130
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
User Interface Control Center
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
00 H
0 H
NA
20
NA
NA
DEVICE ID = 20 FOR ELITE
00 L
0 L
NA
-
0
255
DEVICE SOFTWARE REVISION
01 H
1 H
NA
54
-
-
OPTION BYTE #1
0
BITS 1 AND 0 = 0,0 RESPECTIVELY THERE ARE 0 STAGES OF
HEAT; 0,1 = 1 STAGE; 1,0 = 2 STAGES; 1,1 = 3 STAGES
1
2
1 = HEATING MODE ENABLED FOR OPERATION
3
1 = TURN OFF CONTINUOUS FAN WHEN STARTING HEAT
4
1 = COOLING MODE ENABLED FOR OPERATION
5
1 = ECONOMIZER LOADING ACTIVE
6
1 = SPACE SENSOR FAULT OVERRIDE ENABLED
7
NA
01 L
1 L
NA
NA
NA
NA
ACTIVE ALARM
02 H
2 H
NA
30
0
30
FAN ON DELAY FOR HEAT (SECONDS)
02 L
2 L
NA
60
0
255
FAN OFF DELAY FOR HEAT (SECONDS)
03 H
3 H
NA
0
0
30
FAN ON DELAY FOR COOL (SECONDS)
03 L
3 L
NA
30
0
255
FAN OFF DELAY FOR COOL (SECONDS)
04 L
4 L
NA
3
1
10
MINIMUM RUN TIME FOR COMPRESSORS (MINUTES)
05 H
5 H
NA
0
0
255
HEATING #1 ACCUMULATED RUN TIME (HOURS, HIGH BYTE)
05 L
5 L
NA
0
0
255
HEATING #1 ACCUMULATED RUN TIME (HOURS, LOW BYTE)
06 H
6 H
NA
0
0
255
HEATING #2 ACCUMULATED RUN TIME (HOURS, HIGH BYTE)
06 L
6 L
NA
0
0
255
HEATING #2 ACCUMULATED RUN TIME (HOURS, LOW BYTE)
07 H
7 H
NA
0
0
255
HEATING #3 ACCUMULATED RUN TIME (HOURS, HIGH BYTE)
07 L
7 L
NA
0
0
255
HEATING #3 ACCUMULATED RUN TIME (HOURS, LOW BYTE)
08 H - 14 L
8 H - 20 L
NA
REGISTERS 8 - 20 STORE THE UNIT NAME. WHEN WRITTEN,
ALL 13 REGISTERS (AT 2 BYTES PER REGISTER) SHOULD BE
WRITTEN. THE FORMAT IS ASCII. CHARACTER #1 IS IN 8 H.
CHARACTER #2 IS IN 8 L. CHARACTER #3 IS IN 9 H, AND SO ON.
15 H
21 H
NA
-
-
-
INPUT STATUS BYTE #1
0
1 = Y1 ON (COOLING 1ST STAGE)
1
1 = Y2 ON (COOLING 2ND STAGE)
2
1 = Y3 ON (COOLING 3RD STAGE)
3
1 = Y4 ON (COOLING 4TH STAGE)
4
1 = W1 ON (HEATING 1ST STAGE)
TABLE 6-2 - SIMPLICITY ELITE DATA MAP
Continued on next page
Writing to any register not in this list
may cause erratic operation
This product is not designed to accept
continuous writes to data stored in
long term memory. It is recommended
that no stored value be changed more
often than an average of once per
hour. Changing data more often risks
damaging the ability of the control to
store new data for the full life of the
product.
Содержание ECO2 YPAL 050
Страница 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...105 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 Left click on Software 3 Left click on software LD13037...
Страница 112: ...112 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center SENSOR READINGS LD13017...
Страница 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Страница 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Страница 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Страница 116: ...116 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center COOLING STATUS LD13021...
Страница 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Страница 118: ...118 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center HEATING STATUS LD13023...
Страница 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Страница 120: ...120 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center OUTPUTS STATUS LD13025...
Страница 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Страница 122: ...122 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center GRAPHIC CLOCK LD13027 LD13028...
Страница 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...