150
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
Parameter Description and Options
MENU ITEM
DEFINITION
OUTSIDE AIR HUMIDITY
THIS PARAMETER GIVES THE CURRENT VALUE OF THE
OUTSIDE AIR HUMIDITY INPUT
OUTSIDE AIR HUMIDITY SENSOR INSTALLED
THIS PARAMETERS IDENTIFIES TO THE UNIT CONTROLLER
THAT AN OUTDOOR AIR HUMIDITY SENSOR IS INSTALLED
OUTSIDE AIR TEMP
THIS PARAMETER GIVES THE CURRENT VALUE FOR THE
OUTDOOR AIR TEMPERATURE INPUT
POWER EXHAUST INSTALLED
THIS PARAMETER MUST BE TURNED ON TO ENABLE POWER
EXHAUST OPERATION
PRE-OCCUPANCY PURGE ENABLE
THIS PARAMETER IS USED TO TURN ON THE PRE-OCCUPANCY
PURGE OPTION. THIS FEATURE TURNS ON THE SUPPLY FAN
AND OPENS THE OUTDOOR AIR DAMPER PRIOR TO GOING
INTO THE OCCUPIED MODE.
PRE-OCCUPANCY PURGE TIME (HOURS OF
DAY)
THIS PARAMETER ESTABLISHES THE NUMBER OF HOURS
PRIOR TO THE OCCUPIED START TIME THAT THE PRE-
OCCUPANCY PURGE WOULD START
PRE-OCCUPANCY PURGE TIME (MINUTES OF
DAY)
THIS PARAMETER ESTABLISHES THE NUMBER OF MINUTES
PRIOR TO THE OCCUPIED START TIME THAT THE PRE-
OCCUPANCY PURGE WOULD START
PURGE SWITCH
THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL
PURGE - PURGE MODE
REDLINE
THIS FEATURE CAN BE USED TO TEMPORALLY REDUCE THE
ELECTRICAL CONSUMPTION OF THE UNIT BY TURNING OFF
SOME OF THE ACTIVE COMPRESSORS. THIS FEATURE IS ONLY
AVAILABLE THROUGH A COMMUNICATED INPUT.
REMOTE CONTROL INPUT ENABLE FOR THIRD
PARTY BAS
THIS ALLOWS THE USE OF AN EXTERNAL 0 TO 10 VDC SIGNAL
TO RESET THE SUPPLY AIR TEMPERATURE SETPOINT ON VAV
UNITS.
REMOTE CONTROL INPUT VALUE
GIVES THE VALUE OF THE 0 TO 10 VDC REMOTE CONTROL
INPUT FOR THE REMOTE CONTROL OF THE DAMPERS
RETURN AIR ENTHALPY
THIS PARAMETER IS THE CALCULATED VALUE FOR THE
RETURN AIR ENTHALPY
RETURN AIR HUMIDITY
THIS PARAMETER GIVES THE CURRENT VALUE OF THE
RETURN AIR HUMIDITY INPUT
RETURN AIR HUMIDITY SENSOR INSTALLED
THIS IS THE RETURN ENTHALPY SETTING WHICH THE UNIT
CONTROLLER USES TO DETERMINE WHEN TO SWITCH INTO
ECONOMIZER OPERATION IN DUAL ENTHALPY ECONOMIZER
MODE
RETURN AIR TEMP
THIS PARAMETER GIVE THE CURRENT VALUE FOR THE
RETURN AIR TEMPERATURE INPUT
RUN TEST
BY TURNING THIS FEATURE ON THE UNIT CONTROLLER
SEQUENCING ON ALL THE BINARY OUTPUTS TO VERIFY
OPERATION OF THE UNIT ELECTRICAL DEVICES
SENSOR SPACE TEMPERATURE SENSOR
OUTSET
THIS IS THE ACTUAL SPACE SENSOR OFFSET AMOUNT BEING
USED BY THE UNIT CONTROLLER IN DEGREES.
TABLE 7-1 – DEFINITIONS (CONTINUED)
Continued on next page
Содержание ECO2 YPAL 050
Страница 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...105 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 Left click on Software 3 Left click on software LD13037...
Страница 112: ...112 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center SENSOR READINGS LD13017...
Страница 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Страница 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Страница 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Страница 116: ...116 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center COOLING STATUS LD13021...
Страница 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Страница 118: ...118 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center HEATING STATUS LD13023...
Страница 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Страница 120: ...120 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center OUTPUTS STATUS LD13025...
Страница 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Страница 122: ...122 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center GRAPHIC CLOCK LD13027 LD13028...
Страница 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...