Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
EABD-F024S
EVAPORATOR COIL MODEL NO
FC/MC/PC/UC24
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
600
800
1000
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
26.5
2.1
3.7
21.7
0.7
8.8
25.5
1.9
3.9
70
25.6
2.1
3.5
20.7
1.1
6.3
25.4
2.0
3.7
80
24.6
2.2
3.3
19.7
1.6
3.7
25.2
2.1
3.5
47
60
23.4
1.8
3.7
18.4
1.3
4.1
22.4
1.7
3.8
70
22.3
1.9
3.5
17.3
1.0
5.6
22.3
1.8
3.6
80
21.1
1.9
3.2
16.3
0.7
7.0
22.2
1.9
3.5
40
60
20.4
1.7
3.5
16.4
1.2
3.9
20.7
1.6
3.7
70
19.3
1.8
3.2
15.3
1.3
3.5
20.4
1.7
3.5
80
18.2
1.8
2.9
14.1
1.3
3.1
20.2
1.8
3.4
30
60
18.8
1.6
3.4
13.8
1.2
3.4
19.0
1.5
3.6
70
16.9
1.6
3.0
12.7
1.2
3.1
17.8
1.6
3.3
80
15.0
1.7
2.6
11.7
1.2
2.8
16.6
1.6
3.0
17
60
13.3
1.5
2.6
10.0
1.1
2.6
15.3
1.4
3.1
70
11.4
1.5
2.2
9.0
1.1
2.3
13.0
1.5
2.6
80
9.5
1.6
1.8
8.0
1.2
2.0
10.8
1.5
2.0
10
60
12.0
1.5
2.4
8.9
1.1
2.3
11.8
1.4
2.5
70
9.6
1.5
1.9
8.0
1.1
2.1
10.0
1.5
2.0
80
7.2
1.6
1.4
7.0
1.2
1.8
8.2
1.5
1.6
NOTE:
ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
MA08B
FC/MC24B
1.00
1.00
1.00
MA08B
FC/MC30B
1.00
1.00
1.00
AHP24
–
1.00
1.00
1.00
F*FP030
–
1.00
1.00
1.00
MV12B
FC/MC24B
0.97
0.93
0.90
MV12B
FC/MC30B
0.97
0.93
0.90
AV24
–
0.97
0.93
0.90
–
FC/MC/PC/UC30
1.00
1.00
1.00
–
HC30
1.00
1.01
1.01
–
HD24
1.00
1.00
1.00
Variable Speed
Furnace
Coil
MBH
KW
COP
(F,L)L8VA12
FC/MC/PC24A
0.97
0.96
0.93
FL9VA12
FC/MC/PC24A
0.97
0.96
0.93
FL9(C,V)B12
FC/MC/PC24B
0.97
0.96
0.93
(F,L)L8VA12
FC/MC/PC30A
0.97
0.96
0.93
FL9VA12
FC/MC/PC30A
0.97
0.96
0.93
FL9(C,V)B12
FC/MC/PC30B
0.97
0.96
0.93
(F,L)L8VA12
HC30
1.00
1.01
1.01
FL9VA12
HC30
1.00
1.01
1.01
(F,L)L8VA12
HD30
0.97
0.96
0.93
FL9VA12
HD30
0.97
0.96
0.93