TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2500
1059
1560
1077
1590
1095
1630
1114
1650
1134
1660
1158
1685
1181
1720
2400
1032
1405
1054
1470
1074
1525
1094
1560
1116
1595
1140
1620
1167
1640
2300
1005
1260
1024
1275
1049
1370
1069
1440
1090
1475
1116
1505
1142
1535
2200
980
1160
1002
1170
1022
1190
1044
1250
1066
1350
1090
1410
1117
1440
2100
930
1060
957
1070
983
1080
1010
1100
1039
1160
1064
1260
1092
1340
2000
877
950
908
975
941
1000
976
1020
1009
1050
1040
1100
1070
1225
1900
-
-
-
-
894
885
940
940
980
980
1014
1020
1047
1095
1800
-
-
-
-
855
815
903
860
950
905
988
940
1022
970
1700
-
-
-
-
-
-
884
815
925
850
964
880
1001
910
1600
-
-
-
-
-
-
864
770
908
805
948
835
987
870
1500
-
-
-
-
-
-
-
-
882
740
926
780
965
830
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2400
1193
1665
-
-
-
-
-
-
-
-
-
-
-
-
2300
1170
1580
1202
1620
-
-
-
-
-
-
-
-
-
-
2200
1148
1480
1180
1530
-
-
-
-
-
-
-
-
-
-
2100
1121
1385
1155
1425
1190
1475
-
-
-
-
-
-
-
-
2000
1100
1285
1133
1340
1169
1385
1205
1445
-
-
-
-
-
-
1900
1079
1180
1110
1240
1143
1280
1178
1330
1222
1375
-
-
-
-
1800
1058
1060
1090
1135
1122
1190
1158
1240
1196
1295
-
-
-
-
1700
1035
960
1071
1030
1103
1100
1134
1140
1164
1175
1197
1205
-
-
1600
1020
900
1056
965
1088
1035
1118
1065
1145
1105
1170
1130
1198
1150
1500
1004
860
1038
880
1070
925
1101
980
1130
1045
1158
1075
1184
1110
0.60
0.70
0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
2
0.20
0.30
0.40
0.50
UNIT
TONNAGE
AIR
FLOW
CFM
5
1
UNIT
TONNAGE
AIR
FLOW
CFM
5
1
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
2
0.90
1.00
1.10
1.20
1.30
1.40
1.50
1. Models shown at 230/460 Volts with side duct connections.
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (3-5 TON) SIDE DUCT APPLICATION
UNIT
TONNAGE
MOTOR
SPEED
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
3
2
HI
1535
320
1493
335
1452
349
1416
363
1377
376
1340
390
1299
403
1260
417
1219
430
MED/HI
1444
263
1398
276
1355
290
1315
303
1271
316
1227
329
1179
343
1125
358
1053
374
MED
1300
208
1254
221
1211
234
1166
246
1119
258
1070
272
1006
288
939
303
897
313
MED/LOW 1197
171
1149
183
1102
195
1050
207
996
220
930
235
869
248
-
-
-
-
LOW
1049
130
968
134
908
145
838
158
-
-
-
-
-
-
-
-
-
-
4
2
HI
2056
636
2017
696
1978
714
1942
734
1906
749
1864
764
1815
769
1728
743
1582
685
MED/HI
1866
539
1832
557
1795
571
1754
585
1722
602
1679
619
1636
638
1582
653
1508
639
MED
1680
408
1641
426
1594
438
1558
455
1517
472
1469
490
1415
505
1370
521
1337
536
MED/LOW 1582
362
1541
380
1495
391
1465
406
1426
423
1377
440
1326
455
1292
469
1247
485
LOW
1300
223
1258
237
1202
247
-
-
-
-
-
-
-
-
-
-
-
-
5
2
HI
2256
883
2258
931
2247
950
2223
964
2182
979
2125
971
2044
940
1958
898
1864
854
MED/HI
2145
771
2127
784
2119
808
2089
826
2051
844
2014
859
1965
861
1896
843
1801
806
MED
2020
637
1999
656
1985
675
1947
696
1910
715
1876
730
1832
740
1793
756
1725
748
MED/LOW 1757
413
1713
432
1677
451
1639
468
1597
479
1559
497
1521
513
1472
523
-
-
LOW
1570
327
1536
339
1499
356
-
-
-
-
-
-
-
-
-
-
-
-
1. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.
2. Side Duct application (230 Volts)