514067-UAD-A-0509
10
Johnson Controls Unitary Products
TABLE 3: POINTS LIST IN OBJECT ORDER
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor
Default
Min
Max
Point Description
R/W
(2) AV
1
OCC_COOL_SP
72
45
99
Occupied Cooling Setpoint
R/W
(2) AV
2
UNOC_COOL_SP
85
45
99
Un-Occupied Cooling Setpoint
R/W
(2) AV
3
SAT_COOL_SP
50
40
65
Supply Air Temperature Limit for Cooling
Setpoint (degrees F)
R
(2) AV
4
SUP_AIR_TEMP
–
–
–
Supply Air Temperature
R
(2) AV
5
RET_AIR_TEMP
–
–
–
Return Air Temperature
R
(2) AV
6
SPACE_TEMP
–
–
–
Space (Indoor) Air Temperature
R
(2) AV
7
AMB_TEMP
–
–
–
Outside Air Temperature
R
(2) AV
8
IAQ_VALUE
–
–
–
Demand Ventilation (IAQ) Value (PPM)
R
(2) AV
9
OAQ_VALUE
1000
0
5000
Outside Demand Ventilation (OAQ) Value
(PPM)
R
(2) AV
10
AMB_AIR_HUM
–
–
–
Outside Air Humidity
R
(2) AV
11
AMB_AIR_ENTH
–
–
–
Outside Air Enthalpy
R
(2) AV
12
RET_AIR_HUM
–
–
–
Return Air Humidity
R
(2) AV
13
RET_AIR_ENTH
–
–
–
Return Air Enthalpy
R
(2) AV
14
ACC_OVER_TME
–
–
–
Accumulated Unoccupied Override Time (in
hours)
R
(2) AV
15
ACTIVE_ALARM
–
–
–
Active Alarm
R
(2) AV
16
NUMBER_COMPS
–
–
–
Number of Compressors Available
R
(2) AV
17
OP_COOL_STPT
–
–
–
Operating Cooling Setpoint
R/W
(2) AV
18
DEMVENT_STPT
1000
0
5000
Demand Ventilation Setpoint
R/W
(2) AV
19
ECON_MIN_POS
20
0
100
Economizer Minimum Position
R/W
(2) AV
20
ECO_1ST_STPT
55
40
65
Economizer First Stage Setpoint
R/W
(2) AV
21
ECO_2ND_STPT
50
40
65
Economizer Second Stage Setpoint
R/W
(2) AV
22
ECON_OAEN_SP
27
10
50
Economizer Outside Air Enthalpy Setpoint
R/W
(2) AV
23
ECON_OAT_ENA
55
40
80
Economizer Outside Air Temperature Enable
Setpoint
R/W
(2) AV
24
COM_V_HI_SP
80
60
85
Comfort Ventilation Upper Setpoint (degrees F)
R/W
(2) AV
25
COM_V_LOW_SP
70
60
85
Comfort Ventilation LowerSetpoint (degrees F)
R/W
(2) AV
26
TEM_HUM_STPT
50
20
80
Temperature/Humidity Setpoint (percent
Humidity)
R/W
(2) AV
27
HGR_HUM_STPT
50
0
100
Hot Gas Reheat Humidity Setpoint (percent
Humidity)
R/W
(2) AV
28
MAX_TH_OFSET
3
0
5
Max Temperature/Humidity Setpoint Offset
R/W
(2) AV
29
TH_OFFSET
5
1
10
Temperature/Humidity % Humidity that = 1°F
of Offset
R/W
(2) AV
30
MAX_DMV_ECON
50
0
100
Maximum Demand Ventillation Economizer
Position
R
(2) AV
31
ECO_DAMP_OUT
–
–
–
Economizer Damper Output Status (0-100%)
R
(2) AV
32
EXH_DAMP_OUT
–
–
–
Exhaust Damper Output Status (0-100%)
R
(2) AV
33
BLDG_STATIC
–
–
–
Building Static Pressure
R
(2) AV
34
SFAN_VFD_OUT
–
–
–
Supply Fan VFD Output Status (0-100%)
R
(2) AV
35
DUCT_STATIC
–
–
–
Duct Static Pressure
R
(2) AV
36
ALARM_1
–
–
–
System Alarm #1
R
(2) AV
37
ALARM_2
–
–
–
System Alarm #2