Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
HDBE-F024S
INDOOR COIL MODEL NO.
FC/MC/PC35
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
600
800
1000
ID DB
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
20.1 22.8 25.9 27.9 23.1 24.6 26.9 29.0 26.1 26.4 27.9 30.2 25.6 27.9 30.2
S.C.
19.9 17.8 16.4 12.9 22.8 21.5 18.9 14.6 25.7 25.2 21.5 16.4 21.0 21.5 16.4
K.W
1.2 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
75
T.C.
19.3 21.6 24.8 26.8 22.0 23.3 25.8 27.8 24.8 25.1 26.8 28.8 24.3 26.8 28.8
S.C.
19.1 17.4 15.8 12.5 21.8 20.8 18.1 14.1 24.5 24.2 20.4 15.6 20.6 20.4 15.6
K.W
1.3 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
85
T.C.
18.5 20.3 23.7 25.7 21.0 22.1 24.7 26.5 23.5 23.8 25.8 27.4 23.0 25.8 27.4
S.C.
18.3 16.9 15.3 12.1 20.7 20.0 17.3 13.5 23.2 23.2 19.4 14.9 20.1 19.4 14.9
K.W
1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.6 1.5 1.5 1.5 1.6 1.5 1.5 1.6
95
T.C.
17.6 19.1 22.6 24.6 19.9 20.8 23.7 25.3 22.2 22.6 24.7 25.9 21.7 24.7 25.9
S.C.
17.4 16.4 14.7 11.6 19.7 19.3 16.5 12.9 22.0 22.2 18.3 14.1 19.7 18.3 14.1
K.W
1.6 1.6 1.6 1.7 1.6 1.6 1.7 1.7 1.6 1.6 1.7 1.7 1.6 1.7 1.7
105
T.C.
16.8 18.2 20.8 22.8 18.8 19.6 21.6 23.4 20.7 21.1 22.5 24.0 20.1 22.5 24.0
S.C.
16.7 16.2 14.0 11.0 18.6 18.5 16.0 12.3 20.6 20.9 18.0 13.5 18.7 18.0 13.5
K.W
1.7 1.7 1.8 1.8 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.8 1.8
115
T.C.
16.0 17.4 19.0 21.1 17.7 18.4 19.7 21.6 19.3 19.4 20.4 22.1 18.6 20.4 22.1
S.C.
15.9 16.0 13.4 10.4 17.6 17.6 15.5 11.7 19.3 19.4 17.7 12.9 17.7 17.7 12.9
K.W
1.8 1.8 1.9 1.9 1.8 1.8 1.9 1.9 1.9 1.9 1.9 2.0 1.9 1.9 2.0
125
T.C.
15.2 16.5 17.3 19.4 16.6 17.2 17.7 19.8 17.9 18.3 19.2 20.1 17.1 18.2 20.1
S.C.
15.2 14.7 12.7 9.9 16.6 16.6 15.0 11.1 17.0 18.0 17.3 12.3 16.8 17.3 12.3
K.W
1.9 1.9 2.0 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.1 2.0 2.0 2.1
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
AHP30
–
1.00
1.00
1.00
AV36
–
1.00
1.00
1.00
MA12B
FC/MC35B
1.01
1.00
0.97
MV12B
FC/MC35B
1.01
1.00
0.97
–
FC/MC/PC/UC32B
1.00
1.00
1.00
–
HC36
1.00
1.00
1.00
–
HD36
1.00
1.00
1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
(F,L)L8V*A12
FC/MC/PC32A
1.01
1.00
0.97
FL9V*A12
FC/MC/PC32A
1.01
1.00
0.97
FL9(C,V)*B12
FC/MC/PC35B
1.01
1.00
0.97
FL9(C,V)*B12
HC36
1.01
1.00
0.97
FL8V*B12
HD36
1.01
1.00
0.97
FL9(C,V)*B12
HD36
1.01
1.00
0.97