background image

105564-UIM-A-0205

Unitary Products Group

23

NOTES:

1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m

3

/min).

2. Return air is through side opposite motor (left side).

3. In order to stay within the velocity rating the filters, airflows above 1800 CFM (50.97 m

3

/min) require either return from two sides or one side plus bottom.

4. Motor voltage at 115 V.

5. NR = Operation at this static pressure is not recommended.

FILTER PERFORMANCE

The airflow capacity data published in Table 15 represents blower per-
formance WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the filter being
used or select an appropriate value from the Table 16.

NOTE: 

The filter pressure drop values in Table 16 are typical values for

the type of filter listed and should only be used as a guideline.
Actual pressure drop ratings for each filter type vary between fil-
ter manufacturers.

Washable Fiber Filters are the type supplied with furnace.

TABLE 15: 

Blower Performance CFM

AIRFLOW WITH BOTTOM OR ONE SIDE RETURN

MODELS

Speed

Tap

EXTERNAL STATIC PRESSURE, INCHES W.C. (kPa)

Input/

Airflow/cabinet

0.1 (0.025)

0.2 (0.050)

0.3 (0.075)

0.4 (0.099)

0.5 (0.124)

0.6 (0.149)

0.7 (0.174) 

0.8 (0.199) 

0.9 (0.224)

1.0 (0.249)

CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min

40/1200/A 

HIGH 1635

46

1590

45

1535

43

1480

42

1415

40

1340

39

1280

36

1185

34

NR

NR

NR

NR

M-HI  1245 35

1225 35

1205 34

1185 34

1160

33

1110 31

1065

31

995

28

NR

NR

NR

NR

M-LO  1005 28

1000 28

995

28

975

28

955

27

925

26

885

25

825

23

NR

NR

NR

NR

LOW  775 22

770 22

765

22

750

21

725

21

680

19

655

19

620

18

NR

NR

NR

NR

60/1200/B 
80/1200/B 

HIGH  1650 47 1605 45 1570 44 1525 43 1465 41 1410 40 1350 38 1275 36 1170 33 1060 30 

M-HI  1165 33 1185 34 1175 33 1165 33 1150 33 1140 32 1100 31 1050 30  970  27  875  25 

M-LO  895 25 915 26 935 26 940 27 940 27 920 26 905 26 860 24 815 23 750 21 

LOW  710 20 725 21 725 21 725 21 720 20 700 20 685 19 660 19 625 18 560 16 

80/2000/C

100/2000/C

HIGH 2300

65

2210

63

2120

60

2020

57

1930

55

1830

52

1715

49

1595

45

1480

42

1350

39

M-HI 1950

55

1900

54

1830

52

1755

50

1680

48

1595

45

1500

42

1390

39

1270

36

1155

33

M-LO 1610

46

1545

44

1490

42

1440

41

1390

39

1315

37

1230

33

1155

33

1050

30

920

26

LOW 1325

38

1270

36

1225

35

1175

33

1105

31

1045

30

990

28

905

25

890

25

790

22

80/1600/C 

100/1600/C 

HIGH  1960 56 1955 55 1925 55 1890 54 1830 52 1765 50 1695 48 1615 46 1600 45 1485 42 

M-HI  1565 44 1560 44 1560 44 1575 45 1545 44 1530 43 1475 42 1425 40 1365 39 1260 36 

M-LO  1230 35 1275 36 1285 36 1300 37 1310 37 1300 37 1280 36 1245 35 1190 34 1070 30 

LOW  930 26 945 27 965 27 975 28 975 28 975 28 975 28 950 27 910 26 850 24 

120/2000/D 
135/2000/D

HIGH  2560 72 2485 70 2410 68 2320 66 2220 63 2135 60 2035 58 1920 54 1785 51 1650 47 

M-HI  2090 59 2050 58 1990 56 1970 56 1885 53 1820 52 1760 50 1675 47 1545 44 1405 40 

M-LO  1695 48 1675 47 1665 47 1615 46 1565 44 1510 43 1460 41 1385 39 1285 36 1140 32 

LOW  1175 33 1150 33 1135 32 1110 31 1085 31 1055 30 1005 28  980  28  970  27  845  24 

AIRFLOW WITH TWO SIDE RETURNS OR WITH BOTTOM AND ONE SIDE RETURN

MODELS

Speed

Tap

EXTERNAL STATIC PRESSURE, INCHES W.C. (kPa)

