Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGF48S41S4(E)
INDOOR COIL MODEL NO.
FC/MC62
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1400
1600
1800
ID
DB
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID
WB
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
43.3
48.6
46.2
50.6
54.3
44.9
49.3
47.7
52.2
55.4
46.5
49.9
49.3
53.9
56.5
S.C.
43.2
39.3
33.6
33.2
26.2
44.8
42.1
35.6
35.0
27.1
46.4
45.0
37.6
36.7
27.9
KW
2.60
2.62
2.62
2.63
2.67
2.60
2.62
2.62
2.64
2.68
2.61
2.63
2.62
2.65
2.69
75
T.C.
41.8
46.2
44.3
48.6
52.4
43.2
47.0
45.7
50.2
53.6
44.7
47.7
47.2
51.7
54.7
S.C.
41.7
38.5
32.7
32.4
25.4
43.1
41.2
34.7
34.2
26.4
44.6
43.8
36.6
36.1
27.4
KW
3.00
3.02
3.02
3.03
3.06
3.01
3.02
3.02
3.04
3.07
3.01
3.03
3.02
3.04
3.08
85
T.C.
40.3
43.8
42.4
46.7
50.5
41.6
44.7
43.7
48.1
51.7
42.9
45.5
45.1
49.5
52.9
S.C.
40.2
37.8
31.9
31.6
24.7
41.5
40.2
33.7
33.5
25.8
42.8
42.6
35.6
35.4
26.9
KW
3.40
3.42
3.42
3.43
3.45
3.41
3.42
3.43
3.44
3.46
3.42
3.43
3.43
3.44
3.46
95
T.C.
38.8
41.4
40.5
44.7
48.6
40.0
42.4
41.7
46.0
49.9
41.1
43.3
42.9
47.3
51.1
S.C.
38.7
37.0
31.0
30.8
24.0
39.8
39.2
32.8
32.8
25.2
41.0
41.5
34.6
34.8
26.3
KW
3.80
3.82
3.83
3.84
3.84
3.81
3.82
3.83
3.83
3.84
3.82
3.82
3.83
3.83
3.85
105
T.C.
36.6
38.8
38.2
42.2
45.9
37.8
39.9
39.3
43.4
47.0
38.9
40.9
40.5
44.6
48.1
S.C.
36.6
35.8
29.8
29.8
22.9
37.7
37.7
31.7
31.9
24.1
38.8
39.6
33.6
33.9
25.3
KW
4.48
4.54
4.53
4.48
4.44
4.47
4.51
4.52
4.46
4.44
4.45
4.48
4.50
4.45
4.45
115
T.C.
34.6
36.3
36.0
39.7
43.2
35.7
37.4
37.0
40.8
44.2
36.8
38.5
38.0
41.9
45.2
S.C.
34.5
34.5
28.6
28.9
21.8
35.6
36.2
30.6
30.9
23.1
36.7
37.8
32.6
33.0
24.3
KW
5.14
5.23
5.22
5.10
5.03
5.10
5.17
5.19
5.08
5.03
5.06
5.11
5.16
5.06
5.03
125
T.C.
32.5
33.8
33.7
37.3
40.6
33.6
34.9
34.7
38.3
41.4
34.7
36.1
35.6
39.3
42.3
S.C.
32.4
33.3
27.4
27.9
20.8
33.5
34.7
29.5
30.0
22.1
34.6
36.0
31.6
32.2
23.3
KW
5.80
5.92
5.91
5.72
5.61
5.74
5.83
5.86
5.69
5.61
5.67
5.74
5.81
5.66
5.61
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC48
0.97
1.00
0.99
–
FC/MC/PC60
0.99
0.97
1.01
–
FC/MC62
1.00
1.00
1.00
–
FC64
1.01
1.03
0.99
–
HD60
1.01
0.99
1.01
–
UC48
0.97
1.00
0.99
–
UC60
0.98
0.97
1.00
AHE48D
–
1.00
0.99
0.96
AHE60D
–
1.01
1.01
0.93
AHR48D
–
0.99
0.98
1.01
AHR60D
–
1.01
1.01
0.99
AHV48D
–
0.99
0.97
0.97
AHV60D
–
1.00
0.99
0.96
AV*48
–
1.00
0.99
0.96
AV*60
–
1.00
0.99
0.96
MV16C
FC/MC48C
0.98
1.01
0.96
MV16C
FC60C
1.00
0.98
0.96
MV20D
FC/MC48D
0.99
1.02
0.95
MV20D
FC/MC60D
1.00
0.98
0.98
MV20D
FC/MC62D
1.02
1.03
0.96
MV20D
FC64D
1.03
1.04
0.95
MX16C
FC/MC48C
0.99
1.04
0.97
MX16C
FC60C
0.99
0.95
0.91
MX20D
FC/MC48D
0.99
1.02
0.93
MX20D
FC/MC60D
0.99
0.95
0.91
MX20D
FC/MC62D
1.02
1.04
0.93
MX20D
FC64D
1.03
1.05
0.92
Furnaces
Coils
T.C.
S.C.
KW
T*(8,L)C*C16
FC/MC/PC48C
0.97
1.00
0.99
T*(8,L)C*C16
FC/MC/PC48D
0.97
1.00
0.99
T*(8,L)C*C16
FC/MC/PC60D
0.99
0.98
0.99
T*(8,L)C*C16
FC/MC62D
1.01
1.02
0.99
T*(8,L)C*C16
FC/PC60C
0.99
0.98
0.99
T*(8,L)C*C16
FC64D
1.02
1.04
0.98
T*(8,L)C*C16
HD60
1.02
0.99
0.98
T*(8,L)C*C16
UC48C
0.97
1.01
0.97
T*(8,L)C*C16
UC60C
0.99
0.98
0.99
T*(8,L)C*C20
FC/MC/PC48C
0.98
1.01
0.98
T*(8,L)C*C20
FC/MC/PC48D
0.98
1.01
0.98
T*(8,L)C*C20
FC/MC/PC60D
0.99
0.98
0.99
T*(8,L)C*C20
FC/MC62D
1.01
1.02
0.97
T*(8,L)C*C20
FC/PC60C
0.99
0.98
0.99
T*(8,L)C*C20
FC64D
1.00
0.98
0.92
T*(8,L)C*C20
HD60
1.02
1.00
0.96
T*(8,L)C*C20
UC48C
0.97
1.01
0.99
T*(8,L)C*C20
UC60C
0.99
0.98
0.97
T*(8,L)V*C16
FC/MC/PC48C
0.97
1.00
0.99
T*(8,L)V*C16
FC/MC/PC48D
0.97
1.00
0.99
T*(8,L)V*C16
FC/MC/PC60D
0.99
0.98
0.99
T*(8,L)V*C16
FC/MC62D
1.01
1.02
0.99
T*(8,L)V*C16
FC/PC60C
0.99
0.98
0.99
T*(8,L)V*C16
FC64D
1.02
1.04
0.98
T*(8,L)V*C16
HD60
1.02
0.99
0.98
T*(8,L)V*C16
UC48C
0.97
1.01
0.97
Continued on next page.