Johnson Controls Unitary Products
TABLE 3:
Physical and Electrical Data
Models F*FP
024
030
036
040
Blower - Diameter x Width
10 x 6
10 x 8
10 x 8
10 x 8
Motor
HP
1/4
1/3
1/2
1/3
Nominal RPM
1075
1075
1075
1075
Voltage
208/230
Amps
Full Load (208/230)
1.6/1.4 (50 Hz:2.1)
2.5 / 2.2
3.3/2.9 (50 Hz:2.3)
2.5 / 2.2
Locked Rotor (208/230)
3.3 / 2.9
6.2 / 5.5
7.4 / 6.5
6.2 / 5.5
Filter
1
Type
DISPOSABLE OR PERMANENT
Size
16 x 20 x 1
16 x 20 x 1
20 x 20 x 1
20 x 20 x 1
Permanent Type Kit
1PF0601BK
1PF0601BK
1PF0602BK
1PF0602BK
Shipping / Operating Weight (lbs.)
98 / 93
105 / 100
115 / 109
121 / 115
Models F*FP
042
045
048
060
Blower - Diameter x Width
10x8
10x10
11x10
11x10
Motor
HP
3/4
1/3
1.0
1.0
Nominal RPM
1130
925
1050
1050
Voltage
208/230
230
Amps
Full Load (208/230)
4.4/3.8
3.0/2.7
7.6
7.6
Locked Rotor (208/230)
11.9/10.3
4.8/4.1
NA
NA
Filter
1
Type
DISPOSABLE OR PERMANENT
Size
20 x 20 x 1
22 x 20 x 1
22 x 20 x 1
22 x 20 x 1
Permanent Type Kit
1PF0602BK
1PF0603BK
1PF0603BK
1PF0603BK
Shipping / Operating Weight (lbs.)
121/115
150/144
153/147
160/154
1. Field Supplied
TABLE 4:
Electrical Data - Cooling Only (50 & 60 Hz)
Models F*FP
Total Motor Amps
Minimum Circuit Ampacity
Max. O.C.P.
1
Amps/Type
Minimum Wire
Size A.W.G.
60 Hertz
60 Hertz
208V
240V
208V
240V
024
1.6
1.5
2.0
1.8
15
14
030
2.5
2.3
3.2
2.8
15
14
036
3.3
3.0
4.2
3.7
15
14
040
2.5
2.3
3.2
2.8
15
14
042
4.4
4.0
5.5
4.8
15
14
045
3.1
2.6
3.9
3.4
15
14
048
7.6
7.6
9.5
9.5
15
14
060
7.6
7.6
9.5
9.5
15
14
1.
OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
TABLE 5:
Conversion Table
KW & MBH Conversions - for Total Power Input Requirement
FOR
208V
OPERATION MULTIPLY
240V
TABULATED KW & MBH BY
.751
230V
240V
.918
220V
240V
.840