Input/

Airflow/cabinet

0.1 (0.025)

0.2 (0.050)

0.3 (0.075)

0.4 (0.099)

0.5 (0.124)

0.6 (0.149)

0.7 (0.174) 

0.8 (0.199) 

0.9 (0.224)

1.0 (0.249)

CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min CFM  m

3

/min

80/2000/C

100/2000/C

HIGH 2465

70

2380

67

2295

65

2195

62

2095

59

1995

56

1875

53

1760

50

1620

46

1470

42

M-HI 2085

59

2035

58

1960

55

1880

54

1800

51

1705

48

1605

45

1485

42

1360

39

1235

35

M-LO 1725

49

1625

46

1595

45

1540

44

1485

42

1405

40

1315

37

1235

35

1125

32

995

28

LOW 1420

40

1360

39

1310

37

1255

36

1180

33

1120

32

1070

30

970

27

950

27

845

24

120/2000/D 
135/2000/D

HIGH  2615 74 2535 72 2450 69 2385 68 2285 65 2175 62 2075 59 1945 55 1825 52 1670 47 

M-HI  2055 58 2045 58 2015 57 1985 56 1932 55 1855 53 1785 51 1730 49 1605 45 1470 42 

M-LO  1690 48 1650 47 1620 46 1600 45 1570 44 1525 43 1470 42 1395 40 1300 37 1200 34 

LOW  1345 38 1335 38 1335 38 1285 36 1250 35 1230 35 1180 33 1115 32 1010 29  850  24 

TABLE 16: 

Filter Performance - Pressure Drop Inches W.C. and (kPa)

AIRFLOW 

RANGE

MINIMUM OPENING SIZE

FILTER TYPE

DISPOSABLE

WASHABLE FIBERS*

PLEATED

1 Opening

2 Openings

1 Opening

2 Opening

1 Opening

2 Opening

1 Opening

2 Opening

Sq. in.   

m

2

Sq. in.

m

2

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

In w.c.

Pa

0 - 750

230

.15

0.01

2.5

0.01

2.5

0.15

37

751 - 1000

330

.21

0.04

10

0.03

7.5

0.20

50

1001 - 1250

330

.21

0.08

20

0.07

17

0.20

50

1251 - 1500

330

.21

0.08

20

0.07

17

0.25

62

1501 - 1750

380

.25

658

.42

0.14

35

0.08

20

0.13

32

0.06

15

0.30

75

0.17

42

1751 - 2000

380

.25

658

.42

0.17

42

0.09

22

0.15

37

0.07

17

0.30

75

0.17

42

2001  &  Above

463

.30

658

.42

0.17

42

0.09

22

0.15

37

0.07

17

0.30

75

0.17

42

Содержание FC9S

Страница 1: ...8 TWINNING AND STAGING 9 COMBUSTION AIR AND VENT SYSTEM 11 CONDENSATE PIPING 18 SAFETY CONTROLS 18 START UP AND ADJUSTMENTS 19 WIRING DIAGRAM 25 LIST OF FIGURES Dimensions 5 Furnace Base Rectangular Blockoff Panel 6 Gas Valve 6 Gas Piping 6 Electrical Wiring 8 Line Wiring Connections 9 Single Stage Heat Thermostat Connections 9 Single Stage Heating and Two Stage Cooling Thermostat Connections 9 Ac...

Страница 2: ...e ational vehicles Failure to carefully read and follow all instructions in this manual can result in furnace malfunction death personal injury and or property damage Furnaces for installation on combustible flooring shall not be installed directly on carpeting tile or other combustible material other than wood flooring Check the rating plate and power supply to be sure that the elec trical charac...

Страница 3: ... required for passage to the front when servicing or for inspection or replacement of flue vent connections In all cases accessibility clearances shall take precedence over clear ances for combustible materials where accessibility clearances are greater Installation in a residential garage 1 A gas fired furnace for installation in a residential garage must be installed so the burner s and the igni...

Страница 4: ...ssure drop across any applied coil TABLES 2 AND 3 are to be used as a guide only to help the installer determine if the duct sizes are large enough to obtain the proper air flow CFM through the furnace TABLES 2 and 3 ARE NOT to be used to design ductwork for the building where the furnace is being installed There are several variables associated with proper duct sizing that are not included in the...

Страница 5: ... 1 for unit and plenum dimensions Attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility The supply air temperature MUST NEVER exceed the Maximum Supply Air Temperature specified on the nameplate Operating the furnace above the maximum supply air temperature will cause the heat exchanger to overheat causing premature heat exc...

Страница 6: ...uctions in this section specify the type of gas approved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figure 4 IMPORTANT An accessible manual shutoff valve must be installed upstream of the furnace gas controls and within 6 feet 1 8 m of the fur nace The furnace must be isolated from the gas supply piping system by closing its...

Страница 7: ...cing a wrench to the body of the gas valve will damage the valve causing improper operation and or the valve to leak TABLE 5 High Altitude Conversion 40 120 MBTUH Models Type Of Gas Orifice at Sea Level 2 000 ft 610 m 3 000 ft 914 m 4 000 ft 1219 m Natural 45 46 47 47 Propane 55 55 55 55 Type Of Gas 5 000 ft 1524 m 6 000 ft 1829 m 7 000 ft 2134 m 8 000 ft 2438 m Natural 47 48 48 49 Propane 56 56 5...

Страница 8: ...ternate wiring method is to use a field provided 2 5 08 cm x 4 10 2 cm box and cover on the outside of the furnace Route the furnace leads into the box using a protective bushing where the wires pass through the furnace panel After making the wiring connections replace the wiring box cover and screws 3 The furnace s control system requires correct polarity of the power supply and a proper ground c...

Страница 9: ... using the same duct system it is very important that the two furnace cir culating air blowers operate in unison If one blower starts before the second blower the duct system will become pressurized and the blower on the second furnace will turn backwards causing the second furnace to overheat resulting in damage to the furnace Twinning is used to make two furnaces operate in tandem using one duct...

Страница 10: ... then will shut off at the same time Continuous Fan On a thermostat call for continuous fan G signal both furnace blowers will come on at the same time in cooling speed and will stay on until the G signal is removed STAGING In applications where more heating capacity or more airflow capacity is needed than what one furnace can deliver twinning can be used to make two furnaces operate in tandem usi...

Страница 11: ...low a maximum of 5 elbows in the combustion air piping and a maximum of 5 elbows in the vent piping 4 Three vent terminal elbows two for vent pipe and one for air intake pipe are already accounted for as vent termination 5 Combustion air and vent piping must be of the same diameter 6 All combustion air vent pipe and fittings must conform to American National Standards Institute ANSI standards and ...

Страница 12: ...on air systems from the furnace to the out side termination B Ventilated combustion air systems from the furnace to the attic or crawl space termination 6 Disassemble the combustion air and vent piping apply cement primer and the cement per the manufactures instructions Primer and cement must conform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent airtight ...

Страница 13: ...30 kW 36 inches 91 cm for models 100 000 BTUH 30 kW Two pipe direct vent applications 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW Single pipe applications 4 feet C Clearance to permanently closed window 4 Feet 4 Feet D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet 61 cm from the center line of ...

Страница 14: ...combustion air systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 15 or 16 VENTING MULTIPLE UNITS Multiple units can be installed in a space or structure as either a single pipe configuration or a two pipe configuration The combustion air side of the single pipe configuration shown in Figure 20 is referred to in these instruct...

Страница 15: ...ill bring air in from the outdoors to the furnace combustion air intake collar on the burner box The second pipe Shown in Figure 19 is the furnace vent pipe The combustion air intake pipe should be located either through the wall horizontal or side vent or through the roof vertical vent Care should be taken to locate side vented systems where trees or shrubs will not block or restrict supply air f...

