background image

105564-UIM-A-0205

Unitary Products Group

11

Single-Wire Staging Operation

Heating - On a call for first-stage heat (W1 signal) from the wall thermo-
stat, Furnace #1 will start the ignition sequence and the burners will
light. About thirty seconds after the burners light, the blowers on both
furnaces will come on in heating speed. When the thermostat is satis-
fied, the burners will shut off and, after the selected blower off delay
time, both blowers will shut off at the same time. On a call for second
stage of heat, the burners of Furnace #2 will also light and both blowers
will run. The twinning control ensures that both blowers come on and
shut off at the same time. 

Cooling - On a call for cooling (Y signal) from the wall thermostat, both
furnace blowers will come on at the same time. When the thermostat is
satisfied, both blowers will stay on for 60 seconds, then will shut off at
the same time. 

Continuous Fan - On a thermostat call for continuous fan (G signal),
both furnace blowers will come on at the same time in cooling speed
and will stay on until the G signal is removed.

SECTION VII: COMBUSTION AIR AND 

VENT SYSTEM

COMBUSTION AIR AND VENT SAFETY

This Category IV, dual certified direct vent furnace is designed for resi-
dential application. It may be installed without modification to the con-
densate system in a basement, garage, equipment room, alcove, attic
or any other indoor location where all required clearance to combusti-
bles and other restrictions are met. The combustion air and the venting
system must be installed in accordance with Section 5.3, Air for Com-
bustion and Ventilation, of the National Fuel Gas Code Z223.1/NFPA 54
(latest edition), or Sections 7.2, 7.3 or 7.4 of CSA B149.1, National Gas
and Propane Codes (latest edition) or applicable provisions of the local
building code and these instructions.

IMPORTANT: 

The “VENT SYSTEM” must be installed as specified in

these instructions for Residential and Non HUD Modular Homes. The
sealed combustion air / vent system is the only configuration that can
be installed in a Non HUD Modular Home.

COMBUSTION AIR/VENT PIPE SIZING

Select the correct size from Table 9. The size will be determined by a
combination of furnace model, total length of run, and the number of
elbows required. The following rules must also be observed.

1.

Long radius (sweep) elbows are required for all units.

2.

Elbows are assumed to be 90 degrees. Two 45-degree elbows
count as one 90-degree elbow.

3.

Elbow count refers to combustion air piping and vent piping sepa-
rately. For example, if the table allows for 5 elbows, this will allow a
maximum of 5 elbows in the combustion air piping and a maximum
of 5 elbows in the vent piping.

4.

Three vent terminal elbows (two for vent pipe and one for air
intake pipe) are already accounted for as vent termination.

5.

Combustion air and vent piping must be of the same diameter.

6.

All combustion air/vent pipe and fittings must conform to American
National Standards Institute (ANSI) standards and American Soci-
ety for Testing and Materials (ASTM) standards D1785 (Schedule
40 PVC), D2665 (PVC-DWV), F891 (PVC-DWV Cellular Core).
D2241 (SDR-21 and SDR-26 PVC), D2261 (ABS-DWV), or F628
(Schedule 40 ABS. Pipe cement and primer must conform to
ASTM Standards D2564 (PVC) or D2235 (ABS).

7.

The use of flexible connectors or no hub connectors in the vent
system is not allowed. This type connection is allowed in the com-
bustion air pipe near the furnace for air conditioning coil accessibil-
ity.

8.

Sidewall horizontal vent terminals and roof mounted vertical termi-
nals may be field fabricated. Standard PVC/SRD fittings may be
used. Terminal configuration must comply as detailed in this sec-
tion.

IMPORTANT: 

Accessory concentric vent / intake termination kits

1CT0302 and 1CT0303 are available and approved for use with these
furnaces. Horizontal sidewall vent terminations kit 1HT0901 is also
approved for use with these furnaces.

IMPORTANT: 

Intake and vent pipe connections are sized as shown

above. However, some models require larger vents and some installa-
tions will require larger intake piping. Use Table 9 for the sizes of the
pipe that can be used with each model.

 FIGURE 12:  

Two-Stage Twinning Wiring Diagram

 This furnace may not be common vented with any other appliance,
since it requires separate, properly sized air intake and vent lines.
The furnace shall not be connected to any type of B, BW or L vent
or vent connector, and not connected to any portion of a factory-
built or masonry chimney
The furnace shall not be connected to a chimney flue serving a sep-
arate appliance designed to burn solid fuel.

W

G

C

R

Y/Y2

TWIN

TO A/C

WALL THERMOSTAT

W1

G

R

Y

ISOLATION

RELAY

FURNACE 2 CONTROL BOARD

W

G

C

R

Y/Y2

TWIN

FURNACE 1 CONTROL BOARD

W2

When combustion air pipe is installed above a suspended ceiling or
when it passes through a warm and humid space, the pipe must be
insulated with 1/2” Armaflex or other heat resistant type insulation if
two feet or more of pipe is exposed.
Vent piping must be insulated if it will be subjected to freezing tem-
peratures such as routing through unheated areas or through an
unused chimney.

TABLE 8: 

Combustion Air Intake and Vent Connection Size at Furnace 

(All Models)

FURNACE VENT CONNECTION SIZES

Furnace Input

40 - 100 MBH 

(17.5-29.3 kW)

120-135 MBH

(35.2-39.6 kW)

Intake Pipe Size

2” (5.1 cm)

3” (7.6 cm)

Vent Pipe Size

2” (5.1 cm)

2” (5.1 cm)

Содержание FC9S

Страница 1: ...8 TWINNING AND STAGING 9 COMBUSTION AIR AND VENT SYSTEM 11 CONDENSATE PIPING 18 SAFETY CONTROLS 18 START UP AND ADJUSTMENTS 19 WIRING DIAGRAM 25 LIST OF FIGURES Dimensions 5 Furnace Base Rectangular Blockoff Panel 6 Gas Valve 6 Gas Piping 6 Electrical Wiring 8 Line Wiring Connections 9 Single Stage Heat Thermostat Connections 9 Single Stage Heating and Two Stage Cooling Thermostat Connections 9 Ac...

Страница 2: ...e ational vehicles Failure to carefully read and follow all instructions in this manual can result in furnace malfunction death personal injury and or property damage Furnaces for installation on combustible flooring shall not be installed directly on carpeting tile or other combustible material other than wood flooring Check the rating plate and power supply to be sure that the elec trical charac...

Страница 3: ... required for passage to the front when servicing or for inspection or replacement of flue vent connections In all cases accessibility clearances shall take precedence over clear ances for combustible materials where accessibility clearances are greater Installation in a residential garage 1 A gas fired furnace for installation in a residential garage must be installed so the burner s and the igni...

Страница 4: ...ssure drop across any applied coil TABLES 2 AND 3 are to be used as a guide only to help the installer determine if the duct sizes are large enough to obtain the proper air flow CFM through the furnace TABLES 2 and 3 ARE NOT to be used to design ductwork for the building where the furnace is being installed There are several variables associated with proper duct sizing that are not included in the...

Страница 5: ... 1 for unit and plenum dimensions Attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility The supply air temperature MUST NEVER exceed the Maximum Supply Air Temperature specified on the nameplate Operating the furnace above the maximum supply air temperature will cause the heat exchanger to overheat causing premature heat exc...

Страница 6: ...uctions in this section specify the type of gas approved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figure 4 IMPORTANT An accessible manual shutoff valve must be installed upstream of the furnace gas controls and within 6 feet 1 8 m of the fur nace The furnace must be isolated from the gas supply piping system by closing its...

Страница 7: ...cing a wrench to the body of the gas valve will damage the valve causing improper operation and or the valve to leak TABLE 5 High Altitude Conversion 40 120 MBTUH Models Type Of Gas Orifice at Sea Level 2 000 ft 610 m 3 000 ft 914 m 4 000 ft 1219 m Natural 45 46 47 47 Propane 55 55 55 55 Type Of Gas 5 000 ft 1524 m 6 000 ft 1829 m 7 000 ft 2134 m 8 000 ft 2438 m Natural 47 48 48 49 Propane 56 56 5...

Страница 8: ...ternate wiring method is to use a field provided 2 5 08 cm x 4 10 2 cm box and cover on the outside of the furnace Route the furnace leads into the box using a protective bushing where the wires pass through the furnace panel After making the wiring connections replace the wiring box cover and screws 3 The furnace s control system requires correct polarity of the power supply and a proper ground c...

Страница 9: ... using the same duct system it is very important that the two furnace cir culating air blowers operate in unison If one blower starts before the second blower the duct system will become pressurized and the blower on the second furnace will turn backwards causing the second furnace to overheat resulting in damage to the furnace Twinning is used to make two furnaces operate in tandem using one duct...

Страница 10: ... then will shut off at the same time Continuous Fan On a thermostat call for continuous fan G signal both furnace blowers will come on at the same time in cooling speed and will stay on until the G signal is removed STAGING In applications where more heating capacity or more airflow capacity is needed than what one furnace can deliver twinning can be used to make two furnaces operate in tandem usi...

Страница 11: ...low a maximum of 5 elbows in the combustion air piping and a maximum of 5 elbows in the vent piping 4 Three vent terminal elbows two for vent pipe and one for air intake pipe are already accounted for as vent termination 5 Combustion air and vent piping must be of the same diameter 6 All combustion air vent pipe and fittings must conform to American National Standards Institute ANSI standards and ...

Страница 12: ...on air systems from the furnace to the out side termination B Ventilated combustion air systems from the furnace to the attic or crawl space termination 6 Disassemble the combustion air and vent piping apply cement primer and the cement per the manufactures instructions Primer and cement must conform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent airtight ...

