514067-UAD-A-0509
Johnson Controls Unitary Products
13
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor
Default
Min
Max
Point Description
R
(5) BV
19
LOW_AMB_OVRD
–
–
–
Low Ambient Temperature (0=comps not
overridden by LAT, 1=comps overridden)
R
(5) BV
20
POP_ENABLED
–
–
–
Pre-Occupancy Purge Enabled
R
(5) BV
21
FAN_ON_W_SEN
–
–
–
CV - Indoor Fan Operates with Space
Sensor Present Option Enabled
R
(5) BV
22
SAT_COOLING
–
–
–
Supply Air Temperature Limit for Cooling
Enabled
R
(5) BV
23
COOLING_ENA
–
–
–
Cooling Mode Enabled
R
(5) BV
24
SAT_HEATING
–
–
–
Supply Air Temperature Limit for Heating
Enabled
R
(5) BV
25
HEATING_ENA
–
–
–
Heating Mode Enabled
R
(5) BV
26
SEN_FAULT_EN
–
–
–
Space Sensor Fault Override (Construction
Mode) Enabled
R
(5) BV
28
INTELLI-STRT
–
–
–
Intelli-Start Enabled
R
(5) BV
29
BP_SENS_INST
–
–
–
Building Static Pressure Sensor Installed
R
(5) BV
30
EX_FAN_STAT
–
–
–
Exhaust Fan Output Status (0=output is OFF,
1=output is ON)
R
(5) BV
31
ECONO_STATUS
–
–
–
Economizer Output Status (0=not Free
Cooling, 1= Free Cooling)
R
(5) BV
32
FRECOOL_STAT
–
–
–
Free Cooling Mode Status (0=comps not
overridden by Econo, 1=comps overridden)
R
(5) BV
33
COM_VENT_STA
–
–
–
Comfort Ventilation Mode Status (1=control
is in Comfort Vent mode, 0= it is not)
R
(5) BV
34
CVM_COOLING
–
–
–
Comfort Ventilation Mode for Cooling
Enabled
R
(5) BV
35
CVM_HEATING
–
–
–
Comfort Ventilation Mode for Heating
Enabled
R
(5) BV
36
ECO_L_TO_SAT
–
–
–
Economizer Loading to Control Supply Air
Temperature Enabled
R
(5) BV
37
OAH_SENSOR
–
–
–
Outside Air Humidity Sensor Enabled
R
(5) BV
38
RAH_SENSOR
–
–
–
Return/Inside Air Humidity Sensor Enabled
R
(5) BV
39
DEMAND_VENT
–
–
–
Demand Ventilation (using Inside Sensor)
Enabled
R
(5) BV
40
E_IFAN_STAT
–
–
–
Elite Indoor Fan Output Status (0=output is
OFF, 1=output is ON)
R
(5) BV
41
E_FAN_ OVER
–
–
–
Elite Fan Overload Switch Input Status
(1=closed, 0=open/fault)
R
(5) BV
42
E_COMP1_STAT
–
–
–
Elite Compressor #1 Output Status (0=output
is OFF, 1=output is ON)
R
(5) BV
43
E_LPS1
–
–
–
Elite Low Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R
(5) BV
44
E_HPS1
–
–
–
Elite High Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R
(5) BV
45
E_C1_OVRLOAD
–
–
–
Elite Compressor #1 Overload Switch Input
Status (1=closed, 0=open/fault)
R
(5) BV
46
E_COMP2_STAT
–
–
–
Elite Compressor #2 Output Status (0=output
is OFF, 1=output is ON)