Страница 16: ...he louver is in the fully open position This type of installation requires that the supply air to the appli ance s be of a sufficient amount to support all of the appliance s in the area Operation of a mechanical exhaust such as an exhaust fan kitchen ventilation system clothes dryer or fireplace may cre ate conditions requiring special attention to avoid unsatisfactory operation of gas appliances...

Страница 17: ...usage Follow all notes procedures and required materials in the SEALED COMBUS TION AIR SUPPLY section in these instructions when installing the combustion air pipe from the unit and into a ventilated attic space or crawl space DO NOT terminate vent pipe in an Attic or Crawl Space Ventilated Combustion Air Termination Refer to Figure 22 for required attic termination for the combustion air intake p...

Страница 18: ...p pump must be approved for use with acidic condensate CONDENSATE DRAIN TRAP AND DRAIN FREEZE PROTECTION Special precautions MUST be made if installing furnace in an area which may drop below freezing This can cause improper operation or damage to the equipment If the furnace is installed in an area that has the potential of freezing the drain line and the drain trap must be pro tected Use a 3 to ...

Страница 19: ...gth x 1 8 0 3 cm diameter tubing 2 pieces of 4 10 cm length x 1 8 0 3 cm diameter tubing 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 0 3 cm reducing coupling 1 1 8 0 3 cm adapter 1 Dwyer Manometer These items are required in order to properly perform the required star tup procedure IGNITION SYSTEM SEQUENCE 1 Turn the gas supply ON at external valve and main gas valve 2 Set the thermostat above room temp...

Страница 20: ...s 3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the gas meter times a baro metric pressure and temperature correction factor of 0 960 times 3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter The formula for metric input...

Страница 21: ...ll reference atmo spheric pressure Refer to Figure 26 for connection details IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or tightening the cap does not adjust the flow of gas 1 Refer to Figure 25 for location of pressure regulator adjustment cap and adjustment screw on main gas valve 2 Turn gas and electrical supplies on an...

Страница 22: ...ws user selection of the blower speed that is energized during continuous fan operation Place jumper on the HI COOL LO COOL or HEAT pins The blower speed connections shown in Figure 27 are typical How ever these connections may vary from model to model and may be changed as needed to give proper heating and cooling airflow WITH BURNER BOX COVER IN PLACE WITH BURNER BOX COVER REMOVED FIGURE 26 Read...

Страница 23: ... 35 1175 33 1105 31 1045 30 990 28 905 25 890 25 790 22 80 1600 C 100 1600 C HIGH 1960 56 1955 55 1925 55 1890 54 1830 52 1765 50 1695 48 1615 46 1600 45 1485 42 M HI 1565 44 1560 44 1560 44 1575 45 1545 44 1530 43 1475 42 1425 40 1365 39 1260 36 M LO 1230 35 1275 36 1285 36 1300 37 1310 37 1300 37 1280 36 1245 35 1190 34 1070 30 LOW 930 26 945 27 965 27 975 28 975 28 975 28 975 28 950 27 910 26 8...

Страница 24: ... that total system static is 0 58 w c To determine the system airflow complete the follow ing steps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 2285 CFM 64 70 m3 min Airflow 0 60 2175 CFM 61 59 m3 min Subtract the airflow 0 50 w c 125 Pa from the airflow 0 60 w c 150 Pa to obtain airflow difference 2175 2285 110 CFM 3 11 m3 min Subtract the total system static fro...

Страница 25: ...105564 UIM A 0205 Unitary Products Group 25 SECTION XI WIRING DIAGRAM FIGURE 28 Wiring Diagram ...

Страница 26: ...105564 UIM A 0205 26 Unitary Products Group NOTES ...

Страница 27: ...105564 UIM A 0205 Unitary Products Group 27 NOTES ...

Страница 28: ...o change without notice Printed in U S A 105564 UIM A 0205 Copyright by York International Corp 2005 All rights reserved Supersedes 035 20377 002 Rev A 0904 Unitary 5005 Norman Product York OK Group Drive 73069 ...

Отзывы: