514067-UAD-A-0509
6
Johnson Controls Unitary Products
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor
Default
Min
Max
Point Description
R
(5) BV
44
E_HPS1
–
–
–
Elite High Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R
(5) BV
48
E_HPS2
–
–
–
Elite High Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R
(5) BV
53
E_HPS3
–
–
–
Elite High Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R
(5) BV
57
E_HPS4
–
–
–
Elite High Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R
(5) BV
40
E_IFAN_STAT
–
–
–
Elite Indoor Fan Output Status (0=output is
OFF, 1=output is ON)
R
(5) BV
61
E_LIMIT_ 1
–
–
–
Elite Limit Switch #1 Input Status (1=closed,
0=open/fault)
R
(5) BV
63
E_LIMIT_ 2
–
–
–
Elite Limit Switch #2 Input Status (1=closed,
0=open/fault)
R
(5) BV
65
E_LIMIT_ 3
–
–
–
Elite Limit Switch #3 Input Status (1=closed,
0=open/fault)
R
(5) BV
43
E_LPS1
–
–
–
Elite Low Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R
(5) BV
47
E_LPS2
–
–
–
Elite Low Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R
(5) BV
52
E_LPS3
–
–
–
Elite Low Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R
(5) BV
56
E_LPS4
–
–
–
Elite Low Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R
(2) AV
32
EXH_DAMP_OUT
–
–
–
Exhaust Damper Output Status (0-100%)
R
(5) BV
30
EX_FAN_STAT
–
–
–
Exhaust Fan Output Status (0=output is
OFF, 1=output is ON)
R
(5) BV
10
EX_VFD_INST
–
–
–
Exhaust VFD Installed
R
(5) BV
32
FRECOOL_STAT
–
–
–
Free Cooling Mode Status (0=comps not
overridden by Econo, 1=comps overridden)
R
(5) BV
68
HEAT_1_STAT
–
–
–
H1 Heating Output #1 Status (0=output is
OFF, 1=output is ON)
R
(5) BV
69
HEAT_2_STAT
–
–
–
H2 Heating Output #2 Status (0=output is
OFF, 1=output is ON)
R
(5) BV
70
HEAT_3_STAT
–
–
–
H3 Heating Output #3 Status (0=output is
OFF, 1=output is ON)
R
(2) AV
76
H1_ACCUM_HRS
–
–
–
Heating #1 Accumulated Run Time
(in hours)
R
(2) AV
77
H2_ACCUM_HRS
–
–
–
Heating #2 Accumulated Run Time
(in hours)
R
(2) AV
78
H3_ACCUM_HRS
–
–
–
Heating #3 Accumulated Run Time
(in hours)
R
(5) BV
25
HEATING_ENA
–
–
–
Heating Mode Enabled
R/W
(2) AV
27
HGR_HUM_STPT
50
0
100
Hot Gas Reheat Humidity Setpoint (percent
Humidity)
R
(5) BV
18
HGR_STAT
–
–
–
Hot Gas Reheat Output Status (0=output is
OFF, 1=output is ON)
R
(2) AV
47
HGR_VLV_OUT
–
–
–
Hot Gas Reheat Valve Output Status
(0-100%)