 VDC (or 414 VDC for 50 

HZ), the drive will initiate a system shutdown.  A common 

cause for this shutdown is a severe sag in the incoming 

power to the drive.  Monitor the incoming three phase 

AC line for severe sags and also monitor the DC link 

with a digital meter. 

Message: 

 

BUS VOLTAGE IMBALANCE FAULT

The DC link is filtered by many large, electrolytic capaci

-

tors which are rated for 450 VDC.  These capacitors are 

wired in series to achieve a 900 VDC capability for the 

DC link.  It is important that the voltage be shared equally 

from the junction of the center or series capacitor con-

nection, to the negative bus and to the positive bus.  This 

center point should be approximately ½ of the total DC 

link voltage. Most actual bus voltage imbalance conditions 

are caused by a shorted capacitor, or a leaky or shorted 

IGBT transistor in an output phase bank assembly.  This 

usually indicates the VSD requires service.  

Message:   

HIGH AMBIENT TEMPERATURE FLT

The ambient temperature monitored is actually the 

temperature detected by a component mounted on the 

VSD logic board. The high ambient trip threshold is set 

for 140°F. Some potential causes for this shutdown are: 

internal VSD fan failure, VSD water pump failure or an 

entering condenser water temperature which exceeds 

the allowable limit for the job. Additional causes for the 

shutdown include:

•   Plugged Strainer – The standard 1.5” Y-Strainer con-

tains a woven wire mesh element with 20 stainless-

steel wires per inch.  This has been found to work 

adequately in most applications.  Some users may 

have very dirty condenser water which can cause the 

strainer to plug.  Locations with special conditions 

may want to consider a dual strainer arrangement 

with quarter turn valves, to permit cleaning of one 

strainer with the unit still on-line. 

•   Plugged Heat-Exchanger – In cases where the 

strainer plugs frequently, the heat-exchanger 

eventually may plug or become restricted to the 

point of reduced flow.  At this point we suggest you 

back-flush the heat-exchanger by reversing the two 

rubber hoses which supply condenser water to/from 

the heat-exchanger.  If the rust or sludge cannot be 

back-flushed,  you  may  need  to  replace  the  heat-

exchanger.

•   Low Condenser Flow – The VSD system requires 

8 feet of pressure drop across the heat exchanger 

to maintain adequate GPM. If the pressure drop is 

less than 8 feet, it will be necessary to correct the 

flow problem, or add a booster pump as is applied 

on retrofit chillers.

Message:   

INVALID CURRENT SCALE FAULT

Since the part number of the logic board is the same 

on all horsepower sizes, jumpers tell the logic board 

the size of the VSD being employed in order to properly 

scale the output current.  If the jumper configuration is 

found by the logic to be invalid, the system will be shut 

down and the above message will be generated. The 

proper jumper configuration is shown on the wiring label 

for the VSD.

Содержание MILLENIUM 1100-46D

Страница 1: ...YT YK chillers furnished with an optional Variable Speed Drive VSD TABLE OF CONTENTS VSD Style Variations 2 VSD Unit and Harmonic Filter Component Overview 2 VSD Control System Overview 7 Control Panel VSD Related Keypad Functions 10 VSD Adaptive Capacity Control 12 VSD Display Messages 13 YORK MODEL YK CHILLER WITH OPTIONAL VARIABLE SPEED DRIVE VSD SIZE HP 60 HZ 50 HZ 351 292 503 419 790 658 1100...

Страница 2: ...ocument and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in this document to alert the reader to specific situations Indicates a possible hazardous situation which will result in death or serious injury if prope...

Страница 3: ...g any work on the chiller REVISION NOTES Revisions made to this document are indicated in the following table These revisions are to technical information and any other changes in spelling grammar or formatting are not included AFFECTED PAGES DESCRIPTION 3 Conditioned Based Maintenance program information added CONDITIONED BASED MAINTENANCE Traditional chiller maintenance is based upon assumed and...

Страница 4: ...ter section a three phase DC to AC inverter section and an output suppression network The AC to DC rectifier utilizes a semi converter formed by the connection of three SCR diode modules 1SCR 3SCR in a three phase bridge configuration See Fig 1 The modules are mounted on a liquid cooled heatsink Use of the semi converter configura tion permits implementation of a separate pre charge circuit to lim...

Страница 5: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 5 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 6: ...JOHNSON CONTROLS 6 FORM 160 00 O1 1020 ...

Страница 7: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 7 ...

Страница 8: ...tsink temperature is also monitored using thermistor temperature sensor RT4 The Bus Isolator board 031 01624 utilizes three resistors on the board to provide a safe impedance between the DC link filter capac itors located on the output phase bank assemblies and the VSD logic board It provides the means to sense the positive midpoint and negative connection points of the VSD s DC link A Current Tra...

Страница 9: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 9 FIG 3A VSD INPUT CURRENT WITHOUT FILTER FIG 3B VSD INPUT CURRENT WITH FILTER LD02727 LD02726 ...

Страница 10: ... capacitors located on the phase bank assembly and the Filter logic board It provides the means to sense the positive midpoint and negative connection points of the filter s DC link VSD CONTROL SYSTEM OVERVIEW The VSD control system is composed of various com ponents located within both the Microcomputer Control Center and the VSD thus integrating the Control Center with the VSD Drive The VSD syst...

Страница 11: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 11 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 12: ...JOHNSON CONTROLS 12 FORM 160 00 O1 1020 FIG 4 IEEE 519 FILTER OPTION ...

Страница 13: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 13 LD02725 ...

Страница 14: ...of the VSD s cooling fans and pumps control of the pre charge contactor control of the semi converter gating and generation of the PWM firing pulses which are sent to the VSD gate driver and ultimately gate the IGBT s on and off The VSD Logic board also gathers data from the Cur rent Transformers which monitor the three phases of motor current the heatsink temperatures the internal ambient tempera...

Страница 15: ...rtz When the Filter is present these additional lines are available by scrolling INPUT KVA ___ TOTAL PWR FACTOR ____ INPUT V AB ___V BC ___V CA ___V INPUT CURR A ___A B ___A C ___A INPUT V THD A ___ B ___ C ___ INPUT CURR TDD A ___ B ___ C ___ Display Data Key This key functions as normal but offers two additional lines of display with VSD opera tion After scrolling through the normal displays the...

Страница 16: ...n the vanes hit 100 If there is an increase in load while at this point the ACC will increase speed until the vanes are at 95 The ACC will then be allowed to continue to optimize the speed and vanes Surge is Detected If in the process of dropping speed and opening vanes the compressor should surge theACC will boost the speed back up enough to get the chiller out of surge and will store in memory t...

Страница 17: ...r cur rent exceeds a given limit The motor current is sensed by the Current Transformers on the VSD output pole assemblies and the signals are sent to the VSD logic board for processing Maximum instantaneous permis sible currents are 351 292 HP 771 Amps 503 419 HP 1200 Amps 790 658 HP 1890 Amps 1100 900 HP 3093 Amps If an overcurrent trip occurs but the chiller restarts and runs without a problem ...

Страница 18: ...capacitors are wired in series to achieve a 900 VDC capability for the DC link It is important that the voltage be shared equally from the junction of the center or series capacitor con nection to the negative bus and to the positive bus This center point should be approximately of the total DC link voltage Most actual bus voltage imbalance conditions are caused by a shorted capacitor or a leaky o...

Страница 19: ...e two microprocessors on the VSD logic board Message RUN RELAY FAULT Redundant run signals are generated by the Micropanel one via wire 24 and the second via the serial communica tions link Upon receipt of either of the two run commands by the VSD logic board a 5 second timer shall commence timing If the missing run command is not asserted within the 5 second window the unit will shut down and the...

Страница 20: ... particular shutdown and its accompany ing message is generated if the filter s DC link voltage drops to a level less than 60 VDC below the filter DC link voltage setpoint The filter DC link voltage setpoint is determined by the filter logic board via the sensing of the three phase input line to line voltage This setpoint is set to the peak of the sensed input line to line voltage plus 32 volts no...

Страница 21: ...TDD level of 8 or less for the VSD system Astandard VSD less the optional filter typically has an input current TDD level on the order of 28 30 Message WARNING FILTER DATA LOSS This message is displayed if the communications link between the VSD logic board and the filter logic board or the communications link between the filter logic board and the ACC board is interrupted This message can also oc...

Страница 22: ...sage was intended as a check of the 519 logic board s internal triangle waveform generator However the accuracy of the measuring circuit on the board can have as much error as the generator it is trying to mea sure resulting in nuisance shutdowns If this message occurs repeatedly it can be corrected by installing a special EPROM Message FLTR SERIAL RECEIVE FAULT is a message which would occur on s...

Страница 23: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 23 NOTES ...

Страница 24: ...Pennsylvania USA 17349 1 800 524 1330 Subject to change without notice Printed in USA Copyright by Johnson Controls 2020 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 00 O1 1020 Issue Date October 23 2020 Supersedes 160 00 O1 702 ...

Отзывы: