TROUBLESHOOTING
Alarm
Code
Abnormality of Thermistor for Indoor Unit Inlet Air Temperature
(Inlet Air Thermistor)
l
The RUN indicator (red) flashes.
l
The indoor unit number (refrigerant cycle number - address number), the alarm code, the model code
1
,
the model name
1
and the number of connected indoor units are displayed on the LCD. The indoor unit
number and the alarm code are displayed on the 7-segment display of the outdoor unit PCB.
Note 1: Except for some models.
This alarm code is displayed when a short (0.24kΩ or less) or open sensor (840kΩ or more) is detected
during a heating or cooling operation. The operation automatically restarts when the malfunction is
removed.
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Failure of
Inlet Air
Thermistor
Check resistance.
Replace thermistor
if faulty.
Failure
Check connection.
Correctly connect wires.
Incorrect Connection
Replace I.U. PCB
and check operation.
Replace I.U. PCB
if faulty.
Failure of I.U. PCB
Thermistor for
Air Inlet Temperature
● High Static Type: (H,Y)IDH018 - 048B21S
● Medium Static Type: (H,Y,C)IDM006 - 048B21S
● Slim Type: (H,Y,C)IDS006 - 018B21S
Thermistor for
Air Inlet Temperature
Thermistor for
Air Inlet Temperature
Yes
Yes
Connect them.
No
Failure of
Thermistor
Failure of I.U. PCB
No
Is thermistor THM1
(for inlet air temp.)
connected to THM1
of I.U. PCB?
Is resistance of THM1
between 0.24k
Ω
and
840k
Ω
?
Содержание CIDH018B21S
Страница 2: ......
Страница 10: ...viii SM 18001 rev 1...
Страница 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Страница 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Страница 22: ......
Страница 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Страница 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Страница 76: ...MAINTENANCE 4 2 SM 18001 rev 1 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit...
Страница 130: ......
Страница 131: ...SM 18001 rev 1 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting...
Страница 172: ......
Страница 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Страница 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Страница 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Страница 184: ...SERVICE PARTS LIST 7 2 SM 18001 rev 1 Refer to the Service Parts List for Ducted High Static Medium Static and Slim...
Страница 185: ......
Страница 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...