Страница 13: ...30 kW 36 inches 91 cm for models 100 000 BTUH 30 kW Two pipe direct vent applications 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW Single pipe applications 4 feet C Clearance to permanently closed window 4 Feet 4 Feet D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet 61 cm from the center line of ...

Страница 14: ...combustion air systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 15 or 16 VENTING MULTIPLE UNITS Multiple units can be installed in a space or structure as either a single pipe configuration or a two pipe configuration The combustion air side of the single pipe configuration shown in Figure 20 is referred to in these instruct...

Страница 15: ...ill bring air in from the outdoors to the furnace combustion air intake collar on the burner box The second pipe Shown in Figure 19 is the furnace vent pipe The combustion air intake pipe should be located either through the wall horizontal or side vent or through the roof vertical vent Care should be taken to locate side vented systems where trees or shrubs will not block or restrict supply air f...

Страница 16: ...he louver is in the fully open position This type of installation requires that the supply air to the appli ance s be of a sufficient amount to support all of the appliance s in the area Operation of a mechanical exhaust such as an exhaust fan kitchen ventilation system clothes dryer or fireplace may cre ate conditions requiring special attention to avoid unsatisfactory operation of gas appliances...

Страница 17: ...usage Follow all notes procedures and required materials in the SEALED COMBUS TION AIR SUPPLY section in these instructions when installing the combustion air pipe from the unit and into a ventilated attic space or crawl space DO NOT terminate vent pipe in an Attic or Crawl Space Ventilated Combustion Air Termination Refer to Figure 22 for required attic termination for the combustion air intake p...

Страница 18: ...p pump must be approved for use with acidic condensate CONDENSATE DRAIN TRAP AND DRAIN FREEZE PROTECTION Special precautions MUST be made if installing furnace in an area which may drop below freezing This can cause improper operation or damage to the equipment If the furnace is installed in an area that has the potential of freezing the drain line and the drain trap must be pro tected Use a 3 to ...

Страница 19: ...gth x 1 8 0 3 cm diameter tubing 2 pieces of 4 10 cm length x 1 8 0 3 cm diameter tubing 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 0 3 cm reducing coupling 1 1 8 0 3 cm adapter 1 Dwyer Manometer These items are required in order to properly perform the required star tup procedure IGNITION SYSTEM SEQUENCE 1 Turn the gas supply ON at external valve and main gas valve 2 Set the thermostat above room temp...

Страница 20: ...s 3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the gas meter times a baro metric pressure and temperature correction factor of 0 960 times 3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter The formula for metric input...

Страница 21: ...ll reference atmo spheric pressure Refer to Figure 26 for connection details IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or tightening the cap does not adjust the flow of gas 1 Refer to Figure 25 for location of pressure regulator adjustment cap and adjustment screw on main gas valve 2 Turn gas and electrical supplies on an...

Страница 22: ...ws user selection of the blower speed that is energized during continuous fan operation Place jumper on the HI COOL LO COOL or HEAT pins The blower speed connections shown in Figure 27 are typical How ever these connections may vary from model to model and may be changed as needed to give proper heating and cooling airflow WITH BURNER BOX COVER IN PLACE WITH BURNER BOX COVER REMOVED FIGURE 26 Read...

Страница 23: ... 35 1175 33 1105 31 1045 30 990 28 905 25 890 25 790 22 80 1600 C 100 1600 C HIGH 1960 56 1955 55 1925 55 1890 54 1830 52 1765 50 1695 48 1615 46 1600 45 1485 42 M HI 1565 44 1560 44 1560 44 1575 45 1545 44 1530 43 1475 42 1425 40 1365 39 1260 36 M LO 1230 35 1275 36 1285 36 1300 37 1310 37 1300 37 1280 36 1245 35 1190 34 1070 30 LOW 930 26 945 27 965 27 975 28 975 28 975 28 975 28 950 27 910 26 8...

Страница 24: ... that total system static is 0 58 w c To determine the system airflow complete the follow ing steps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 2285 CFM 64 70 m3 min Airflow 0 60 2175 CFM 61 59 m3 min Subtract the airflow 0 50 w c 125 Pa from the airflow 0 60 w c 150 Pa to obtain airflow difference 2175 2285 110 CFM 3 11 m3 min Subtract the total system static fro...

Страница 25: ...105564 UIM A 0205 Unitary Products Group 25 SECTION XI WIRING DIAGRAM FIGURE 28 Wiring Diagram ...

Страница 26: ...105564 UIM A 0205 26 Unitary Products Group NOTES ...

Страница 27: ...105564 UIM A 0205 Unitary Products Group 27 NOTES ...

Страница 28: ...o change without notice Printed in U S A 105564 UIM A 0205 Copyright by York International Corp 2005 All rights reserved Supersedes 035 20377 002 Rev A 0904 Unitary 5005 Norman Product York OK Group Drive 73069 ...

Отзывы: