All dimensions are in inches. They are subject to change with-
out notice. Certified dimensions will be provided upon request.
Physical and Electrical Data - 3 Phase
MODEL
EABD-
T030S
EABD-
T036S
EABD-
T042S
EABD-
T048S
EABD-
T060S
EABD-
W030S
EABD-
W036S
EABD-
W042S
EABD-
W048S
EABD-
W060S
Unit Supply Voltage
208-230V, 3
φ,
60Hz
460V, 3
φ,
60Hz
Normal Voltage Range
1
187 to 252
432 to 532
Minimum Circuit Ampacity
12.1
14.3
14.4
20.2
23.1
5.6
6.9
7.2
9.5
11.2
Max. Overcurrent Device Amps
2
20
20
20
35
40
15
15
15
15
15
Min. Overcurrent Device Amps
3
15
15
15
25
25
15
15
15
15
15
Compressor Type
Recip
Recip
Recip
Scroll
Scroll
Recip
Recip
Recip
Scroll
Scroll
Compressor Amps
Rated Load
8.5
10.2
10.4
15.0
16
3.9
4.9
6.1
6.1
8
Locked Rotor
62
72
71
95
123
30
45
45
45
70
Crankcase Heater
Yes
Yes
Yes
No
No
Yes
Yes
Yes
No
No
Fan Motor Amps
Rated Load
1.5
1.5
1.5
1.5
1.5
0.7
0.7
0.7
0.7
0.7
Fan Diameter Inches
22
22
22
24
24
22
22
22
24
24
Fan Motor
Rated HP
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
Nominal RPM
850
850
850
850
850
850
850
850
850
850
Nominal CFM
3450
3500
3500
3400
3500
3450
3500
3500
3400
3500
Coil
Face Area Sq. Ft.
20.96
23.58
23.58
24.00
27.00
20.96
23.58
23.58
24.00
27.00
Rows Deep
1
1
1
2
2
1
1
1
2
2
Fin / Inches
22
22
22
18
18
22
22
22
18
18
Liquid Line Set OD (Field Installed)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapor Line Set OD (Field Installed)
7/8
7/8
7/8
7/8
1-1/8
7/8
7/8
7/8
7/8
1-1/8
Unit Charge (Lbs. - Oz.)
4
8 - 7
8 - 7
8 - 7
12 - 8
16 - 7
8 - 7
8 - 7
8 - 7
12 - 8
16 - 7
Charge Per Foot, Oz.
0.70
0.70
0.70
0.70
0.76
0.70
0.70
0.70
0.70
0.78
Operating Weight Lbs.
196
208
208
250
294
196
208
208
250
294
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value. If line exceeds 25
feet, you may refer to publications software 036-68001-001 for proper line sizing.
C
B
A
DIMENSIONS
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1. Including Fan Guard.
* Adapter fitting required for 1-1/8” line set.
B
C
Liquid
Vapor
030
35
37
27
3/8”
7/8”
036
39
37
27
042
39
37
27
048
34
43
32
060
38
43
32
7/8”*